Plan Review Details - Permit 07010901
Plan Review Stops For Permit 07010901
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-08-09 Cont ID  
Sent By lmartine Date 2007-08-09 Time 12:34 Rev Time 0.00
Received By lmartine Date 2007-08-09 Time 12:34 Sent To  
Notes
2007-08-09 13:19:04BUILDING REVIEW COMMENTS
  
  
  
 1)
 SINCE YOUR PROJECT IS CLASSIFIED FULLY SPRINKLED , FL.
 STATUTE 553.79(2) REQUIRES SPRINKLER DESIGN (HEAD
 LAYOUT) AT TIME OF PERMIT SUBMITTAL.
  
 2)
 CONSTRUCTION TYPE ON COVER SHEET SHALL REFLECT TYPE
 IIA , W/1HR. STRUCTURAL ELEMENTS. SEE TABLE 601, 2004
 FBC.
  
  
  
  
  
  
  
  
  
 L. MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-07-19 Cont ID  
Sent By jwitmer Date 2007-07-19 Time 10:56 Rev Time 0.00
Received By   Date 2007-07-27 Time 10:07 Sent To  
Notes
2007-07-19 11:01:51BUILDING PLAN REVIEW
 PERMIT: 07010901
 ADD: 223 CLEMATIS ST
 CONT: MYRICK ENTERPRISES
 TEL: (954)445-2451
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED.
  
 3) 3RD REQUEST,FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4) 3RD REQUEST, 4) THE PERMIT APPLICATION, DESSCRIPTION
 OF WORK, INDICATES ONLY A INTERIOR DEMOLITION PERMIT
 WHERE AS PLANS INDICATE ADDITIONAL SCOPE OF WORK.
 PLEASE CORRECT THE PERMIT APPLICATION TO INCLUDE THE
 LARGER SCOPE OF WORK.106.1.2*OR IF A TRUE INTERIOR DEMO
 INDICATE SUCH ON PLAN.
  
 5) COMPLIED.
  
 6A) COMPLIED.
  
 6B) COMPLIED.
  
 6C) COMPLIED.
  
 6D)ERROR, THE BUILDING TYPEOF CONSTRUCTION, AS
 DEFINED IN CHAPTER 3. THIS BUILDING IS A TYPE II-A TO
 BE SPRINKLERED. THIS IS A 4 STORY BUILDING,WITH THE 1
 STORY INCREASE FROM A FULLY SPRINKLED BUILDING!
 THE OWNERS ARE TAKING THE AREA INCREASES GIVEN TO THEM
 BY THE SPINKLERS.
 THIS MEANS THIS SPACE WILL REQUIRE FIRE SPRINKLERS AND
 FIRE SPRINKLER PLANS.
  
 6ECOMPLIED.
  
 6F) YES A FIRE SPRINKLER WILL BE REQUIRED.
  
 6G-H) COMPLIED.
  
 7)COMPLIED.
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-06 Cont ID  
Sent By jwitmer Date 2007-03-06 Time 16:47 Rev Time 2.22
Received By jwitmer Date 2007-03-06 Time 16:46 Sent To  
Notes
2007-03-06 16:50:17BUILDING PLAN REVIEW
 PERMIT: 07010901
 ADD: 223 CLEMATIS ST
 CONT: MYRICK ENTERPRISES
 TEL: (954)445-2451
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED.
  
 3) 2ND REQUEST,FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4) 2ND REQUEST, 4) THE PERMIT APPLICATION, DESSCRIPTION
 OF WORK, INDICATES ONLY A INTERIOR DEMOLITION PERMIT
 WHERE AS PLANS INDICATE ADDITIONAL SCOPE OF WORK.
 PLEASE CORRECT THE PERMIT APPLICATION TO INCLUDE THE
 LARGER SCOPE OF WORK.106.1.2*.
  
 5) COMPLIED.
  
 6A) COMPLIED.
  
 6B) COMPLIED.
  
 6C) COMPLIED.
  
