| Plan Review Stops For Permit 07011114 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-08-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-08-08 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-08-08 |
Time |
14:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-07-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-07-05 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-07-05 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2007-07-05 14:41:50 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | 1.)PLANS SPECIFY 1/2INCH ANCHOR; NO DIAMETER OR | | | LENGTH. SPECIFY TYPE OF ANCHOR AND ALL DIMENSIONAL | | | INFORMATION TO COMPLY WITH FBC1606.1.3. | | | | | | 2ND REVIEW, PLEASE PROVIDE ALL INFORMATION REQUIRED TO | | | SHOW HOW WIND LOADS WILL BE RESISTED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-02-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-02-21 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-02-21 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2007-02-21 15:36:35 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | 1.)PLANS SPECIFY 1/2INCH ANCHOR; DIAMETER OR LENGTH. | | | SPECIFY TYPE OF ANCHOR AND ALL DIMENSIONAL INFORMATION | | | TO COMPLY WITH FBC1606.1.3. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-08-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-22 |
Time |
18:46 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-08-22 |
Time |
18:34 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-07-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-07-27 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-07-27 |
Time |
12:44 |
Sent To |
G |
|
| Notes |
| 2007-07-27 13:22:04 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | | AMENDED.A PERMIT SHALL NOT BE ISSUED UNTIL FEES | | | AUTHORIZED UNDER SECTION 553.80, FLORIDA STATUTES, HAVE | | | BEEN PAID. 108.1 FBC. | | | | | | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY | | | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. | | | | | | 2} PROVIDE MANUFACTURERS SPECIFICATIONS | | | INDICATING RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S | | | FOR THE GENERATOR. THE SETBACK IS NOT STATED IN THE | | | PLANS PROVIDED. | | | | | | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH | | | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM | | | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. PROVIDE A | | | WRITTEN RESPONSE TO THE COMMENTS AS IT DOES NOT APPEAR | | | THE PREVIOUS REVIEW HAS BEEN ADDRESSED. | | | | | | NOTE: THE ATS IS THE FIRST MEANS OF DISCONNECT FROM THE | | | SERVICE AS IT IS PLACED BETWEEN THE METER AND PANEL. | | | THE NEUTRAL MUST BE ISOLATED FROM THE GROUNDS IN THE | | | EXISTING PANEL PANEL. 250.24(C).. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-06-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-06-22 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-06-22 |
Time |
15:04 |
Sent To |
G |
|
| Notes |
| 2007-06-22 15:20:23 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | | AMENDED.A PERMIT SHALL NOT BE ISSUED UNTIL FEES | | | AUTHORIZED UNDER SECTION 553.80, FLORIDA STATUTES, HAVE | | | BEEN PAID. 108.1 FBC. | | | | | | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY | | | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. | | | | | | 2} PROVIDE MANUFACTURERS SPECIFICATIONS | | | INDICATING RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S | | | FOR THE GENERATOR. THE SETBACK IS NOT STATED IN THE | | | PLANS PROVIDED. | | | | | | NOTE: THE ATS IS THE FIRST MEANS OF DISCONNECT FROM THE | | | SERVICE AS IT IS PLACED BETWEEN THE METER AND PANEL. | | | THE NEUTRAL MUST BE ISOLATED FROM THE GROUNDS IN THE | | | EXISTING PANEL PANEL. 250.24(C). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-02-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-02-12 |
Time |
10:18 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-02-12 |
Time |
08:21 |
Sent To |
M |
|
| Notes |
