Plan Review Details - Permit 07011114
Plan Review Stops For Permit 07011114
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-08 Cont ID  
Sent By shill Date 2007-08-08 Time 14:06 Rev Time 0.00
Received By shill Date 2007-08-08 Time 14:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-05 Cont ID  
Sent By shill Date 2007-07-05 Time 14:23 Rev Time 0.00
Received By shill Date 2007-07-05 Time 14:23 Sent To  
Notes
2007-07-05 14:41:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PLANS SPECIFY 1/2INCH ANCHOR; NO DIAMETER OR
 LENGTH. SPECIFY TYPE OF ANCHOR AND ALL DIMENSIONAL
 INFORMATION TO COMPLY WITH FBC1606.1.3.
  
 2ND REVIEW, PLEASE PROVIDE ALL INFORMATION REQUIRED TO
 SHOW HOW WIND LOADS WILL BE RESISTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-21 Cont ID  
Sent By shill Date 2007-02-21 Time 15:34 Rev Time 0.00
Received By shill Date 2007-02-21 Time 15:34 Sent To  
Notes
2007-02-21 15:36:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PLANS SPECIFY 1/2INCH ANCHOR; DIAMETER OR LENGTH.
 SPECIFY TYPE OF ANCHOR AND ALL DIMENSIONAL INFORMATION
 TO COMPLY WITH FBC1606.1.3.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-08-22 Cont ID  
Sent By btrobaug Date 2007-08-22 Time 18:46 Rev Time 0.00
Received By btrobaug Date 2007-08-22 Time 18:34 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-27 Cont ID  
Sent By btrobaug Date 2007-07-27 Time 13:22 Rev Time 0.00
Received By btrobaug Date 2007-07-27 Time 12:44 Sent To G
Notes
2007-07-27 13:22:04 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.A PERMIT SHALL NOT BE ISSUED UNTIL FEES
 AUTHORIZED UNDER SECTION 553.80, FLORIDA STATUTES, HAVE
 BEEN PAID. 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S
 FOR THE GENERATOR. THE SETBACK IS NOT STATED IN THE
 PLANS PROVIDED.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS. PROVIDE A
 WRITTEN RESPONSE TO THE COMMENTS AS IT DOES NOT APPEAR
 THE PREVIOUS REVIEW HAS BEEN ADDRESSED.
  
 NOTE: THE ATS IS THE FIRST MEANS OF DISCONNECT FROM THE
 SERVICE AS IT IS PLACED BETWEEN THE METER AND PANEL.
 THE NEUTRAL MUST BE ISOLATED FROM THE GROUNDS IN THE
 EXISTING PANEL PANEL. 250.24(C)..
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-22 Cont ID  
Sent By btrobaug Date 2007-06-22 Time 16:27 Rev Time 0.00
Received By btrobaug Date 2007-06-22 Time 15:04 Sent To G
Notes
2007-06-22 15:20:23 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.A PERMIT SHALL NOT BE ISSUED UNTIL FEES
 AUTHORIZED UNDER SECTION 553.80, FLORIDA STATUTES, HAVE
 BEEN PAID. 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S
 FOR THE GENERATOR. THE SETBACK IS NOT STATED IN THE
 PLANS PROVIDED.
  
 NOTE: THE ATS IS THE FIRST MEANS OF DISCONNECT FROM THE
 SERVICE AS IT IS PLACED BETWEEN THE METER AND PANEL.
 THE NEUTRAL MUST BE ISOLATED FROM THE GROUNDS IN THE
 EXISTING PANEL PANEL. 250.24(C).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-12 Cont ID  
Sent By btrobaug Date 2007-02-12 Time 10:18 Rev Time 1.00
Received By btrobaug Date 2007-02-12 Time 08:21 Sent To M
Notes
2007-02-12 10:18:43 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 IT IS THE DETERMINATION OF THIS OFFICE THAT LOADS BEING
 TRANSFERRED AUTOMATICALLY ARE THE LOADS SELECTED PER
 ARTICLE 702.5. UTILITY POWER CAN BE DISRUPTED AT ANY
 TIME, POSSIBLY IN THE OWNERS ABSENCE. THEREFORE ALL
 CONNECTED LOADS WILL BE ENERGIZED AS THERE IS NO ONE TO
 "SELECT" WHICH CIRCUITS WILL BE DE-ENERGIZED.
  
 ALSO THE NOTE IN THE "LOAD CALCULATION" AREA REGARDING
 HURRICANE SEASON IS NOT APPLICABLE AS POWER FROM THE
 UTILITY CAN BE INTERUPTED AT ANY TIME REGARDLESS OF
 SEASON.THE HEAT LOAD MUST BE CALCULATED PER ARTICLE 220
 IF THAT LOAD IS CONNECTED TO THE PANEL BEING ENERGIZED
 BY THE TRANSFER SWITCH.
  