 6D) TYPE OF CONSTRUCTION, AS DEFINED IN CHAPTER 3. THIS
 BUILDING IS A TYPE II-B TO BE SPRINKLERED.
 THE OWNERS ARE TAKING THE AREA INCREASES GIVEN TO THEM
 BY THE SPINKLERS.
 THIS MEANS THIS SPACE WILL REQUIRE FIRE SPRINKLERS AND
 FIRE SPRINKLER PLANS.
  
 6ECOMPLIED.
  
 6F) YES A FIRE SPRINKLER WILL BE REQUIRED.
  
 6G-H) COMPLIED.
  
 7) 2ND REQUEST, THE EXITING CONFIGURATION OF THE REAR
 CORRIDOR WILL BE RECONFIGURED TO SOME EXTENT WITH THE
 MODIFICATIONS THAT OF THE REAR EXIT REQUIREMENTS FOR
 THE
 WEST SECOND STORY STAIRWELL ( A COMMON STAIRWELL
 SERVING 2 OR MORE TENANTS) AND VESTIBULE ON THE FIRST
 FLOOR THAT WILL TAKE PLACE. 2004 EXISTING BUILDING CODE
 CHAPTER 8 CHANGE IN OCCUPANCYSEE TABLE 812.4.1.
  
 IFTHERE ARE ANY QUESTIONS PLEASE CALL:
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By jwitmer Date 2007-01-22 Time 08:31 Rev Time 0.77
Received By mawillia Date 2007-01-22 Time 08:31 Sent To Z
Notes
2007-01-22 08:45:19BUILDING PLAN REVIEW
 PERMIT: 07010901
 ADD: 223 CLEMATIS ST
 CONT: MYRICK ENTERPRISES
 TEL: (954)445-2451
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) VALUE FOR THE SCOPE OF WORK IS LOW , PLEASE PROVIDE
 ACURATE VALUE OF
 DESCRIBED WORK OR CITY WILL CALCULATE VALUE OF WORK
 FROM MARSHAL AND SWIFT OR ICC
 VALUES. 108.3* WEST PALM ADMINISTRATIVE CODE.
  
 3 ) ONCE VALUES ARE INCREASED A NOC WILL BE REQUIRED:
 FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4) THE PERMIT APPLICATION, DESSCRIPTION OF WORK,
 INDICATES ONLY A INTERIOR DEMOLITION PERMI,
 WHERE AS PLANS INDICATE ADDITIONAL SCOPE OF WORK.
 PLEASE CORRECT SO BOTH WILL REFLECT THE TRUE NATURE OF
 THIS PERMIT.
 106.1.2*
  
 5)PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6)) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) LEVEL OF ALTERATIONS:
 D) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 E) THE DESIGN OCCUPANT LOAD, SEE 1004.
 F) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 H) NUMBER OF FLOORS
  
 7) THE EXITING CONFIGURATION OF THE REAR CORRIDOR DOES
 NOT REFLECT WHAT ACTUALLY OCCURS AT THE SITE.
 A NOTE OF CAUTION. THE WEST EXIT OF THE NEWLY EXPANDED
 MONKEY CLUB( IN FOR PERMIT AT THIS TIME) MAY
 CAUSE SOME RECONFIGURATION ON THE FIRST FLOOR TO MEET
 EGRESS REQUIREMENTS, THIS MAY AFFECT YOUR PROJECT.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2007-07-19 Cont ID  
Sent By dpalmer Date 2007-07-19 Time 14:04 Rev Time 0.00
Received By dpalmer Date 2007-07-19 Time 14:04 Sent To  
Notes
2007-07-19 14:08:07CONTRACTOR CAME IN AND ADJUSTED PERMIT APPLICATION FOR
 SCOPE OF WORK TO MATCH PLANS.
  