| 2007-02-12 10:18:43 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | | AMENDED. | | | | | | 2} PROVIDE MANUFACTURERS SPECIFICATIONS | | | INDICATING RECOMMENDED SETBACKS AND | | | ELECTRICAL SPEC'S FOR THE GENERATOR AND | | | TRANSFER SWITCH. | | | | | | IT IS THE DETERMINATION OF THIS OFFICE THAT LOADS BEING | | | TRANSFERRED AUTOMATICALLY ARE THE LOADS SELECTED PER | | | ARTICLE 702.5. UTILITY POWER CAN BE DISRUPTED AT ANY | | | TIME, POSSIBLY IN THE OWNERS ABSENCE. THEREFORE ALL | | | CONNECTED LOADS WILL BE ENERGIZED AS THERE IS NO ONE TO | | | "SELECT" WHICH CIRCUITS WILL BE DE-ENERGIZED. | | | | | | ALSO THE NOTE IN THE "LOAD CALCULATION" AREA REGARDING | | | HURRICANE SEASON IS NOT APPLICABLE AS POWER FROM THE | | | UTILITY CAN BE INTERUPTED AT ANY TIME REGARDLESS OF | | | SEASON.THE HEAT LOAD MUST BE CALCULATED PER ARTICLE 220 | | | IF THAT LOAD IS CONNECTED TO THE PANEL BEING ENERGIZED | | | BY THE TRANSFER SWITCH. | | | | | | 3}PROVIDE A CALCULATION OF ALL LOADS TO BE SUPPLIED | | | BY THE GENERATOR: AN OPTIONAL STANDBY SYSTEM SHALL HAVE | | | ADEQUATE CAPACITY AND RATING FOR THE SUPPLY OF ALL | | | EQUIPMENT INTENDED TO BE OPERATED AT ONE TIME, 702.5 | | | 2005 NEC. IN THE EVENT A MANUAL TRANSFER SWICH IS | | | INSTALLED, THESE CALCULATIONS WOULD NOT BE REQUIRED AS | | | SOMEONE WOULD HAVE TO BE PRESENT TO SELECT THE TRANSFER | | | AND THEREFORE THE LOADS. | | | | | | 4} NOTE #2, SHEET E-1, INCORRECTLY REFERENCES ARTICLE | | | 110.16, WHICH IS FROM THE 1996 CODE, FLORIDA HAS | | | CURRENTLY ADOPTED THE 2005 NEC AS OF 12/8/2006. | | | | | | 5} THE SITE DIAGRAM ON SHEET C-1 INDICATES THE ATS | | | BEING FED DIRECTLY FROM THE METER AND GENERATOR. THE | | | RISER ON SHEET E-1 INDICATES THE METER FEED TO THE | | | PANEL. THE ATS MUST BE SERVICE RATED PER 225.36, 230.66 | | | AND RATED PER 110.9 AND 110.10FOR AIC FROM THE | | | UTILITY IF IN BEING INSTALLED AS SERVICE EQUIPMENT. | | | PLEASE CLARIFY THE INSTALLATION PROPOSED AND CORRELATE | | | DRAWINGS. OPTIONAL STANDBY SYSTEM EQUIPMENT SHALL BE | | | SUITABLE FOR THE MAXIMUM AVAILABLE FAULT CURRENT AT ITS | | | TERMINALS.702.5. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
N |
Date |
2007-08-29 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-08-29 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-08-29 |
Time |
10:03 |
Sent To |
M |
|
| Notes |
| 2007-08-29 10:12:19 | NOTE:GAS PLANS PASSED 8/3/07, THERE ARE NO CHANGES | | | FOR GAS ON THIS RESUBMITTAL. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2007-08-03 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-08-03 |
Time |
10:02 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2007-08-03 |
Time |
10:02 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2007-08-02 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-08-02 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-08-02 |
Time |
13:52 |
Sent To |
Z |
|
| Notes |
| 2007-08-02 13:54:38 | NOTE: ROUTED TO ZONING FOR APPROVAL OF GENERATOR | | | LOCATION DUE TO NEW SHEETS. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-07-02 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-07-02 |
Time |
11:11 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-07-02 |
Time |
11:11 |
Sent To |
M |
|
| Notes |
| 2007-07-02 11:14:38 | DENIED 2ND TIME | | | REFERENCE: | | | ** FBC-2004 FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, | | | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING | | | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT | | | MADE ON PREVIOUS REVIEWS. | | | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. | | | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE | | | PREVIOUS REVIEW NOTES. | | | | | | A **NO** IS IF THE COMMENT WAS NOT FULLY ADDRESSED | | | AND/OR FURTHER EXPLANATION OR CHANGES IN PLANS OR | | | DOCUMENTS ARE STILL NEEDED. THIS REVIEWER WILL TRY TO | | | BETTER EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. | | | | | | AN **OK** WILL BE LABELED AS SUCH ON THE SAME NUMERICAL | | | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. | | | | | | A **NO/OK** MEANS PART OF THE COMMENT MAY HAVE BEEN | | | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW | | | COMMENT MAY HAVE BEEN FULLY ADDRESSED. | | | | | | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF | | | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. | | | | | | 1. **NO** VALUE OF GENERATOR IS TO LOW. | | | PER FBC-2004, CHAPTER 1, SECTION | | | 108.3, BUILDING PERMIT VALUATION: IF IN | | | THE OPINION OF THE BUILDING OFFICIAL, | | | THE CLAIMED VALUATION OF THE BUILDING, | | | ALTERATION, STRUCTURE, ELECTRICAL, GAS | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS | | | TO BE UNDERESTIMATED ON THE APPLICATION, | | | THE PERMIT SHALL BE DENIED. FOR | | | PERMITTING PURPOSES, VALUATION OF | | | BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR | | | FINISH, NORMAL SITE WORK (EXCAVATION AND | | | BACKFILL FOR BUILDINGS), ARCHITECTURAL | | | AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND | | | VALUE. VALUATION REFERENCES MAY INCLUDE | | | THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, | | | MEANS ECT.) WITH | | | REGIONAL