Plan Review Details - Permit 07011124
Plan Review Stops For Permit 07011124
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-07 Cont ID  
Sent By jjohnsto Date 2007-11-07 Time 17:59 Rev Time 1.00
Received By jjohnsto Date 2007-11-07 Time 17:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-12 Cont ID  
Sent By jwitmer Date 2007-09-12 Time 16:19 Rev Time 1.11
Received By jwitmer Date 2007-09-12 Time 16:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-27 Cont ID  
Sent By jwitmer Date 2007-02-27 Time 13:51 Rev Time 4.44
Received By jwitmer Date 2007-02-27 Time 13:37 Sent To  
Notes
2007-02-27 13:54:42BUILDING PLAN REVIEW
 PERMIT: 07011124
 ADD: 901 45TH ST / ST. MARY'S MEDICAL CENTER CONT:
 OVERLAND CONSTRUCTION
 TEL: (561)683-3210
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)BRIDGE DESIGN ASSOCIATES SHEET SK-1 ROOF EQUIPMENT
 CONNECTION IS MISSING THEIR CERTIFICATE OF
 AUTHORIZATION NUMBER.) 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY BE ADDED BY
 HAND.
  
 4) SHEET X1.1 CODE CRITERIA, FLORIDA BUILDING CODE
 2004/ 2006 REVISIONS BUILDING
  
 5) SHEET X1.1 FIRE PROTECTION CRITERIA, THE PLANS
 INDICATE A TYPE II BUILDING BUT THE FIRE RATINGS DO NOT
 MATCH, PLEASE
 SEE IF THE PLANS ARE TO BE A TYPE L TYPE A OR B ?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-11-19 Cont ID  
Sent By dpalmer Date 2007-11-19 Time 11:37 Rev Time 0.00
Received By dpalmer Date 2007-11-19 Time 11:37 Sent To B
Notes
2007-11-19 11:38:49NEW ELECTRICAL SHEET E-2, WHEN PLANS WERE PREVIOUSLY
 PASSED.
 PLANS SENT TO LUIS MARTINEZ. ZONING STILL HAS "FAILED"
 STATUS FOR NO PERMITS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-26 Cont ID  
Sent By dpalmer Date 2007-08-26 Time 17:27 Rev Time 0.00
Received By dpalmer Date 2007-08-26 Time 17:19 Sent To  
Notes
2007-08-26 17:28:062007-08-26 17:28:06
 OK,
 STAMPED E-SHEETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-04 Cont ID  
Sent By dpalmer Date 2007-02-04 Time 18:55 Rev Time 0.00
Received By dpalmer Date 2007-02-04 Time 18:48 Sent To  
Notes
2007-02-04 18:55:42** UNSAT **
  
 1) NOTE: PLEASE SEE THE CODES ADOPTED AND IN DESIGN
 SHALL BE STATED ON THE PLANS.
 PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE STATE OF
 FLORIDA ADOPTED THE 2006 REVISIONS TO THE 2004 FBC AND
 THE 2005 NFPA-70.
 PLEASE BE SURE TO STATE THE FOLLOWING ON THE PLANS AT A
 MINIMUM AND ANY OTHERS WHICH MAY BE MENTIONED BY OTHER
 TRADES.
 2004 FBC W/2006 (REVISIONS)
 2005 NFPA-70 NEC.
  
 2) NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR NEW
 CIRCUIT(S) LOADS ON NEW AND EXISTING. PLEASE SHOW THE
 CONDUCTOR SIZE(S), OVER CURRENT PROTECTION ETC.
 408.4, 310.16, 240.4.
 PLEASE INDICATE ANY CONTINUOUS LOADS AT 125% 215.3,
 230.42/ MOTOR LOADS?
  
 3) NOTE: PLEASE INDICATE NEW OR EXISTING SHUNT/SHUT
 DOWN OF ALL ELECTRICAL UNDER HOOD PER NFPA-96.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-09 Cont ID  
Sent By mwennerg Date 2007-11-09 Time 11:04 Rev Time 0.00
Received By mwennerg Date 2007-11-09 Time 11:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-07 Cont ID  
Sent By mwennerg Date 2007-09-07 Time 15:13 Rev Time 0.00
Received By mwennerg Date 2007-09-07 Time 15:13 Sent To  
Notes
2007-09-07 15:16:31***DENIED***
 A RESPONSE LETTER WAS INCLUDED ADDRESSING OTHER REVIEW
 COMMENTS. IT WOULD HELP EXPEDITE THIS PROCESS IF A
 LETTER ADDRESSING FIRE REVIEW COMMENTS WAS PROVIDED
 INDICATING WHERE INFORMATION MAY BE FOUND IF CORRECTED
 ON PLANS.
  