 ** PLANS SHOW ALL ELECTRICAL AS EXISTING AND NO NEW
 ELECTRICAL WORK IS BEING DONE.
 IF ANY DEMO WORK INCLUDES AREAS WHERE ELECTRICAL IS
 PRESENT, ELECTRICAL CONTRACTOR IS TO OBTAIN AN
 ELECTRICAL DEMO PERMIT TO SAFE OFF ELECTRICAL SYSTEMS.
 ** ALL OTHER ELECTRICAL IS EXISTING TO REMAIN. ANY NEW
 WORK SHALL BE PERMITTED WITH PLANS AND WILL BE REQUIRED
 TO MEET CURRENT NEC AND FBC.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-13 Cont ID  
Sent By dpalmer Date 2007-07-13 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2007-07-13 Time 17:42 Sent To  
Notes
2007-07-13 18:12:06** UNSAT **
  
 1) NOTE: PLANS ARE TOREMAIN IN *F* STATUS UNTIL
 CLARIFICATION IS OBTAINED FOR BELOW.
 PERMIT APPLICATION STILL INDICATES THIS SCOPE OF WORK
 IS FOR "INTERIOR DEMO ONLY" AND NOT TO DO ANY NEW
 INSTALLATION OF OTHER ITEMS WHICH ARE BEING SHOWN ON
 PLANS. THIS WAS STATED BY OTHER TRADE REVIEWERS AS
 WELL.
 PLEASE SEE THE PLANS INDICATE WORK WHICH IS NOT STATED
 ON PERMIT APPLICATION. IS THIS APPLICATION FOR INTERIOR
 DEMO WORK AS STATED OR IS OTHER WORK BEING DONE AS
 STATED ON PLANS? PLEASE KNOW IN EITHER CASE PLANS
 INDICATE ALL ELECTRICAL IS EXISTING AND WILL NOT BE
 TOUCHED, RELOCATED, REMOVED ETC.
 PLANS ALSO STILL INDICATES A * NEW EQUIPMENT* SCHEDULE
 AND LOCATIONS OF EQUIPMENT. IS THIS EQUIPMENT BEING FED
 FROM ALL EXISTING LOCATIONS WHICH ALREADY PROVIDE
 ELECTRICAL FOR ELECTRICAL EQUIPMENT?
 PLEASE SEE PLANS DO CONTAIN NOTES THAT *ALL* ELECTRICAL
 IS EXISTING INCLUDING LIGHTS, RECEPTACLES ETC.!!!
 PLEASE KNOW, THAT IF ANY ELECTRICAL WORK IS BEING DONE,
 PLANS AND PERMIT APPLICATION NEED TO BE REVISED.
 ELECTRICAL WORK FOR ANY REPLACEMENT, NEW INSTALLED OR
 CHANGED OUT ELECTRICAL WILL REQUIRE CURRETN CODE
 COMPLIANCE. AT THIS TIME, PERMIT APPLICATION IS FOR
 *INTERIOR DEMO* ONLY AS CLEARLY STATED ON PERMIT
 APPLICATION.
 THIS INFORMATION ABOVE NEEDS TO BE CLEARED UP BY THE
 CONTRACTOR AND/OR DESIGNER OF RECORD.IF NO ELECTRICAL
 WORK IS BEING AFFECTED OR DONE, THEN THE REVIEW STATUS
 WILL CHANGE TO AN *N* AND A PERMIT WILL BE REQUIRED FOR
 ANY ELECTRICAL DEMO WORK BEFORE COMMENCING BUILDING
 DEMO WORK AS STATED.
  
 ** PLEASE SEE PERMIT APPLICATION HAS ALWAYS STATED
 INTERIOR DEMO WORK ONLY.
  
 PLEASE CALL IF THERE IS ANY QUESTIONS OR INFORMATION
 WHICH CAN BE PROVIDED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT.
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-05 Cont ID  
Sent By dpalmer Date 2007-03-05 Time 15:27 Rev Time 0.00
Received By dpalmer Date 2007-03-05 Time 12:42 Sent To  
Notes
2007-03-05 15:30:12*** UNSAT ***
  
 1) NOTE: PLEASE KNOW AT THIS TIME THE MEANS OF EGRESS
 FOR THIS SPACE AND FOR OTHER TENANT BUILD OUTS ARE IN
 QUESTION. PLEASE KNOW THAT THERE WILL BE WORK UNDER
 SEPARATE WHICH MAY AFFECT THE EGRESS AND EXIT OF THIS
 SPACE.
  