ADJUSTMENTS FOR LOCATION AS | | | PUBLISHED BY INTERNATIONAL CODE | | | CONGRESS. | | | NOTE: PLEASE CORRECT THIS PRIOR TO THE RESUBMITTAL. | | | | | | 2. **NO/OK** PLEASE PROVIDE MANUFACTURER | | | SPECIFICATIONS INDICATING RECOMMENDING SETBACKS OF | | | GENERATOR TO STRUCTURES AND TO VERIFY BTU LOAD. | | | NOTE: THE MANUFACTURER SPECIFICATIONS REQUESTED FOR THE | | | RESUBMITTAL INDICATING THE RECOMMENDED SETBACKS OF | | | GENERATOR TO STRUCTURES WAS NOT PROVIDED. PLEASE | | | PROVIDE THIS INFORMATION ON THE NEXT RESUBMITTAL. | | | | | | 3. **OK** | | | | | | 4. **OK** | | | | | | 5. **OK** | | | | | | ** THE FOLLOWING IS A NEW COMMENT ** | | | | | | 6. SHEET C-1: THE LONGEST RUN OF 31' ON THE RESUBMITTED | | | GAS ISOMETRIC IS WRONG. THE CORRECT LONGEST RUN ON THE | | | GAS SYSTEM IS 44' FROM THE NEWLY PROVIDED INFORMATION. | | | PLEASE CORRECT THIS ON THE RESUBMITTAL. | | | | | | ******IMORTANT INFORMATION | | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. | | | NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-02-14 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-02-14 |
Time |
09:56 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2007-02-14 |
Time |
09:56 |
Sent To |
B |
|
| Notes |
| 2007-02-14 10:22:10 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS; CITY OF WEST PALM BEACH | | | GAS PERMIT APPLICATION REQUIREMENTS; | | | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN | | | REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. VALUE OF GENERATOR IS TO LOW. | | | PER FBC-2004, CHAPTER 1, SECTION | | | 108.3, BUILDING PERMIT VALUATION: IF IN | | | THE OPINION OF THE BUILDING OFFICIAL, | | | THE CLAIMED VALUATION OF THE BUILDING, | | | ALTERATION, STRUCTURE, ELECTRICAL, GAS | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS | | | TO BE UNDERESTIMATED ON THE APPLICATION, | | | THE PERMIT SHALL BE DENIED. FOR | | | PERMITTING PURPOSES, VALUATION OF | | | BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR | | | FINISH, NORMAL SITE WORK (EXCAVATION AND | | | BACKFILL FOR BUILDINGS), ARCHITECTURAL | | | AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND | | | VALUE. VALUATION REFERENCES MAY INCLUDE | | | THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, | | | MEANS ECT.) WITH | | | REGIONAL ADJUSTMENTS FOR LOCATION AS | | | PUBLISHED BY INTERNATIONAL CODE | | | CONGRESS. | | | | | | 2. PLEASE PROVIDE MANUFACTURER SPECIFICATIONS | | | INDICATING RECOMMENDING SETBACKS OF GENERATOR TO | | | STRUCTURES AND TO VERIFY BTU LOAD. | | | | | | 3. SHEET C-1 INDICATES THE EXISTING GAS PIPE TO THE | | | EXISTING WATER HEATER BEING 3/8". THIS IS WRONG PER | | | FBC-2004 TABLE 402.4(8) AND FBC-2004 FUEL GAS , SECTION | | | 402.4.1 LONGEST LENGTH METHOD, THE GAS PIPE TO THE | | | EXISTING WATER HEATER NEEDS TO BE INCREASED TO 1/2". | | | PLEASE REFERENCE THE ATTACHED TABLE INDICATING THIS. | | | PLEASE CORRECT AND RESBMIT. | | | | | | 4. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED ON | | | THE GAS ISOMETRIC ON SHEET C-1. PLEASE CORRECT AND | | | RESUBMIT. | | | | | | 5. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | NOTE: NOT ALL MATERIAL TYPES ARE INDICATED ON THE GAS | | | ISOMETRIC ON SHEET C-1. PLEASE CORRECT AND RESUBMIT. | | | | | | ******IMORTANT INFORMATION | | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-08-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-16 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-16 |
Time |
16:18 |
Sent To |
Z |
|
| Notes |
| 2007-08-16 16:18:44 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-07-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-20 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-20 |
Time |
16:54 |
Sent To |
E |
|
| Notes |
| 2007-07-20 16:54:35 | TO "BTROBAUGH" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-18 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-18 |
Time |
16:02 |
Sent To |
E |
|
| Notes |
| 2007-06-18 16:03:10 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-02-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-05 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-05 |
Time |
13:50 |
Sent To |
E |
|
| Notes |
| 2007-02-05 13:51:03 | TO "GEN-RES" BOX "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-02-21 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2007-02-21 |
Time |
15:36 |
Rev Time |
|
| Received By |
shill |
Date |
2007-01-29 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2007-01-29 11:04:07 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-08-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-29 |
