Plan Review Details - Permit 07011099
Plan Review Stops For Permit 07011099
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By mjacobs Date 2007-03-12 Time 10:32 Rev Time 0.00
Received By mjacobs Date 2007-03-09 Time 15:20 Sent To PC
Notes
2007-03-09 16:46:12BUILDING PLAN REVIEW
 PERMIT: 07011099
 ADD: 14228TH STREET
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3)WPB AMENDMENTS 108.3*IF, IN THE OPINION OF THE
 BUILDING OFFICIAL THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALLBE
 THE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 ARCHITECTURAL AND DESIGN FEES, EXCLUDING LAND. OUR
 VALUATION REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND
 MEANS COST ANALYSIS SERVICES.
  
 4)THE REFERENCE TO SEC. 905.22 F.B.C. ON SHEET 2 OF
 5HAS NOTHING TO DO WITH SMOKE DECTORS. SEE2004
 RESIDENTIAL F.B.C. SEC.313 FOR MORE INFORMATION. AND
 EITHER REMOVE THAT REFERENCE OR SHOW WHERE IT APPLIES
 TO THIS PROJECT.
  
 5)R807.1 ATTIC ACCESS .
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 6)ON THE ELEVATION DETAILS SHOW THE DIMENTIONS OF THE
 WINDOWS INCLUDING THE HEIGHT OF THE WIDOWSILL AND THE
 DISTANCE BETWEEN EACH WINDOW AND FROM THE CORNERS.
  
 7)THE MINIMUM UNIFORM DISTRIBUTED LIVE LOAD FOR
 ATTICS WITHOUT STORAGE IS 10PSF. THE REPORT FROM THE
 TRUSS DESIGN ENGINEER INDICATE A 0.0 BCLL. CLARIFY.
  
 8)61G15-23.002 (2)ALL INFORMATION BEING FILED FOR
 PUBLIC RECORD SHALL BE ORIGINALLY SIGN AND SEALED.THE
 SIGNATURE ON THE TRUSS REPORTS IS A PHOTO COPY.EACH
 SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED UNDER
 THE PROVISIONS OF CH.471, F.S., SHALL BE SEALED, SIGNED
 AND DATED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE
 CHARGE. ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME,ADDRESS,AND LICENSE NUMBER ON EACH SHEET.
  
 9) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.THE PRODUCT APPROVALS SHALL
 BE APPROVED IN WRITING BY THE DESIGNER OF RRECORD.
  
 10) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 ) NUMBER OF FLOORS
 ) NUMBER OF BEDROOMS
 ) NUMBER OF ROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By btrobaug Date 2007-02-06 Time 09:53 Rev Time 0.75
Received By btrobaug Date 2007-02-06 Time 07:50 Sent To P
Notes
2007-02-06 09:53:16 
  
 NONCOMPLIANT
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} SHOW THE PHYSICAL LOCATION OF ALL SERVICE EQUIPMENT
 ON THE PLAN. 215.5.
  
 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.THIS IS
 ALSO A REQUIREMENT OF THIS DEPARTMENT.
  
 3} THRE ARE CONFLICTING NOTES ON SHEET 5 OF 5 AND 2 OF
 5 REGARDING THE SERVICE FEED BEING OVERHEAD OR
 UNDERGROUND. MAKE A DETERMINATIION AND INDICATE SAME ON
 PLANS, CORRELATE NOTES.
  
 4} NOTE 26 SHEET 2 OF 5 MENTIONS INSTALLING A 200 AMP
 MAIN IN THE EXISTING 100 AMP PANEL. INDICATE THE
 VOLTAGE AND AMPERAGE RATING OF THE PANEL ON THE PLAN SO
 THAT UL RATING CAN BE REVIEWED.
  
 5} NOTE 29,SHEET 2 OF 5 INCORRECTLY REFERENCES FBC
 ARTICLE 905.2.2. THE SMOKE ALARM REFERENCE FOR
 RESIDENTIAL OCCUPANCIES IS R313.1.1.
  
 6} PLEASE SUBMITPANEL SCHEDULES PER 106 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-05 Cont ID  
Sent By adarroug Date 2007-02-05 Time 09:32 Rev Time 0.00
Received By adarroug Date 2007-02-05 Time 09:32 Sent To E
Notes
2007-02-05 09:32:34TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-03-12 Time   Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 10:55 Sent To  
Notes
2007-01-29 10:55:57TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-07 Cont ID  
Sent By tgordon Date 2007-02-07 Time 09:28 Rev Time 0.30
Received By tgordon Date 2007-02-07 Time 09:28 Sent To B
Notes
2007-02-07 09:33:31*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.2.2.
  
 2) NO MECHANICAL PLANS WERE SUBMITTED FOR
 REVIEW. PLEASE SUBMIT MECHANICAL PLANS
 FOR REVIEW, PER 2004 FBC WPB AMEND. 106.3.5.4, AS
 MECHANICAL PERMIT NUMBER 07011131 HAS BEEN APPLIED
 FOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-02-07 Cont ID  
Sent By jleech Date 2007-02-07 Time 07:10 Rev Time 0.00
Received By jleech Date 2007-02-07 Time 07:10 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-03 Cont ID  
Sent By mmclean Date 2007-02-03 Time 09:38 Rev Time 0.00
Received By mmclean Date 2007-02-03 Time 09:38 Sent To I
Notes
2007-02-03 09:39:28DENIED,
 1. PLEASE PROVIDE A COPY OF THE CURRENT SURVEY.
 2. NO SURVEY WAS SUBMITTED INTO PACKAGE.
 3. PLEASE SHOW THE LOCATION OF THE A/C UNIT ON THE TWO
 COPIES OF SITEPLAN.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720