| Plan Review Stops For Permit 07010901 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-08-09 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-08-09 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-08-09 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2007-08-09 13:19:04 | BUILDING REVIEW COMMENTS | | | | | | | | | | | | 1) | | | SINCE YOUR PROJECT IS CLASSIFIED FULLY SPRINKLED , FL. | | | STATUTE 553.79(2) REQUIRES SPRINKLER DESIGN (HEAD | | | LAYOUT) AT TIME OF PERMIT SUBMITTAL. | | | | | | 2) | | | CONSTRUCTION TYPE ON COVER SHEET SHALL REFLECT TYPE | | | IIA , W/1HR. STRUCTURAL ELEMENTS. SEE TABLE 601, 2004 | | | FBC. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | L. MARTINEZ | | | 561-805-6710 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-07-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-07-19 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
|
Date |
2007-07-27 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2007-07-19 11:01:51 | BUILDING PLAN REVIEW | | | PERMIT: 07010901 | | | ADD: 223 CLEMATIS ST | | | CONT: MYRICK ENTERPRISES | | | TEL: (954)445-2451 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RD REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) COMPLIED. | | | | | | 3) 3RD REQUEST,FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLYCOMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE | | | IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 4) 3RD REQUEST, 4) THE PERMIT APPLICATION, DESSCRIPTION | | | OF WORK, INDICATES ONLY A INTERIOR DEMOLITION PERMIT | | | WHERE AS PLANS INDICATE ADDITIONAL SCOPE OF WORK. | | | PLEASE CORRECT THE PERMIT APPLICATION TO INCLUDE THE | | | LARGER SCOPE OF WORK.106.1.2*OR IF A TRUE INTERIOR DEMO | | | INDICATE SUCH ON PLAN. | | | | | | 5) COMPLIED. | | | | | | 6A) COMPLIED. | | | | | | 6B) COMPLIED. | | | | | | 6C) COMPLIED. | | | | | | 6D)ERROR, THE BUILDING TYPEOF CONSTRUCTION, AS | | | DEFINED IN CHAPTER 3. THIS BUILDING IS A TYPE II-A TO | | | BE SPRINKLERED. THIS IS A 4 STORY BUILDING,WITH THE 1 | | | STORY INCREASE FROM A FULLY SPRINKLED BUILDING! | | | THE OWNERS ARE TAKING THE AREA INCREASES GIVEN TO THEM | | | BY THE SPINKLERS. | | | THIS MEANS THIS SPACE WILL REQUIRE FIRE SPRINKLERS AND | | | FIRE SPRINKLER PLANS. | | | | | | 6ECOMPLIED. | | | | | | 6F) YES A FIRE SPRINKLER WILL BE REQUIRED. | | | | | | 6G-H) COMPLIED. | | | | | | 7)COMPLIED. | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-03-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-03-06 |
Time |
16:47 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-03-06 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2007-03-06 16:50:17 | BUILDING PLAN REVIEW | | | PERMIT: 07010901 | | | ADD: 223 CLEMATIS ST | | | CONT: MYRICK ENTERPRISES | | | TEL: (954)445-2451 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) COMPLIED. | | | | | | 3) 2ND REQUEST,FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLYCOMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE | | | IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 4) 2ND REQUEST, 4) THE PERMIT APPLICATION, DESSCRIPTION | | | OF WORK, INDICATES ONLY A INTERIOR DEMOLITION PERMIT | | | WHERE AS PLANS INDICATE ADDITIONAL SCOPE OF WORK. | | | PLEASE CORRECT THE PERMIT APPLICATION TO INCLUDE THE | | | LARGER SCOPE OF WORK.106.1.2*. | | | | | | 