 1) THE APPLICATION INDICATES KITCHEN HOOD REPLACEMENT
 AND THE NARRATIVE ON SHT X1.1 MENTIONS FIRE SUPPRESSION
 SYSTEM. DOES THE SYSTEM CURRENTLY MEET THE REQUIREMENTS
 FOR A WET CHEMICAL UL 300 APPLICATION, OR WILL IT BE
 UPGRADED DURING THE SCOPE OF THIS WORK?
  
 2) PLEASE SHOW LOCATION OF REQUIRED "K" FIRE
 EXTINGUISHER.
  
 3) IN ADDITION TO LISTED CODES, CONSTRUCTION,
 ALTERATION AND DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR HOOD
 AND FIRE SUPPRESSION SYSTEMS.
  
 5) WORK SHALL NOT INTERFERE WITH EXISTING BUILDING FIRE
 PROTECTION EQUIPMENT AND REQUIRED MEANS OF EGRESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW(561) 805-6722
 FIRE PREVENTION(561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-07 Cont ID  
Sent By mwennerg Date 2007-03-07 Time 10:17 Rev Time 0.00
Received By mwennerg Date 2007-03-07 Time 10:17 Sent To  
Notes
2007-03-07 10:28:24***DENIED***
  
 1) THE APPLICATION INDICATES KITCHEN HOOD REPLACEMENT
 AND THE NARRATIVE ON SHT X1.1 MENTIONS FIRE SUPPRESSION
 SYSTEM. DOES THE SYSTEM CURRENTLY MEET THE REQUIREMENTS
 FOR A WET CHEMICAL UL 300 APPLICATION, OR WILL IT BE
 UPGRADED DURING THE SCOPE OF THIS WORK?
  
 2) PLEASE SHOW LOCATION OF REQUIRED "K" FIRE
 EXTINGUISHER.
  
 3) IN ADDITION TO LISTED CODES, CONSTRUCTION,
 ALTERATION AND DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR HOOD
 AND FIRE SUPPRESSION SYSTEMS.
  
 5) WORK SHALL NOT INTERFERE WITH EXISTING BUILDING FIRE
 PROTECTION EQUIPMENT AND REQUIRED MEANS OF EGRESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW(561) 805-6722
 FIRE PREVENTION(561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-10 Cont ID  
Sent By adarroug Date 2008-04-10 Time 17:25 Rev Time 0.00
Received By adarroug Date 2008-04-10 Time 17:25 Sent To M
Notes
2008-04-10 17:25:54TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 12:21 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 12:21 Sent To  
Notes
2007-10-26 15:47:02TO "COMM" BD#5
2007-10-10 12:21:35WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 15:25 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 15:25 Sent To  
Notes
2007-08-26 17:19:51TO COMM BOARD SPACE #59
2007-08-03 15:25:20WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-07 Cont ID  
Sent By mwennerg Date 2007-03-07 Time 10:34 Rev Time 0.00
Received By mwennerg Date 2007-01-25 Time 09:05 Sent To  
Notes
2007-02-02 09:52:00TO "COMM" BD#27
2007-01-25 09:23:53WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-06 Cont ID  
Sent By rregueir Date 2008-05-06 Time 11:13 Rev Time 0.00
Received By rregueir Date 2008-04-29 Time 13:57 Sent To PC
Notes
2008-05-06 11:14:37REVISED PAGE M-3. SEE REDLINE NOTE ON PLANS. CLEANOUTS
 ARE REQUIRED EVERY 20 FEET IN HORIZONTAL DUCTS IN
 ACCORDANCE WITH FBCM 506.3.9 RATHER THAN AT EACH CHANGE
 IN DIRECTION AS STATED ON PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-17 Cont ID  
Sent By rregueir Date 2007-11-17 Time 11:33 Rev Time 0.00
Received By rregueir Date 2007-11-17 Time 10:38 Sent To PC
Notes
2007-11-17 11:08:48**************PROVISO*****************
 ACCESS PANELS FOR CLEAN-OUTS IN HORIZONTAL GREASE DUCTS
 SHALL BE SPACED NOT MORE THAN 20 FEET APART IN
 ACCORDANCE WITH FBC,M 506.3.9, NOT ONLY AT CHANGES OF
 DIRECTION AS INDICATED ON PG M-3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-23 Cont ID  
Sent By rregueir Date 2007-08-23 Time 09:10 Rev Time 0.00
Received By rregueir Date 2007-08-22 Time 16:10 Sent To  
Notes
2007-08-23 08:50:48REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS THE DESIGNER'S
 WRITTEN RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. THERE WAS NO WRITTEN RESPONSE TO THIS COMMENT
 PROVIDED AND NO CHANG SHOWN ON PLANS. PLEASE SHOW HOW
 THIS ITEM IS TO BE ADDRESSED AND RESUBMIT.
  
