Plan Review Details - Permit 07010880
Plan Review Stops For Permit 07010880
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-03-14 Cont ID  
Sent By mjacobs Date 2007-03-14 Time 06:37 Rev Time 0.00
Received By mjacobs Date 2007-03-14 Time 05:58 Sent To PC
Notes
2007-03-14 06:24:39BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST STRENGTH
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-12 Cont ID  
Sent By mjacobs Date 2007-02-12 Time 07:43 Rev Time 0.00
Received By mjacobs Date 2007-02-12 Time 06:38 Sent To PC
Notes
2007-02-12 07:22:59BUILDING PLAN REVIEW
 PERMIT:07010880
 ADD:7240WINDING BAY LN
 CONT: AAACUSTOM POOLS. INC.
 TEL: (561)753-3366
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE. SEE SHEET #3
  
 3)INDICATE THE SQUARE FOOTAGE OF THE DECK AREA ON THE
 DRAWINGS
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-04-04 Cont ID  
Sent By btrobaug Date 2007-04-04 Time 08:55 Rev Time 0.50
Received By btrobaug Date 2007-04-04 Time 07:42 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-27 Cont ID  
Sent By btrobaug Date 2007-03-27 Time 13:10 Rev Time 0.33
Received By btrobaug Date 2007-03-27 Time 12:39 Sent To PC
Notes
2007-03-27 13:11:25 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 SAME COMMENT AS LAST REVIEW. THERE IS AN ELECTRICAL
 "PANEL" SHOWN ON THE ELECTRICAL SCHEMATIC. THIS WOULD
 APPEAR TO BE A "POOL PANEL". IF IT IS EXISTING PLEASE
 INDICATE ON THE PLAN. IF IT IS BEING INSTALLED AS PART
 OF THIS PERMIT, SUBMIT THE FOLLOWING DETAILS ON THE
 PLAN:
  
 MAKE THE FOLLOWING CORRECTIONS FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 PLEASE SUBMIT DETAILS FOR THE PANEL SHOWN ON THE
 SCHEMATIC, FEEDER AND CONDUIT SIZE AND TYPE, PANEL
 RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-08 Cont ID  
Sent By btrobaug Date 2007-03-08 Time 06:54 Rev Time 0.50
Received By btrobaug Date 2007-03-08 Time 06:29 Sent To P
Notes
2007-03-08 06:49:44 
 DENIED/INCOMPLETE INFORMATION
  
 SAME COMMENT AS LAST REVIEW. THERE IS AN ELECTRICAL
 "PANEL" SHOWN ON THE ELECTRICAL SCHEMATIC. THIS WOULD
 APPEAR TO BE A "POOL PANEL". IF IT IS EXISTING PLEASE
 INDICATE ON THE PLAN. IF IT IS BEING INSTALLED AS PART
 OF THIS PERMIT, SUBMIT THE FOLLOWING DETAILS ON THE
 PLAN:
  
 MAKE THE FOLLOWING CORRECTIONS FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 PLEASE SUBMIT DETAILS FOR THE PANEL SHOWN ON THE
 SCHEMATIC, FEEDER AND CONDUIT SIZE AND TYPE, PANEL
 RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-01 Cont ID  
Sent By btrobaug Date 2007-02-01 Time 08:01 Rev Time 0.33
Received By btrobaug Date 2007-02-01 Time 07:55 Sent To P
Notes
2007-02-01 08:00:55 
 DENIED/INCOMPLETE INFORMATION
  
 MAKE THE FOLLOWING CORRECTIONS FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDUIT SIZE AND
 TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-02-05 Cont ID  
Sent By mperson Date 2007-02-05 Time 16:27 Rev Time 0.00
Received By mperson Date 2007-02-05 Time 16:27 Sent To B
Notes
2007-02-05 16:28:40CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-28 Cont ID  
Sent By spalmer Date 2007-03-28 Time 17:46 Rev Time 0.00
Received By spalmer Date 2007-03-28 Time 17:46 Sent To E
Notes
2007-03-28 17:47:08TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-20 Cont ID  
Sent By adarroug Date 2007-03-20 Time 10:16 Rev Time 0.00
Received By adarroug Date 2007-03-20 Time 10:16 Sent To E
Notes
2007-03-20 10:17:31TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-01 Cont ID  
Sent By adarroug Date 2007-03-01 Time 16:05 Rev Time 0.00
Received By adarroug Date 2007-03-01 Time 16:04 Sent To E
Notes
2007-03-01 16:05:20TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 11:52 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 11:52 Sent To E
Notes
2007-01-31 11:53:04TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-02-12 Time   Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 13:06 Sent To  
Notes
2007-01-20 13:07:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-03-13 Cont ID  
Sent By mperson Date 2007-03-13 Time 10:54 Rev Time 0.33
Received By mperson Date 2007-03-13 Time 10:53 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-05 Cont ID  
Sent By mperson Date 2007-02-05 Time 16:00 Rev Time 0.33
Received By mperson Date 2007-02-05 Time 16:00 Sent To G
Notes
2007-02-05 16:26:16DENIED
 REFERENCE: FBC-2004 SECTIONS 424.2 AND R4101, SWIMMING
 POOLS;CITY OF WEST PALM BEACH AMENDMENTS TO FBC-2004
 CHAPTER 1, ADMINISTRATION
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1)SHEET 3 OF 3 PLEASE DELETE THE 2001 YEAR REFERENCE
 AND ADD 2004 YEAR REFERENCE IN ITS PLACE, PER FBC 2004
 CHAPTER 1, SECTION 106.1.1 INFORMATION ON ONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2)FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPER- ATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.
 NOTE: PLEASE PROVIDE MANUFACTURER CUT SHEET OR INDICATE
 THE MAKE AND MODEL NUMBER ON THE RESUBMITTED PRINTS.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2007-01-27 Cont ID  
Sent By mmclean Date 2007-01-27 Time 09:22 Rev Time 0.00
Received By mmclean Date 2007-01-27 Time 09:24 Sent To I
Notes
2007-01-29 09:23:36PROVISO: SEC 94-304(2)(B) - EVERY SWIMMING POOL SHALL
 BE ENCLOSED BY A FENCE OR SIMILAR STRUCTURE WHICH IS
 INSTALLED TO OBSTRUCT ACCESS BY PERSONS OTHER THAN THE
 OWNERS OR OCCUPANTS OF THE RESIDENCE WITHIIN WHICH A
 SWIMMING POOL IS LOCATED.BARRIERS OR FENCES SHALL BE
 AT LEAST FOUR FEET IN HEIGHT ABOVE GRADE.