5) COMPLIED. | | | | | | 6A) COMPLIED. | | | | | | 6B) COMPLIED. | | | | | | 6C) COMPLIED. | | | | | | 6D) TYPE OF CONSTRUCTION, AS DEFINED IN CHAPTER 3. THIS | | | BUILDING IS A TYPE II-B TO BE SPRINKLERED. | | | THE OWNERS ARE TAKING THE AREA INCREASES GIVEN TO THEM | | | BY THE SPINKLERS. | | | THIS MEANS THIS SPACE WILL REQUIRE FIRE SPRINKLERS AND | | | FIRE SPRINKLER PLANS. | | | | | | 6ECOMPLIED. | | | | | | 6F) YES A FIRE SPRINKLER WILL BE REQUIRED. | | | | | | 6G-H) COMPLIED. | | | | | | 7) 2ND REQUEST, THE EXITING CONFIGURATION OF THE REAR | | | CORRIDOR WILL BE RECONFIGURED TO SOME EXTENT WITH THE | | | MODIFICATIONS THAT OF THE REAR EXIT REQUIREMENTS FOR | | | THE | | | WEST SECOND STORY STAIRWELL ( A COMMON STAIRWELL | | | SERVING 2 OR MORE TENANTS) AND VESTIBULE ON THE FIRST | | | FLOOR THAT WILL TAKE PLACE. 2004 EXISTING BUILDING CODE | | | CHAPTER 8 CHANGE IN OCCUPANCYSEE TABLE 812.4.1. | | | | | | IFTHERE ARE ANY QUESTIONS PLEASE CALL: | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-01-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-01-22 |
Time |
08:31 |
Rev Time |
0.77 |
| Received By |
mawillia |
Date |
2007-01-22 |
Time |
08:31 |
Sent To |
Z |
|
| Notes |
| 2007-01-22 08:45:19 | BUILDING PLAN REVIEW | | | PERMIT: 07010901 | | | ADD: 223 CLEMATIS ST | | | CONT: MYRICK ENTERPRISES | | | TEL: (954)445-2451 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) VALUE FOR THE SCOPE OF WORK IS LOW , PLEASE PROVIDE | | | ACURATE VALUE OF | | | DESCRIBED WORK OR CITY WILL CALCULATE VALUE OF WORK | | | FROM MARSHAL AND SWIFT OR ICC | | | VALUES. 108.3* WEST PALM ADMINISTRATIVE CODE. | | | | | | 3 ) ONCE VALUES ARE INCREASED A NOC WILL BE REQUIRED: | | | FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 4) THE PERMIT APPLICATION, DESSCRIPTION OF WORK, | | | INDICATES ONLY A INTERIOR DEMOLITION PERMI, | | | WHERE AS PLANS INDICATE ADDITIONAL SCOPE OF WORK. | | | PLEASE CORRECT SO BOTH WILL REFLECT THE TRUE NATURE OF | | | THIS PERMIT. | | | 106.1.2* | | | | | | 5)PLANS, SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | | BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 6)) 110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WAS ISSUED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) LEVEL OF ALTERATIONS: | | | D) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | E) THE DESIGN OCCUPANT LOAD, SEE 1004. | | | F) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | H) NUMBER OF FLOORS | | | | | | 7) THE EXITING CONFIGURATION OF THE REAR CORRIDOR DOES | | | NOT REFLECT WHAT ACTUALLY OCCURS AT THE SITE. | | | A NOTE OF CAUTION. THE WEST EXIT OF THE NEWLY EXPANDED | | | MONKEY CLUB( IN FOR PERMIT AT THIS TIME) MAY | | | CAUSE SOME RECONFIGURATION ON THE FIRST FLOOR TO MEET | | | EGRESS REQUIREMENTS, THIS MAY AFFECT YOUR PROJECT. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
N |
Date |