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-21 Cont ID  
Sent By dpalmer Date 2007-01-21 Time 13:25 Rev Time 0.00
Received By dpalmer Date 2007-01-21 Time 13:25 Sent To  
Notes
2007-01-21 13:26:12** UNSAT **
  
 1) NOTE: PLEASE SEE THE VALUE FOR THE SCOPE OF WORK
 BEING DICTATED ON PLANS IS EXTREMELY LOW FOR SCOPE OF
 WORK SHOWN.
 PLEASE SEE FBC ADMIN SECTION 108.3
 PLEASE KNOW IF ONE IS NOT ADJUSTED FOR SCOPE AS SHOWN
 ON PLANS, ONE WILL BE ASSESSED USING THE FBC AND
 METHODS ADOPTED INTO THE 2004 FBC AND THE FBC
 ADMINISTRATIVE SECTIONS TO THE FBC.
  
 2) NOTE: PLEASE SEE THE CODES RELEVANT FOR SCOPE OF
 WORK SHALL BE STATED ON PLANS.
 2006 REVISIONS TO THE 2004 FBC, 2003 NFPA-101, 2002
 NFPA-72 AND THE 2005 NFPA-70.
 PLEASE SEE PLANS SHALL STATE THE OCCUPANCY, LOAD ETC,
 WHICH WILL BE IN BUILDING REVIEW NOTES.
  
 3) NOTE: PLEASE SEE PLANS SHALL BE SIGNED, DATED AND
 SEALED BY THE ARCHITECT OF RECORD AS LISTED ON PLANS.
 FAC 61G1-16, FS 481.221
 FBC ADMIN SECTION 106.1
  
 4) NOTE: PLEASE INDICATE NEW OR EXISTING REMAIN
 EMERGENCY LIGHT FIXTURES AND EXIT LIGHTING AS REQUIRED
 PER NFPA-101 7.8 AND 7.9.
 PLEASE ALSO SEE 700.12E AS CIRCUITING SHALL MEET THIS
 SECTION, IF IT DOES NOT ALREADY.
 **PLEASE BE SURE TO SEE POSSIBLE FIRE REVIEW COMMENTS.
  
 5) NOTE: PLEASE SEE PLANS MENTIONS REPLACING CEILING
 GRID, PLEASE PROVIDE LIGHTING LAYOUT FOR EXISTING OR
 NEW FIXTURES FOR LOCATIONS. THIS CAN BE DONE AS
 REFLECTED CEILING PLANS IF ALL EXISTING. IF ANY OF
 THESE FIXTURES ARE GOING TO BE NEW, THEN PLEASE PROVIDE
 ON ELECTRICAL SHEETS ALONG WITH NOTE #4 ABOVE.
  
  
 ** PLEASE KNOW AS THE COMPLETE SCOPE OF WORK IS NOT
 EXACTLY CLEAR AT THIS TIME, THERE MAY BE COMMENTS ON
 THE NEXT REVIEW DEPENDING ON THE PLANS AND INFORMATION
 PROVIDED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-24 Cont ID  
Sent By mawillia Date 2007-07-24 Time 17:43 Rev Time 0.00
Received By mawillia Date 2007-07-24 Time 17:17 Sent To  
Notes
2007-07-24 17:37:39*****PROVISO*****
  
 1.ON SHEET NO. T-1, INTERIOR FINISH CLASSIFICATION
 SHALL BE WORDED AS CLASS IN LIEU OF TYPE.FOR EXAMPLE,
 EXIT -CLASS B,NOT EXIT - TYPE B
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By mawillia Date 2007-02-06 Time 14:56 Rev Time 0.00
Received By mawillia Date 2007-02-06 Time 14:56 Sent To Z
Notes
2007-02-06 15:42:13*****DENIED*****
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE.
  
 5.INDICATE THE LOCATION OF FIRE EXTINGUISHERS, EXIT
 LIGHTS, EMERGENCY LIGHTS, FIRE SPRINKLERS, FIRE ALARM
 DEVICES, ETC.HOW WILL THEY BE AFFECTED BY THE SCOPE
 OF WORK?
  
 6.WHAT IS THE INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS SND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN OTHER AREAS?
  
