Plan Review Details - Permit 07010866
Plan Review Stops For Permit 07010866
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-07-21 Cont ID  
Sent By lmartine Date 2008-07-21 Time 14:12 Rev Time 0.00
Received By lmartine Date 2008-07-21 Time 14:12 Sent To  
Notes
2008-07-21 14:13:24ROOF TOP ANCHORING DETAILS REVISION APPROVEDLM

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-05-05 Cont ID  
Sent By lmartine Date 2008-05-05 Time 14:01 Rev Time 0.00
Received By lmartine Date 2008-05-05 Time 14:01 Sent To  
Notes
2008-05-05 14:04:21REVISION APPROVED, U#S AND R#S CORRECTEDLM

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-05-02 Cont ID  
Sent By lmartine Date 2008-05-02 Time 17:31 Rev Time 0.00
Received By lmartine Date 2008-05-02 Time 16:53 Sent To  
Notes
2008-05-02 17:31:03REVISION COMMENTS
  
  
 THE EFFICIENCY #S ON THE NEW ENERGY CALCULATIONSFOR
 WALLS AND ROOF ARE HIGHER THAN THE APPROVED PLANS,
 PLEASE JUSTIFY THE DISCREPANCIES.
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-19 Cont ID  
Sent By lmartine Date 2008-03-19 Time 12:02 Rev Time 0.00
Received By lmartine Date 2008-03-19 Time 12:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-08 Cont ID  
Sent By lmartine Date 2008-01-08 Time 11:38 Rev Time 0.00
Received By lmartine Date 2008-01-08 Time 11:38 Sent To  
Notes
2008-01-08 11:39:39REVISION #4 ,OK LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-13 Cont ID  
Sent By lmartine Date 2007-09-13 Time 17:04 Rev Time 0.00
Received By lmartine Date 2007-09-13 Time 17:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-24 Cont ID  
Sent By jjohnsto Date 2007-08-24 Time 09:26 Rev Time 3.00
Received By jjohnsto Date 2007-08-24 Time 09:26 Sent To  
Notes
2007-08-24 14:21:31BUILDING PLAN REVIEW
 PERMIT:07010866
 ADD:3231S. DIXIE HIGHWAY
 CONT:WAYJOHN INC.
 TEL: (561)683-8444
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 2 NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 RESPONCE TO CORRECTIONS SUBMITTED
  
  
 (1) WHEN RE-SUBMITTING PLANS FOR CORRECTIONS MADE,
 PLEASE PROCESSASFOLLOWS:
  (A)INDICATE THE CORRECTIONS BY CLOUDING THE
 CORRECTED AREAS
  (B)REMOVE THE OLD SHEET AND INSERT THE NEW CORRECTED
 SHEET INTO THE PLAN.
  (C) SUBMIT THE OLD SHEETS SEPARATE FROM THE CORRECTED
 PLAN FOR THE PLAN REVIEWER?S REFERENCE
  
 (2) F.S.713.13 (2)THE NOTICE OF COMMENCEMENT
 RECORDED ON 12/21/06EFFECTIVE FOR 90 DAYS FROM
 RECORDING
 HAS EXPIRED.PLEASE RESUBMIT A NEW RECORDED NOC
  
 (3) FBC EXISTING:304.1SHEETT. 1.0PLAN
 SPECIFIES LEVELTHIS IS A LEVEL2 ALTERATION
  
 (4) FBC1604.5SHEETA.3.0CHANGEWIND IMPORTANCE
 FACTOR TO CATEGORY II,FACTORI
  
 (8) FBC1503.4SHEETA-2.0HOW WILL STORM OR RAIN
 WATER BE REMOVED FROM AREA BELOW CANOPY IN
  THE ABSENCE OF PROTECTION?FURNISHROOF DRAIN AND
 2ND DRAIN OR OVERFLOW SCUPPER FOR DRAINAGE.
  
 (9) 9-B -72SHEET A- 4.0STUD PLATE CONNECTION
 SPECIFYUSPTIE DOWN FOR UP-LIFT RESTRAINT
  FBC 1703PROVIDE STATE OF FLORIDA PRODUCT APPROVALS
 FOR ALL STRUCTURAL CONNECTIONS.
  REQUIRES PRODUCT APPROVAL
  FLORIDA APPROVAL RATING
 PRODUCT APPROVAL FOR BACK-UP
  HAVE DESIGNER REVIEW AND ACKNOWLEDGE WITH SHOP STAMPS
 THEIR ACCEPTANCE.
  