2007-07-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-19 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-19 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2007-07-19 14:08:07 | CONTRACTOR CAME IN AND ADJUSTED PERMIT APPLICATION FOR | | | SCOPE OF WORK TO MATCH PLANS. | | | | | | ** PLANS SHOW ALL ELECTRICAL AS EXISTING AND NO NEW | | | ELECTRICAL WORK IS BEING DONE. | | | IF ANY DEMO WORK INCLUDES AREAS WHERE ELECTRICAL IS | | | PRESENT, ELECTRICAL CONTRACTOR IS TO OBTAIN AN | | | ELECTRICAL DEMO PERMIT TO SAFE OFF ELECTRICAL SYSTEMS. | | | ** ALL OTHER ELECTRICAL IS EXISTING TO REMAIN. ANY NEW | | | WORK SHALL BE PERMITTED WITH PLANS AND WILL BE REQUIRED | | | TO MEET CURRENT NEC AND FBC. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-13 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-13 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2007-07-13 18:12:06 | ** UNSAT ** | | | | | | 1) NOTE: PLANS ARE TOREMAIN IN *F* STATUS UNTIL | | | CLARIFICATION IS OBTAINED FOR BELOW. | | | PERMIT APPLICATION STILL INDICATES THIS SCOPE OF WORK | | | IS FOR "INTERIOR DEMO ONLY" AND NOT TO DO ANY NEW | | | INSTALLATION OF OTHER ITEMS WHICH ARE BEING SHOWN ON | | | PLANS. THIS WAS STATED BY OTHER TRADE REVIEWERS AS | | | WELL. | | | PLEASE SEE THE PLANS INDICATE WORK WHICH IS NOT STATED | | | ON PERMIT APPLICATION. IS THIS APPLICATION FOR INTERIOR | | | DEMO WORK AS STATED OR IS OTHER WORK BEING DONE AS | | | STATED ON PLANS? PLEASE KNOW IN EITHER CASE PLANS | | | INDICATE ALL ELECTRICAL IS EXISTING AND WILL NOT BE | | | TOUCHED, RELOCATED, REMOVED ETC. | | | PLANS ALSO STILL INDICATES A * NEW EQUIPMENT* SCHEDULE | | | AND LOCATIONS OF EQUIPMENT. IS THIS EQUIPMENT BEING FED | | | FROM ALL EXISTING LOCATIONS WHICH ALREADY PROVIDE | | | ELECTRICAL FOR ELECTRICAL EQUIPMENT? | | | PLEASE SEE PLANS DO CONTAIN NOTES THAT *ALL* ELECTRICAL | | | IS EXISTING INCLUDING LIGHTS, RECEPTACLES ETC.!!! | | | PLEASE KNOW, THAT IF ANY ELECTRICAL WORK IS BEING DONE, | | | PLANS AND PERMIT APPLICATION NEED TO BE REVISED. | | | ELECTRICAL WORK FOR ANY REPLACEMENT, NEW INSTALLED OR | | | CHANGED OUT ELECTRICAL WILL REQUIRE CURRETN CODE | | | COMPLIANCE. AT THIS TIME, PERMIT APPLICATION IS FOR | | | *INTERIOR DEMO* ONLY AS CLEARLY STATED ON PERMIT | | | APPLICATION. | | | THIS INFORMATION ABOVE NEEDS TO BE CLEARED UP BY THE | | | CONTRACTOR AND/OR DESIGNER OF RECORD.IF NO ELECTRICAL | | | WORK IS BEING AFFECTED OR DONE, THEN THE REVIEW STATUS | | | WILL CHANGE TO AN *N* AND A PERMIT WILL BE REQUIRED FOR | | | ANY ELECTRICAL DEMO WORK BEFORE COMMENCING BUILDING | | | DEMO WORK AS STATED. | | | | | | ** PLEASE SEE PERMIT APPLICATION HAS ALWAYS STATED | | | INTERIOR DEMO WORK ONLY. | | | | | | PLEASE CALL IF THERE IS ANY QUESTIONS OR INFORMATION | | | WHICH CAN BE PROVIDED. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT. | | | 561-805-6717 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-03-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-05 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-05 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2007-03-05 15:30:12 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE KNOW AT THIS TIME THE MEANS OF EGRESS | | | FOR THIS SPACE AND FOR OTHER TENANT BUILD OUTS ARE IN | | | QUESTION. PLEASE KNOW THAT THERE WILL BE WORK UNDER | | | SEPARATE WHICH MAY AFFECT THE EGRESS AND EXIT OF THIS | | | SPACE. | | | | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-01-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-21 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-21 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2007-01-21 13:26:12 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE THE VALUE FOR THE SCOPE OF WORK | | | BEING DICTATED ON PLANS IS EXTREMELY LOW FOR SCOPE OF | | | WORK SHOWN. | | | PLEASE SEE FBC