Plan Review Details - Permit 07011083
Plan Review Stops For Permit 07011083
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-01-29 Cont ID  
Sent By lursu Date 2007-01-29 Time 14:18 Rev Time 0.00
Received By lursu Date 2007-01-29 Time 14:10 Sent To  
Notes
2007-01-29 14:23:35PERMIT HAS BEEN ATTACHED TO THE CORRECT UNIT #
 0001,UNDER PCN = 74434403010004860
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-09-12 Cont ID  
Sent By shill Date 2007-09-12 Time 19:14 Rev Time 0.00
Received By shill Date 2007-09-12 Time 19:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-08-31 Cont ID  
Sent By shill Date 2007-08-31 Time 14:38 Rev Time 0.00
Received By shill Date 2007-08-31 Time 14:38 Sent To  
Notes
2007-08-31 14:39:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)TWO SETS REQUIRED.ONE SET IS A PHOTOCOPY.
 ENGINEERING IS TO BE ORIGINAL, FS471.
  
 2.)SHEET 4 STILL SHOWS SCUPPERS ON THE STRUCTURAL
 DETAIL.PLEASE CHECK ALL SHEETS AND AS THE ENGINEER
 HAS DETERMINED THAT SCUPPERS ARE NOT REQUIRED, REMOVE
 REFERENCES FROM THE PLAN.
  
 3.)APPLICATION DESCRIPTION IS NOT CONSISTENT WITH THE
 PLAN.APPLICATION STATES THAT INSULATION WILL BE
 INSTALLED.WHERE?WHAT TYPE?PROVIDE A DETAIL/PLAN.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-29 Cont ID  
Sent By shill Date 2007-08-29 Time 09:34 Rev Time 0.00
Received By shill Date 2007-08-29 Time 09:29 Sent To P
Notes
2007-08-29 09:35:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)THE ENGINEER'S LETTER HAS BEEN ALTERED (FROM
 SCUPPERS "WILL BE" ADDED TO "MAY BE").SCUPPERS ARE A
 PART OF THE ENGINEER'S DESIGN AND THE LETTER CAN ONLY
 BE CHANGED BY THE ENGINEER.EITHER SUBMIT A LETTER
 WHICH HAS NOT BEEN ALTERED OR HAVE THE ENGINEER REVISE
 THE LETTER AND PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-19 Cont ID  
Sent By shill Date 2007-03-19 Time 18:07 Rev Time 0.00
Received By shill Date 2007-03-19 Time 18:07 Sent To  
Notes
2007-03-19 18:36:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)SE FBC R 301.1, "BUILDINGS AND STRUCTURES, AND ALL
 PARTS THEREOF, SHALL BE CONSTRUCTED TO SAFELY SUPPORT
 ALL LOADS . . . INCLUDING WIND LOADS."THE DETAIL
 PROVIDED IS NOT STRUCTURALLY CONTINUOUS; IT DIVIDES THE
 WALL INTO TWO PARTS AND DOES NOT ADDRESS HOW THE NEW
 PARAPET WILL WITHSTAND WIND LOADS.THE DETAIL IS NOT
 CLEAR; STATES "SPT66 STRAPS AT TOP & BOTTOM OF EACH
 STUD", AND "STRAPS AT EA STUD TOP & BOTTOM OVER & UNDER
 PLATES."WHEN RESUBMITTING, INCLUDE THE STRAPS IN THE
 STRUCTURAL DETAIL.
  
 2.)SPT66 IS FOR 6" FRAMING.2X4 FRAMING IS SHOWN ON
 YOUR DETAIL.SPT66 DOES NOT PROPERLY ADDRESS ITEM #1.
 HOWEVER, WHEN REDESIGNING THE WALL DETAIL, PLEASE
 CONFIRM THAT THE CONNECTORS SPECIFIED ARE THE CORRECT
 SIZE FOR FRAMING SPECIFIED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-08 Cont ID  
Sent By shill Date 2007-02-08 Time 17:25 Rev Time 0.00
Received By shill Date 2007-02-08 Time 17:25 Sent To P
Notes
2007-02-08 17:38:51SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PROVIDE STRUCTURAL PLANS PREPARED BY AN ENGINEER
 OR ARCHITECT.
  
 2.)PROVIDE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 3.)PROVIDE A DRAINAGE PLAN.PROVIDE CALCULATIONS.
 FBC 15.
  
 4.)PROVIDE INFORMATION AS TO HOW THE ROOF WILL BE
 PITCHED TO PROPERLY DRAIN.
  
 5.)PROVIDE INFORMATION IN REGARDS TO THE EXISTING
 ROOF (DESIGN LIVE LOAD).SHOW THAT THE EXISTING ROOF
 CAN ACCOMODATE THE ADDITIONAL LIVE LOAD OF RAINWATER.
  
 6.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 09:34 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 09:34 Sent To B
Notes
2007-09-07 09:34:35TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-24 Cont ID  
Sent By adarroug Date 2007-08-24 Time 14:38 Rev Time 0.00
Received By adarroug Date 2007-08-24 Time 14:38 Sent To B
Notes
2007-08-24 14:38:15TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-02 Cont ID  
Sent By adarroug Date 2007-03-02 Time 11:24 Rev Time 0.00
Received By adarroug Date 2007-03-02 Time 11:24 Sent To P
Notes
2007-03-02 11:24:52TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-08 Cont ID  
Sent By shill Date 2007-02-08 Time 17:39 Rev Time 0.00
Received By shill Date 2007-01-29 Time 09:08 Sent To  
Notes
2007-01-29 09:08:15TO "MISC" BOX#1

Review Stop P PLUMBING
Rev No 2 Status N Date 2007-03-13 Cont ID  
Sent By mperson Date 2007-03-13 Time 09:21 Rev Time 0.00
Received By mperson Date 2007-03-13 Time 09:21 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-09 Cont ID  
Sent By mperson Date 2007-02-09 Time 16:03 Rev Time 0.45
Received By mperson Date 2007-02-09 Time 16:03 Sent To PC
Notes
2007-02-09 16:37:44DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. MUST PROVIDE A ROOF PLAN THAT INDICATES HOW THE ROOF
 WILL BE PITCHED TO PROPERLY DRAIN, AND INDICATE THE
 FOLLOWING INFORMATION PER THE FOLLOWING CODE
 REFERENCES.
 A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF
 AND VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS
 AND SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004
 PLUMBING, SECTIONS 1106.
 B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004
 PLUMBING, SECTION 1106.2.
 C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION
 1106.4.
 D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING,
 SECTIONS 1503.4.2 AND 1503.4.3 ) SIZE PER FBC-2004
 PLUMBING, TABLE 1106.7.
 E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004
 PLUMBING, SECTION 1107.
 A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004
 PLUMBING, SECTION 1107.1.
 B) SEPERATE SYSTEMS REQUIRED, PER FBC-2004 PLUMBING,
 SECTION 1107.2.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721