Plan Review Details - Permit 07010874
Plan Review Stops For Permit 07010874
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-17 Cont ID  
Sent By rmcdouga Date 2007-01-17 Time 17:29 Rev Time 0.00
Received By rmcdouga Date 2007-01-17 Time 17:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-16 Cont ID  
Sent By rmcdouga Date 2007-01-16 Time 17:20 Rev Time 0.00
Received By rmcdouga Date 2007-01-16 Time 17:10 Sent To  
Notes
2007-01-16 17:19:56DENIED BY BUILDING
  
 1) SPECIFY THE APPROVED ASSEMBLY THAT WILL BE
 INSTALLED. CIRCLE THE FASTENING OPTION AND MAXIMUM
 DESIGN PRESSURE FOR THE ASSEMBLY. SEE PAGES 9-31 OF THE
 NOA.
  
 2) SUBMIT RAS 117 CALCULATIONS FOR THE PERIMETER AND
 CORNER AREAS IF THE MAXIMUM DESIGN PRESSURE SELECTED IS
 NOT ADEQUATE FOR THESE AREAS. SEE LIMITATION NUMBER 7
 ON PAGE 32 OF THE NOA. FOR THIS STRUCTURE THE PERIMETER
 AREA PRESSURE IS -59.2 PSF AND THE CORNER AREAS
 PRESSURE IS -89.0 PSF.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-01-16 Cont ID  
Sent By ssherman Date 2007-01-16 Time 15:19 Rev Time 0.00
Received By ssherman Date 2007-01-16 Time 15:18 Sent To  
Notes
2007-01-16 15:19:05HISTORICAL APPROVAL PER GALINA JUDGE