Plan Review Details - Permit 07010935
Plan Review Stops For Permit 07010935
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-29 Cont ID  
Sent By rmcdouga Date 2007-01-29 Time 18:45 Rev Time 0.00
Received By rmcdouga Date 2007-01-29 Time 18:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-18 Cont ID  
Sent By rmcdouga Date 2007-01-18 Time 10:58 Rev Time 0.00
Received By rmcdouga Date 2007-01-18 Time 10:58 Sent To  
Notes
2007-01-18 11:27:23DENIED BY BUILDING
  
 1)INDICATE WHICH ONE OF THE APPROVED ASSEMBLIES AND
 ITS CORRESPONDING DESIGN PRESSURE WILL BE INSTALLED.
 CIRCLE THE APPROPRIATE ONE ON PAGE 26 OF THE NOA.
  
 2) THE FASTENER SPACING LISTED FOR THE FIELD ON THE
 HVHZ FORM DOES NOT MATCH ANY OF THE FASTENING OPTIONS
 ON PAGE 26 OF THE PRODUCT APPROVAL.
  
 3) USING THE FASTENER SPACING FOR THE BASE SHEET
 ATTACHMENT FOR RING SHANK NAILS AND TIN CAPS WITH
 MAXIMUM DESIGN PRESSURE OF -45 PSF IN THE RAS 117
 CALCULATIONS, THE SPACING FOR THE CORNERS WILL BE 5" ON
 CENTER AT THE LAP AND TWO ROWS AT 5" OC.PROVIDE RAS
 117 CALCULATIONS AS REQUIRED BY LIMITATION # 7 ON PAGE
 32 OF THE PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-29 Cont ID  
Sent By adarroug Date 2007-01-29 Time 16:53 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 16:53 Sent To B
Notes
2007-01-29 16:53:45TO "RMCDOUGAL" DESK/RESUB