 4. THERE IS NO FIRE DAMPER SHOWN ON 20 INCH ROUND DUCT
 PENETRATING THE RATED TEMPORARY BARRIER. SHOW OPENING
 PROTECTIVES PER FBC,M 607.5.
  
 5. OK
  
 6. OK
  
 7. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS
 FOR THIS REVIEW. PLEASE INCLUDE THIS INFORMATION ON THE
 PLANS. SEE FBC 106.1.1
  
 8. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS
 FOR THIS REVIEW. HOWEVER, THE RELEVANT INFORMATION HAS
 BEEN ADDED TO THE PLANS. THIS COMMENT HAS BEEN
 ADEQUATELY ADDRESSED.
  
 9. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS
 FOR THIS REVIEW. NOTE 18 ON PG M-3 CALLS FOR DUCT TO BE
 SLOPED AT MIN. 1 INCH PER FOOT. IS THIS INTENTIONAL
 BECAUSE THE HORIZONTAL DUCT MAY BE IN EXCESS OF 75
 FEET? THE 9X9 DUCT FOR HOOD #7 WOULD HAVE A RISE OF
 MORE THAN 4 FEET BEFORE IT REACHES THE LARGER DUCT.
 PLEASE VERIFY THAT THIS IS EVEN FEASIBLE WITH FIELD
 CONDITIONS.
  
 10. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS
 FOR THIS REVIEW. ALSO, THERE ARE NO CLEANOUTS SHOWN ON
 THE 9X9 GREASE DUCT. PLEASE CORRECT AND RESUBMIT.
  
 11. OK
  
 12. OK
  
 13. PLEASE INDICATE ON PLANS HOW THE ADDED FIRE/SMOKE
 DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH FBC,M
 607.5.4.1.
  
 14. DRAWING S-1 ATTACHED TO FRONT OF PLANS: PROVIDE TWO
 SETS WITH ORIGINAL SEAL AND DATE/SIGNATURE PER FAC
 61G15-23.002
  
 NEW COMMENT: THERE HAS BEEN A CHANGE OF CONTRACTOR FORM
 FILED WITH A NEW PERMIT APPPLICATION FOR JP HURBON,
 INC. HOWEVER, ONE OF THE SUBCONTRACTORS HAS ALSO BEEN
 CHANGED ON THE PERMIT APPLICATION FROM BRADLEY HEATING
 AND AIR CONDITIONING, INC. TO FARMER & IRWIN CORP. AN
 ADDITIONAL CHANGE OF CONTRACTOR FORM MUST BE FILED TO
 FACILITATE THIS CHANGE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-05 Cont ID  
Sent By rregueir Date 2007-03-05 Time 08:51 Rev Time 0.00
Received By rregueir Date 2007-03-02 Time 09:08 Sent To  
Notes
2007-03-05 09:41:13----------------DENIED------------------
  
 FLORIDA BUILDING CODE 2004
 FLORIDA BUIDLING CODE, MECHANICAL 2004
 NFPA 96-01
  
 1. PG M-1 INFECTION CONTROL PLAN: NOTES CALL FOR
 EX-AHU-3 TO PROVIDE 100% OUTDOOR AIR FOR AREA BEING
 RENOVATED. THERE IS NO AHU-3 SHOWN ON THIS PLAN. PLEASE
 CLARIFY PER FBC 106.1.1.
  
 2. PG A3.0 DETAIL D4 NOTES: REFERS TO PG A13.2 AND
 A13.5 FOR ADDITIONAL INFO. NO SUCH PAGES WERE INCLUDED
 IN PLAN. PLEASE CLARIFY PER FBC 106.1.1.
  