Time |
11:10 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-08-29 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2007-08-29 11:11:09 | PASSED REVIEW ON 8-6-07. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-08-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-06 |
Time |
10:27 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-08-06 |
Time |
10:27 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-07-03 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-07-03 |
Time |
08:33 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-07-03 |
Time |
08:33 |
Sent To |
B |
|
| Notes |
| 2007-07-03 08:34:57 | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 2-13-07. GENERATOR IS TO | | | CLOSE TO WOOD FENCE, SEE NFPA 37 4.1.4. | | | | | | 2) SEE ZONING REVIEW PROVISO, PLEASE CORRECT GENERATOR | | | DISTANCE TO WOOD FENCE. | | | | | | 3) PER 2004 FBC, FUEL GAS - POWERED | | | EQUIPMENT - PERMANENTLY INSTALLED | | | EQUIPMENT POWERED BY INTERNAL COMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS AND NFPA 37. | | | | | | NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION | | | ENGINES & GAS TURBINES: | | | 4.1.4ENGINES (GENERATORS) LOCATED | | | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM | | | OPENINGS IN WALLS & AT LEAST 5 FT FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS.A | | | MINIMUM CLEARANCE IS NOT REQUIRED WHEN | | | (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE | | | RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS | | | CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS | | | BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. | | | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS | | | SHOULD NOT TERMINATE UNDER STRUCTURES OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO | | | THE VENTILATION INTAKES. | | | PLEASE NOTE, WHILE ZONING ALLOWS | | | MECHANICAL EQUIPMENT TO ENCROACH 4 FT | | | INTO THE REQUIRED SETBACK, GENERATORS | | | SHALL MAINTAIN THE REQUIRED ABOVE | | | MENTIONED CLEARANCES TO THE ADJACENT | | | PROPERTY STRUCTURES, I.E. FENCE, | | | BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | | | | 4) SEE ATTACHED NOTICE FS 553.80(2)(B) | | | REGARDING FOUR TIMES THE FEE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-02-13 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-02-13 |
Time |
13:55 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-02-13 |
Time |
13:55 |
Sent To |
G |
|
| Notes |
| 2007-02-13 14:11:46 | *** DENIED *** | | | 1) GENERATOR IS TO CLOSE TO WOOD FENCE, SEE NFPA 37 | | | 4.1.4. | | | | | | 2) SEE ZONING REVIEW PROVISO, PLEASE CORRECT GENERATOR | | | DISTANCE TO WOOD FENCE. | | | | | | 3) PER 2004 FBC, FUEL GAS - POWERED | | | EQUIPMENT - PERMANENTLY INSTALLED | | | EQUIPMENT POWERED BY INTERNAL COMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS AND NFPA 37. | | | | | | NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION | | | ENGINES & GAS TURBINES: | | | 4.1.4ENGINES (GENERATORS) LOCATED | | | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM | | | OPENINGS IN WALLS & AT LEAST 5 FT FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS.A | | | MINIMUM CLEARANCE IS NOT REQUIRED WHEN | | | (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE | | | RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS | | | CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS | | | BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. | | | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS | | | SHOULD NOT TERMINATE UNDER STRUCTURES OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO | | | THE VENTILATION INTAKES. | | | PLEASE NOTE, WHILE ZONING ALLOWS | | | MECHANICAL EQUIPMENT TO ENCROACH 4 FT | | | INTO THE REQUIRED SETBACK, GENERATORS | | | SHALL MAINTAIN THE REQUIRED ABOVE | | | MENTIONED CLEARANCES TO THE ADJACENT | | | PROPERTY STRUCTURES, I.E. FENCE, | | | BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-08-03 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-08-03 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-08-03 |
Time |
08:40 |
Sent To |
P |
|
| Notes |
| 2007-08-03 08:41:06 | APPROVED LOCATION OF GENERATOR. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2007-02-01 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2007-02-01 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2007-02-01 |
Time |
10:32 |
Sent To |
I |
|
| Notes |
| 2007-02-01 10:36:10 | PROVISO: THE PROPOSED GENERATOR SHALL NOT BE CLOSER | | | THAN 6FT FROM SIDE AND 6FT REAR PROPERTY LINE. |
|
|