 7.WHAT IS THE OCCUPANT LOAD FOR THIS STRUCTURE AS
 DETERMINED PER THE OCCUPANT LOAD FACTORS OF NFPA 101,
 TABLE 7.3.1.2 THAT ARE CHARACTERISTIC OF THE USE OF THE
 SPACE OR SHALL BE DETERMINED AS THE MAXIMUM PROBABLE
 POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER
 IS GREATER.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED ON THE PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-07-12 Time 10:03 Rev Time 0.00
Received By adarroug Date 2007-07-12 Time 10:03 Sent To  
Notes
2007-07-27 08:19:427/27/07--PLANS TAKEN FROM "BOB"#15 AND ROUTED TO
 "LMARTINEZ" DESK
2007-07-13 10:36:12TO "BOB"#15
2007-07-12 10:04:17WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-02 Cont ID  
Sent By adarroug Date 2007-03-02 Time 16:22 Rev Time 0.00
Received By adarroug Date 2007-03-02 Time 16:22 Sent To  
Notes
2007-03-05 08:44:37TO "BOB"#3
2007-03-02 16:22:24WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-13 Cont ID  
Sent By adarroug Date 2007-02-09 Time 14:52 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 14:35 Sent To  
Notes
2007-01-20 14:38:17TO "BOB"#6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-01-22 Cont ID  
Sent By tgordon Date 2007-01-22 Time 11:56 Rev Time 0.15
Received By tgordon Date 2007-01-22 Time 11:56 Sent To  
Notes
2007-01-22 11:57:38NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status N Date 2007-07-27 Cont ID  
Sent By jleech Date 2007-07-27 Time 10:09 Rev Time 0.00
Received By jleech Date 2007-07-27 Time 10:09 Sent To  
Notes
2007-07-27 10:24:09NO PLUMBING PLANS SUBMITED.
 PLUMBING CONTRACTOR TO SUBMIT ENGINEERED SEALED PLANS,
 REVIEWED BY THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION DIVISION OF HOTEL AND RESTAURANTS AND
 APPROVED BY THE UTILITY DEPARTMENT FOR COMPLIANCE TO
 WASTE ORDINANCE # 3434. CONTACT PERSON IS RODNEY COMPO
 PHONE # 822-2272 FOR GREASE TRAP APPROVAL.

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-10 Cont ID  
Sent By jleech Date 2007-03-10 Time 06:26 Rev Time 0.00
Received By jleech Date 2007-03-10 Time 06:26 Sent To  
Notes
2007-03-10 06:28:36PLUMBING DEMO OK.
 NOT ENOUGH INFORMATION FOR A PLUMBING PLAN REVIEW.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-29 Cont ID  
Sent By jleech Date 2007-01-29 Time 08:56 Rev Time 0.00
Received By jleech Date 2007-01-29 Time 08:38 Sent To  
Notes
2007-01-29 09:14:31DENIED;
 1.PLANS NOT SIGNED OR SEALED.
 2. NOT ENOUGH INFORMATION TO DO A PLAN REVIEW;
 A) IS THIS A NEW BUSINESS?
 B) IS THIS A NEW RESTAURANT?
 C) SIZE (SQ. FT.)
 D) NUMBER OF OCCUPANTS
 3.SINK TO BE REMOVED;
 A) IS SINK A REQUIRED HAND SINK
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status N Date 2007-07-19 Cont ID  
Sent By choops Date 2007-07-19 Time 17:46 Rev Time 0.00
Received By choops Date 2007-07-19 Time 17:46 Sent To  
Notes
2007-07-19 17:47:16*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.

Review Stop Z ZONING
Rev No 1 Status N Date 2007-02-09 Cont ID  
Sent By mflis Date 2007-02-09 Time 10:25 Rev Time 0.00
Received By mflis Date 2007-02-09 Time 10:25 Sent To  
Notes
2007-02-09 10:26:03ZONING REVIEW: NOT REQUIRED
  
 - PROJECT SCOPE INCLUDES ONLY INTERNIOR DEMOLITION
 - NO EXTERIOR MODIFICATIONS NOTED ON PLANS
  
 MATT FLIS 822-1445