ADMIN SECTION 108.3 | | | PLEASE KNOW IF ONE IS NOT ADJUSTED FOR SCOPE AS SHOWN | | | ON PLANS, ONE WILL BE ASSESSED USING THE FBC AND | | | METHODS ADOPTED INTO THE 2004 FBC AND THE FBC | | | ADMINISTRATIVE SECTIONS TO THE FBC. | | | | | | 2) NOTE: PLEASE SEE THE CODES RELEVANT FOR SCOPE OF | | | WORK SHALL BE STATED ON PLANS. | | | 2006 REVISIONS TO THE 2004 FBC, 2003 NFPA-101, 2002 | | | NFPA-72 AND THE 2005 NFPA-70. | | | PLEASE SEE PLANS SHALL STATE THE OCCUPANCY, LOAD ETC, | | | WHICH WILL BE IN BUILDING REVIEW NOTES. | | | | | | 3) NOTE: PLEASE SEE PLANS SHALL BE SIGNED, DATED AND | | | SEALED BY THE ARCHITECT OF RECORD AS LISTED ON PLANS. | | | FAC 61G1-16, FS 481.221 | | | FBC ADMIN SECTION 106.1 | | | | | | 4) NOTE: PLEASE INDICATE NEW OR EXISTING REMAIN | | | EMERGENCY LIGHT FIXTURES AND EXIT LIGHTING AS REQUIRED | | | PER NFPA-101 7.8 AND 7.9. | | | PLEASE ALSO SEE 700.12E AS CIRCUITING SHALL MEET THIS | | | SECTION, IF IT DOES NOT ALREADY. | | | **PLEASE BE SURE TO SEE POSSIBLE FIRE REVIEW COMMENTS. | | | | | | 5) NOTE: PLEASE SEE PLANS MENTIONS REPLACING CEILING | | | GRID, PLEASE PROVIDE LIGHTING LAYOUT FOR EXISTING OR | | | NEW FIXTURES FOR LOCATIONS. THIS CAN BE DONE AS | | | REFLECTED CEILING PLANS IF ALL EXISTING. IF ANY OF | | | THESE FIXTURES ARE GOING TO BE NEW, THEN PLEASE PROVIDE | | | ON ELECTRICAL SHEETS ALONG WITH NOTE #4 ABOVE. | | | | | | | | | ** PLEASE KNOW AS THE COMPLETE SCOPE OF WORK IS NOT | | | EXACTLY CLEAR AT THIS TIME, THERE MAY BE COMMENTS ON | | | THE NEXT REVIEW DEPENDING ON THE PLANS AND INFORMATION | | | PROVIDED. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-07-24 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-24 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-24 |
Time |
17:17 |
Sent To |
|
|
| Notes |
| 2007-07-24 17:37:39 | *****PROVISO***** | | | | | | 1.ON SHEET NO. T-1, INTERIOR FINISH CLASSIFICATION | | | SHALL BE WORDED AS CLASS IN LIEU OF TYPE.FOR EXAMPLE, | | | EXIT -CLASS B,NOT EXIT - TYPE B | | | | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-02-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-02-06 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-02-06 |
Time |
14:56 |
Sent To |
Z |
|
| Notes |
| 2007-02-06 15:42:13 | *****DENIED***** | | | | | | | | | 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE | | | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 4.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE | | | OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE. | | | | | | 5.INDICATE THE LOCATION OF FIRE EXTINGUISHERS, EXIT | | | LIGHTS, EMERGENCY LIGHTS, FIRE SPRINKLERS, FIRE ALARM | | | DEVICES, ETC.HOW WILL THEY BE AFFECTED BY THE SCOPE | | | OF WORK? | | | | | | 6.WHAT IS THE INTERIOR FINISH CLASSIFICATION FOR THE | | | WALLS SND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, | | | AND IN OTHER AREAS? | | | | | | 7.WHAT IS THE OCCUPANT LOAD FOR THIS STRUCTURE AS | | | DETERMINED PER THE OCCUPANT LOAD FACTORS OF NFPA 101, | | | TABLE 7.3.1.2 THAT ARE CHARACTERISTIC OF THE USE OF THE | | | SPACE OR SHALL BE DETERMINED AS THE MAXIMUM PROBABLE | | | POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER | | | IS GREATER. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | ITEM WAS ADDRESSED ON THE PLAN. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-12 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-12 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2007-07-27 08:19:42 | 7/27/07--PLANS TAKEN FROM "BOB"#15 AND ROUTED TO | | | "LMARTINEZ" DESK | | 2007-07-13 10:36:12 | TO "BOB"#15 | | 2007-07-12 10:04:17 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-02 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-02 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2007-03-05 08:44:37 | TO "BOB"#3 | | 2007-03-02 16:22:24 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-02-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-09 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-20 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2007-01-20 14:38:17 | TO "BOB"#6 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2007-01-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-01-22 |
Time |
11:56 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2007-01-22 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2007-01-22 11:57:38 | NO MECHANICAL PLANS SUBMITTED, AND NO | | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | | THIS TIME. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-27 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-07-27 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-07-27 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2007-07-27 10:24:09 | NO PLUMBING PLANS SUBMITED. | | | PLUMBING CONTRACTOR TO SUBMIT ENGINEERED SEALED PLANS, | | | REVIEWED BY THE DEPARTMENT OF BUSINESS AND PROFESSIONAL | | | REGULATION DIVISION OF HOTEL AND RESTAURANTS AND | | | APPROVED BY THE UTILITY DEPARTMENT FOR COMPLIANCE TO | | | WASTE ORDINANCE # 3434. CONTACT PERSON IS RODNEY COMPO | | | PHONE # 822-2272 FOR GREASE TRAP APPROVAL. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-03-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-03-10 |
Time |
06:26 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-03-10 |
Time |
06:26 |
Sent To |
|
|
| Notes |
| 2007-03-10 06:28:36 | PLUMBING DEMO OK. | | | NOT ENOUGH INFORMATION FOR A PLUMBING PLAN REVIEW. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-01-29 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-01-29 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-01-29 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2007-01-29 09:14:31 | DENIED; | | | 1.PLANS NOT SIGNED OR SEALED. | | | 2. NOT ENOUGH INFORMATION TO DO A PLAN REVIEW; | | | A) IS THIS A NEW BUSINESS? | | | B) IS THIS A NEW RESTAURANT? | | | C) SIZE (SQ. FT.) | | | D) NUMBER OF OCCUPANTS | | | 3.SINK TO BE REMOVED; | | | A) IS SINK A REQUIRED HAND SINK | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2007-07-19 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-07-19 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-07-19 |
Time |
17:46 |
Sent To |
|
|
| Notes |
| 2007-07-19 17:47:16 | *VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | | IMPROVEMENT VALUE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-02-09 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2007-02-09 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2007-02-09 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2007-02-09 10:26:03 | ZONING REVIEW: NOT REQUIRED | | | | | | - PROJECT SCOPE INCLUDES ONLY INTERNIOR DEMOLITION | | | - NO EXTERIOR MODIFICATIONS NOTED ON PLANS | | | | | | MATT FLIS 822-1445 |
|
|