 3. PG A5.1 WHAT PROVISIONS ARE BEING MADE TO MAINTAIN
 FIRE RATED SEPARATION BETWEEN GROUND FLOOR AND FIRST
 FLOOR WHILE SHAFT IS REMOVED FOR REPLACEMENT OF DUCTS?
  
 4. PG A1.0 AND A3.0 SHOW TEMPORARY CONTAINMENT BARRIER
 TO BE 1-HOUR RATED. ARE REQUIRED WHERE DUCTS (OUTSIDE
 AIR FROM EX-AHU-3 AND TEMPORARY EF) PENETRATE THE RATED
 ASSEMBLY PER FBC,M 607.5.
  
 5. PG M-2 PLAN NOTE #5: NO INFORMATION REGARDING THE
 REMOVAL OF A THROUGH-WALL FAN COULD BE FOUND IN
 ARCHITECTURAL DRAWINGS. PLEASE CLARIFY PER FBC
 106.1.1.
  
 6. PG M-1 FAN SCHEDULE SHOWS EX-EF-1 MOVING 13,700 CFM.
 PG M-5 KITCHEN AIR BALANCE SCHEDULE SHOWS EX-EF-1
 MOVING 2530 CFM. THESE TWO SCHEDULES DO NOT MATCH. IT
 ALSO APPEARS THAT THERE IS AN EXTRA 2530 CFM IF EXHAUST
 IN THE KITCHEN AIR BALANCE SCHEDULE SINCE EX-EF-1 IS
 ALREADY BEING USED BY THE COMBINED HOODS TO PRODUCE THE
 13,700 CFM LISTED AT THE TOP OF THE SCHEDULE. PLEASE
 CLARIFY PER FBC 106.1.1.
  
 7. PLEASE INDICATE ON PLAN THE THICKNESS OF THE
 STAINLESS STEEL EXHAUST DUCTS TO SHOW COMPLIANCE WITH
 FBC,M 506.3.1.1.
  
 8. PG X1.1 PLEASE REFERENCE SMACNA-95 HVAC DUCT
 CONSTRUCTION STANDARDS - METAL AND FLEXIBLE TO SHOW
 COMPLIANCE WITH FBC,M 603.3.
  
 9. GREASE DUCTS TO BE SLOPED TOWARD THE HOOD AT NOT
 LESS THAN 1/4 UNIT VERTICAL IN 12 UNITS HORIZONTAL PER
 FBC,M 506.3.7.
  
 10. THERE ARE NO CLEANOUTS SHOWN ON HORIZONTAL GREASE
 DUCTS IN KITCHEN AREA. CLEANOUTS LOCATED ON HORIZONTAL
 DUCTS SHALL BE SPACED NOT MORE THAN 20' APART PER FBC,M
 506.3.9.
  
 11. GREASE DUCTS FOR TYPE I HOODS SHALL NOT BE
 INTERCONNECTED UNLESS THEY MEET ALL THE REQUIREMENTS OF
 FBC,M 506.3.5. THIS DESIGN CALLS FOR THE GREASE DUCTS
 FROM HOODS 1,2 AND 7 TO INTERCONNECT AFTER ENTERING THE
 RATED SHAFT ASSEMBLY. THIS DOES NOT COMPLY WITH
 REQUIREMENT #3 OF THIS SECTION.
  
 12. DUCT ENCLOSURE FOR GREASE DUCTS SHALL SERVE ONLY A
 SINGLE GREASE EXHAUST DUCT SYSTEM AND SHALL MEET THE
 MINIMUM AND MAXIMUM CLEARANCE REQUIREMENTS OF FBC,M
 506.3.10. MAKE-UP AIR DUCTS MAY NOT USE THE SAME SHAFT
 ENCLOSURE AS THE GREASE DUCT.
  
 13. DUCTS PENETRATING A SHAFT ENCLOSURE SHALL BE
 PROTECTED WITH APPROVED FIRE AND SMOKE DAMPERS
 INSTALLED IN ACCORDANCE WITH THEIR LISTING PER FBC,M
 607.5.5.1. THIS APPLIES ONLY TO THE MAKE-UP AIR DUCTS.
  
 14. DRAWING SK-1 SHOWS METAL STRAPS OVER TOP OF FAN
 HOUSINGS FOR THE PURPOSE OF ROOF ATTACHMENT. THESE
 STRAPS SHOULD NOT HAVE TO BE REMOVED FOR EQUIPMENT
 SERVICE PANEL ACCESS PER FBC,M 306.1.
  