 3}PROVIDE A CALCULATION OF ALL LOADS TO BE SUPPLIED
 BY THE GENERATOR: AN OPTIONAL STANDBY SYSTEM SHALL HAVE
 ADEQUATE CAPACITY AND RATING FOR THE SUPPLY OF ALL
 EQUIPMENT INTENDED TO BE OPERATED AT ONE TIME, 702.5
 2005 NEC. IN THE EVENT A MANUAL TRANSFER SWICH IS
 INSTALLED, THESE CALCULATIONS WOULD NOT BE REQUIRED AS
 SOMEONE WOULD HAVE TO BE PRESENT TO SELECT THE TRANSFER
 AND THEREFORE THE LOADS.
  
 4} NOTE #2, SHEET E-1, INCORRECTLY REFERENCES ARTICLE
 110.16, WHICH IS FROM THE 1996 CODE, FLORIDA HAS
 CURRENTLY ADOPTED THE 2005 NEC AS OF 12/8/2006.
  
 5} THE SITE DIAGRAM ON SHEET C-1 INDICATES THE ATS
 BEING FED DIRECTLY FROM THE METER AND GENERATOR. THE
 RISER ON SHEET E-1 INDICATES THE METER FEED TO THE
 PANEL. THE ATS MUST BE SERVICE RATED PER 225.36, 230.66
 AND RATED PER 110.9 AND 110.10FOR AIC FROM THE
 UTILITY IF IN BEING INSTALLED AS SERVICE EQUIPMENT.
 PLEASE CLARIFY THE INSTALLATION PROPOSED AND CORRELATE
 DRAWINGS. OPTIONAL STANDBY SYSTEM EQUIPMENT SHALL BE
 SUITABLE FOR THE MAXIMUM AVAILABLE FAULT CURRENT AT ITS
 TERMINALS.702.5.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 5 Status N Date 2007-08-29 Cont ID  
Sent By mperson Date 2007-08-29 Time 10:03 Rev Time 0.00
Received By mperson Date 2007-08-29 Time 10:03 Sent To M
Notes
2007-08-29 10:12:19NOTE:GAS PLANS PASSED 8/3/07, THERE ARE NO CHANGES
 FOR GAS ON THIS RESUBMITTAL.

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-08-03 Cont ID  
Sent By mperson Date 2007-08-03 Time 10:02 Rev Time 0.45
Received By mperson Date 2007-08-03 Time 10:02 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2007-08-02 Cont ID  
Sent By mperson Date 2007-08-02 Time 13:52 Rev Time 0.00
Received By mperson Date 2007-08-02 Time 13:52 Sent To Z
Notes
2007-08-02 13:54:38NOTE: ROUTED TO ZONING FOR APPROVAL OF GENERATOR
 LOCATION DUE TO NEW SHEETS.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-07-02 Cont ID  
Sent By mperson Date 2007-07-02 Time 11:11 Rev Time 0.33
Received By mperson Date 2007-07-02 Time 11:11 Sent To M
Notes
2007-07-02 11:14:38DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A **NO** IS IF THE COMMENT WAS NOT FULLY ADDRESSED
 AND/OR FURTHER EXPLANATION OR CHANGES IN PLANS OR
 DOCUMENTS ARE STILL NEEDED. THIS REVIEWER WILL TRY TO
 BETTER EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN **OK** WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A **NO/OK** MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO** VALUE OF GENERATOR IS TO LOW.
 PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
 NOTE: PLEASE CORRECT THIS PRIOR TO THE RESUBMITTAL.
  
 2. **NO/OK** PLEASE PROVIDE MANUFACTURER
 SPECIFICATIONS INDICATING RECOMMENDING SETBACKS OF
 GENERATOR TO STRUCTURES AND TO VERIFY BTU LOAD.
 NOTE: THE MANUFACTURER SPECIFICATIONS REQUESTED FOR THE
 RESUBMITTAL INDICATING THE RECOMMENDED SETBACKS OF
 GENERATOR TO STRUCTURES WAS NOT PROVIDED. PLEASE
 PROVIDE THIS INFORMATION ON THE NEXT RESUBMITTAL.
  
 3. **OK**
  
 4. **OK**
  
 5. **OK**
  
 ** THE FOLLOWING IS A NEW COMMENT **
  
 6. SHEET C-1: THE LONGEST RUN OF 31' ON THE RESUBMITTED
 GAS ISOMETRIC IS WRONG. THE CORRECT LONGEST RUN ON THE
 GAS SYSTEM IS 44' FROM THE NEWLY PROVIDED INFORMATION.
 PLEASE CORRECT THIS ON THE RESUBMITTAL.
  