 NOTE: A SEPARATE PERMIT WILL BE NEEDED FOR THE REQUIRED
 MECHANICAL HOOD SUPPRESSION SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS PLEASE FEEL FREE TO CONTACT
 ME.
  
 RONALD J REGUEIRO
 561-805-6719
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-11-19 Cont ID  
Sent By lmartine Date 2007-11-19 Time 15:43 Rev Time 0.00
Received By LFRANCO Date 2007-11-19 Time 15:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-29 Cont ID  
Sent By lfranco Date 2007-10-29 Time 18:21 Rev Time 0.00
Received By lfranco Date 2007-10-29 Time 18:19 Sent To  
Notes
2007-10-29 18:21:11PLANNING AND ZONING:**** FAILED **** - COMMENT IS
 STILL OUTSTANDING, NO BUILDING PERMIT WILL BE ACCEPTED
 OR APPROVED (WITH THE EXCEPTION OF LIFE SAFETY BLDG.
 PERMITS) UNTIL COMMENT IS ADDRESSED.
  
 1. PLEASE RESPOND TO COMMENTS IN WRITING.
  
 2. PURSUANT TO A LETTER DATED JULY 11, 2007 (ATTACHED
 HEREIN) , SENT BY THE DEPUTY PLANNING DIRECTOR, ANGELLA
 JONES-VANN TO REBECCA K. BOYAJIAN, ESQ. HOLLAND &
 KNIGHT, LLP, ON BEHALF OF TENENT ST. MARY'S, NO PERMIT
 WILL BE ISSUED WITH SOME EXCEPTIONS UNTIL THE FOLLOWING
 REPLAT CONDITIONS ARE MADE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT THE DEPUTY
 PLANNING DIRECTOR, ANGELLA JONES-VANN AT THE NUMBER
 BELOW.
  
 AJV/LMF
  
  
 JULY 11, 2007
  
  
 REBECCA K. BOYAJIAN, ESQ.
 HOLLAND & KNIGHT, LLP
 222 LAKEVIEW AVENUE, SUITE 1000
 WEST PALM BEACH, FLORIDA 33401
  
  
 RE: ST. MARY'S HOSPITAL COMMUNITY SERVICE PLANNED
 DEVELOPMENT (CSPD)
  
  
 DEAR MS. BOYAJIAN:
  
 IT WAS BROUGHT TO THE ATTENTION OF THE PLANNING AND
 ZONING DEPARTMENT THAT ST. MARY TENET ILLEGALLY SOLD A
 PORTION OF THEIR PROPERTY WITHOUT GOING THROUGH THE
 CITY?S SUBDIVISION PROCESS.THIS PORTION WAS LATER
 UNIFIED TO THE HANLEY CENTER CAMPUS? PROPERTY, LOCATED
 IMMEDIATELY WEST OF THE ST. MARY?S MEDICAL CENTER.AS
 A RESULT, ANY DEVELOPMENT ORDERS, TO INCLUDE BUILDING
 PERMITS WITH THE EXCEPTION OF PERMITS FOR LIFE SAFETY
 SYSTEMS (I.E.: FIRE EXTINGUISHERS, FIRE SPRINKLERS,
 FIRE DETECTION AND ALARM SYSTEMS, EXIT SYSTEMS
 INCLUDING MARKING AND HARDWARE, ILLUMINATION SYSTEMS
 INCLUDING NORMAL AND EMERGENCY LIGHTING AND
 GENERATORS), FOR THE ST. MARY?S AND THE HANLEY CENTER
 SITES, WILL NOT BE ISSUED UNTIL THE FOLLOWING HAS BEEN
 COMPLETED:
  
 1. A REPLAT OF THE ST. MARY?S MEDICAL CENTER PARCEL
 THROUGH THE CITY?S MINOR SUBDIVISION PROCESS; AND 2. A
 MAJOR AMENDMENT TO THE ST. MARY?S MEDICAL CENTER CSPD
 TO CHANGE THE EXISTING BOUNDARY OF THE PLANNED
 DEVELOPMENT.PLEASE NOTE THAT THE MAJOR AMENDMENT WILL
 REQUIRE APPROVAL BY THE CITY COMMISSION.
  
 IF YOU HAVE ANY OTHER QUERIES, PLEASE DO NOT HESITATE
 TO CONTACT ME AT (561) 822-1435.
  
 SINCERELY,
 ANGELLA VANN, AICP
 DEPUTY PLANNING DIRECTOR
  
 C: ERIC SCHNEIDER, PRINCIPAL PLANNER
  NEIL K. MELICK, CONSTRUCTION SERVICES DIRECTOR NANCY
 URCHECK, DEPUTY CITY ATTORNEY
  G. SCOTT MANIS, FACHE, CHIEF OPERATING OFFICER
  CHARLES W. MILLAR, DEVELOPMENT PLANNER

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-07 Cont ID  
Sent By lfranco Date 2007-09-07 Time 18:17 Rev Time 0.00
Received By lfranco Date   Time   Sent To  
Notes
2007-09-07 18:17:11PLANNING AND ZONING:**** FAILED ****
  
 1. PLEASE RESPOND TO COMMENTS IN WRITING.
  
 2. PURSUANT TO A LETTER DATED JULY 11, 2007 (ATTACHED
 HEREIN) , SENT BY THE DEPUTY PLANNING DIRECTOR, ANGELLA
 JONES-VANN TO REBECCA K. BOYAJIAN, ESQ. HOLLAND &
 KNIGHT, LLP, ON BEHALF OF TENENT ST. MARY'S, NO PERMIT
 WILL BE ISSUED WITH SOME EXCEPTIONS UNTIL THE FOLLOWING
 REPLAT CONDITIONS ARE MADE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT THE DEPUTY
 PLANNING DIRECTOR, ANGELLA JONES-VANN AT THE NUMBER
 BELOW.
  
 AJV/LMF
  
  
 JULY 11, 2007
  
  
 REBECCA K. BOYAJIAN, ESQ.
 HOLLAND & KNIGHT, LLP
 222 LAKEVIEW AVENUE, SUITE 1000
 WEST PALM BEACH, FLORIDA 33401
  
  
 RE: ST. MARY'S HOSPITAL COMMUNITY SERVICE PLANNED
 DEVELOPMENT (CSPD)
  
  
 DEAR MS. BOYAJIAN:
  
 IT WAS BROUGHT TO THE ATTENTION OF THE PLANNING AND
 ZONING DEPARTMENT THAT ST. MARY TENET ILLEGALLY SOLD A
 PORTION OF THEIR PROPERTY WITHOUT GOING THROUGH THE
 CITY?S SUBDIVISION PROCESS.THIS PORTION WAS LATER
 UNIFIED TO THE HANLEY CENTER CAMPUS? PROPERTY, LOCATED
 IMMEDIATELY WEST OF THE ST. MARY?S MEDICAL CENTER.AS
 A RESULT, ANY DEVELOPMENT ORDERS, TO INCLUDE BUILDING
 PERMITS WITH THE EXCEPTION OF PERMITS FOR LIFE SAFETY
 SYSTEMS (I.E.: FIRE EXTINGUISHERS, FIRE SPRINKLERS,
 FIRE DETECTION AND ALARM SYSTEMS, EXIT SYSTEMS
 INCLUDING MARKING AND HARDWARE, ILLUMINATION SYSTEMS
 INCLUDING NORMAL AND EMERGENCY LIGHTING AND
 GENERATORS), FOR THE ST. MARY?S AND THE HANLEY CENTER
 SITES, WILL NOT BE ISSUED UNTIL THE FOLLOWING HAS BEEN
 COMPLETED:
  
 1. A REPLAT OF THE ST. MARY?S MEDICAL CENTER PARCEL
 THROUGH THE CITY?S MINOR SUBDIVISION PROCESS; AND 2. A
 MAJOR AMENDMENT TO THE ST. MARY?S MEDICAL CENTER CSPD
 TO CHANGE THE EXISTING BOUNDARY OF THE PLANNED
 DEVELOPMENT.PLEASE NOTE THAT THE MAJOR AMENDMENT WILL
 REQUIRE APPROVAL BY THE CITY COMMISSION.
  
 IF YOU HAVE ANY OTHER QUERIES, PLEASE DO NOT HESITATE
 TO CONTACT ME AT (561) 822-1435.
  
 SINCERELY,
 ANGELLA VANN, AICP
 DEPUTY PLANNING DIRECTOR
  
 C: ERIC SCHNEIDER, PRINCIPAL PLANNER
  NEIL K. MELICK, CONSTRUCTION SERVICES DIRECTOR NANCY
 URCHECK, DEPUTY CITY ATTORNEY
  G. SCOTT MANIS, FACHE, CHIEF OPERATING OFFICER
  CHARLES W. MILLAR, DEVELOPMENT PLANNER