 ******IMORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-02-14 Cont ID  
Sent By mperson Date 2007-02-14 Time 09:56 Rev Time 0.45
Received By mperson Date 2007-02-14 Time 09:56 Sent To B
Notes
2007-02-14 10:22:10DENIED
 REFERENCE: FBC-2004 FUEL GAS; CITY OF WEST PALM BEACH
 GAS PERMIT APPLICATION REQUIREMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. VALUE OF GENERATOR IS TO LOW.
 PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 2. PLEASE PROVIDE MANUFACTURER SPECIFICATIONS
 INDICATING RECOMMENDING SETBACKS OF GENERATOR TO
 STRUCTURES AND TO VERIFY BTU LOAD.
  
 3. SHEET C-1 INDICATES THE EXISTING GAS PIPE TO THE
 EXISTING WATER HEATER BEING 3/8". THIS IS WRONG PER
 FBC-2004 TABLE 402.4(8) AND FBC-2004 FUEL GAS , SECTION
 402.4.1 LONGEST LENGTH METHOD, THE GAS PIPE TO THE
 EXISTING WATER HEATER NEEDS TO BE INCREASED TO 1/2".
 PLEASE REFERENCE THE ATTACHED TABLE INDICATING THIS.
 PLEASE CORRECT AND RESBMIT.
  
 4. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED ON
 THE GAS ISOMETRIC ON SHEET C-1. PLEASE CORRECT AND
 RESUBMIT.
  
 5. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: NOT ALL MATERIAL TYPES ARE INDICATED ON THE GAS
 ISOMETRIC ON SHEET C-1. PLEASE CORRECT AND RESUBMIT.
  
 ******IMORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 16:18 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 16:18 Sent To Z
Notes
2007-08-16 16:18:44TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-20 Cont ID  
Sent By adarroug Date 2007-07-20 Time 16:54 Rev Time 0.00
Received By adarroug Date 2007-07-20 Time 16:54 Sent To E
Notes
2007-07-20 16:54:35TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-06-18 Time 16:02 Rev Time 0.00
Received By adarroug Date 2007-06-18 Time 16:02 Sent To E
Notes
2007-06-18 16:03:10TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-05 Cont ID  
Sent By adarroug Date 2007-02-05 Time 13:50 Rev Time 0.00
Received By adarroug Date 2007-02-05 Time 13:50 Sent To E
Notes
2007-02-05 13:51:03TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-21 Cont ID  
Sent By mmclean Date 2007-02-21 Time 15:36 Rev Time  
Received By shill Date 2007-01-29 Time 11:03 Sent To  
Notes
2007-01-29 11:04:07TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-08-29 Cont ID  
Sent By tgordon Date 2007-08-29 Time 11:10 Rev Time 0.30
Received By tgordon Date 2007-08-29 Time 11:10 Sent To  
Notes
2007-08-29 11:11:09PASSED REVIEW ON 8-6-07.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-06 Cont ID  
Sent By tgordon Date 2007-08-06 Time 10:27 Rev Time 0.20
Received By tgordon Date 2007-08-06 Time 10:27 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-03 Cont ID  
Sent By tgordon Date 2007-07-03 Time 08:33 Rev Time 0.25
Received By tgordon Date 2007-07-03 Time 08:33 Sent To B
Notes
2007-07-03 08:34:57*** DENIED ***
 1) AS NOTED IN LAST REVIEW 2-13-07. GENERATOR IS TO
 CLOSE TO WOOD FENCE, SEE NFPA 37 4.1.4.
  
 2) SEE ZONING REVIEW PROVISO, PLEASE CORRECT GENERATOR
 DISTANCE TO WOOD FENCE.
  
 3) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 4) SEE ATTACHED NOTICE FS 553.80(2)(B)
 REGARDING FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-13 Cont ID  
Sent By tgordon Date 2007-02-13 Time 13:55 Rev Time 0.25
Received By tgordon Date 2007-02-13 Time 13:55 Sent To G
Notes
2007-02-13 14:11:46*** DENIED ***
 1) GENERATOR IS TO CLOSE TO WOOD FENCE, SEE NFPA 37
 4.1.4.
  
 2) SEE ZONING REVIEW PROVISO, PLEASE CORRECT GENERATOR
 DISTANCE TO WOOD FENCE.
  
 3) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-03 Cont ID  
Sent By choops Date 2007-08-03 Time 08:40 Rev Time 0.00
Received By choops Date 2007-08-03 Time 08:40 Sent To P
Notes
2007-08-03 08:41:06APPROVED LOCATION OF GENERATOR.

Review Stop Z ZONING
Rev No 1 Status P Date 2007-02-01 Cont ID  
Sent By mmclean Date 2007-02-01 Time 10:32 Rev Time 0.00
Received By mmclean Date 2007-02-01 Time 10:32 Sent To I
Notes
2007-02-01 10:36:10PROVISO: THE PROPOSED GENERATOR SHALL NOT BE CLOSER
 THAN 6FT FROM SIDE AND 6FT REAR PROPERTY LINE.