 (10) SHEET A-4.1SPECIFIES PARAPET WALL SHEATHING ??
 SHEET A-4.0STATES 5/8?FURNISH CORRECT INFORMATION
  
 (11) PLEASE PLACE THEADA -1 SHEET BEHIND SHEET A-6.0.
 THIS WILL HELP THE CONTRACTOR AND FIELD INSPECTOR
 READILYIDENTIFY THE REQUIRED MEASUREMENTS FOR
 PLACEMENT OF BATHROOM ACCESSORIES.
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-07 Cont ID  
Sent By jwitmer Date 2007-03-07 Time 16:31 Rev Time 1.33
Received By jwitmer Date 2007-03-07 Time 16:31 Sent To  
Notes
2007-03-07 16:54:23BUILDING PLAN REVIEW
 PERMIT: 07010866
 ADD: 3231 S DIXIE HWY
 CONT: DARRELL SHAFRANSKI CONSTRUCTION
 TEL: (772)569-5862
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)SHEET C-1.0 ACCESSIBLE PARKING:
 PLEASE PROVIDE SIGNAGE, 11-4.6.4 SIGNAGE.
 EACH ACCESSIBLE PARKING SPACE MUST BE PROMINENTLY
 OUTLINED WITH BLUE PAINT, AND MUST BE REPAINTED AS
 NECESSARY, TO BE CLEARLY DISTINGUISHABLE AS A PARKING
 SPACE DESIGNATED FOR PERSONS WHO HAVE DISABILITIES AND
 MUST BE POSTED WITH A PERMANENT ABOVE-GRADE SIGN
 BEARING THE INTERNATIONAL SYMBOL OF ACCESSIBILITY,
 MEETING THE REQUIREMENTS OF COLOR AND DESIGN APPROVED
 BY THE DEPARTMENT OF TRANSPORTATION, OF SECTION
 11-4.30.7 AND THE CAPTION ?PARKING BY DISABLED PERMIT
 ONLY.? SUCH SIGN ERECTED AFTER OCTOBER 1, 1996, MUST
 INDICATE THE PENALTY FOR ILLEGAL USE OF THE SPACE.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 WHAT LEVEL OF ALTERATION WILL THIS BE , 2004 EXISTING
 BUILDING CODE?
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THEOCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 4) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EFIS WALL SYSTEMS
 B) TRUSS ANCHORS
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 8) SHEET A-4.1 INDICATES THE FRAMING DETAIL FOR THE
 NEWLY DESIGNEDTOWER, SHEET A-4.1 INDICATES THE NEW
 TOWER HAS THE CENTER OPEN AND THE INSIDE WALLS HAVE A
 MODIFIED BITUMEN ROOFING MEMBRANE, THERE APPEARS TO BE
 NO ROOF DRAIN NOR OVERFLOW SCUPPERS TO ALLOW THE RAIN
 WATER OUT OF THIS BOX LOOKING TOWER. HOW WILL RAIN
 WATER
 BE DRAINED?
  
 SHEET A-3.0 INDICATES A STRIPED ILLUMINATED TOWER BY
 KFC/ VENDOR, IS THIS TO BE UNDER SEPERATE PERMIT? IS
 THIS TO KEEP OUT RAIN OR IS THIS ADVERTISEMENT
 PURPOSES?
 WILL THERE BE ENGINEERING SHOWING COMPLIANCE WITH 140
 MPH WIND LOADS?
  
 9) PLANS SHOW AWNINGS BUT NO INFORMATION HAS BEEN
 PROVIDED AS TO THE TYPE OF AWNING IF FIXED IN PLACE, IF
 CLOTH ETC, TO BE UNDER A SEPERATE PERMIT?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
2007-03-07 16:32:34 

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2008-07-16 Cont ID  
Sent By dpalmer Date 2008-07-16 Time 10:53 Rev Time 0.00
Received By dpalmer Date 2008-07-16 Time 10:53 Sent To PC
Notes
2008-07-16 10:56:49LETTER DELETING TWO GFI IN BATHROOMS

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2008-04-23 Cont ID  
Sent By dpalmer Date 2008-04-23 Time 13:31 Rev Time 0.00
Received By dpalmer Date 2008-04-23 Time 13:31 Sent To  
Notes
2008-04-23 13:32:20ENERGY CALCULATIONS REVIEWED FOR ELECTRICAL CODE
 COMPLIANCE ONLY

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2008-04-04 Cont ID  
Sent By dpalmer Date 2008-04-04 Time 14:21 Rev Time 0.00
Received By dpalmer Date 2008-04-04 Time 14:21 Sent To M
Notes
2008-04-04 14:22:03** DENIED REVISIONS FOR THE 6TH REVIEW **
  
 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS FIVE REVIEWS
 WHICH *STILL* REMAIN THE SAME. PLEASE SEE 13-415.2,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
 THE CALCULATIONS NOW SUBMITTED ARE METHOD *C* WHEN ALL
 PREVIOUS SUBMITTED CALCULATIONS WERE *A*.
 PLEASE SEE THE NEW *C* CALCULATIONS DO NOT CORRELATE
 WITH PLANS. PLEASE SEE NOT ALL INTERIOR FIXTURES ON
 PLANS FOR WATTAGE AS SHOWN AND COUNT CORRELATES WITH
 FIXTURE LEGEND AND SOME LIGHTING ON PLANS IS NOT ON THE
 INPUT DATA REPORT AT ALL.
 FOR EXAMPLE:
 SEE SHEET A-6.1 SHOWS LIGHTING NOT SHOWN ON ELECTRICAL
 PLANS FOR BATHROOMS. SEE THE ELECTRICAL PLANS FOR THESE
 SAME LOCATIONS AS FIXTURE LEGEND DOES NOT INCLUDE
 THESE. SEE THE FIXTURES ON A SHEETS AND E-SHEETS ARE
 SHOWN AS TWO COMPLETELY DIFFERENT FIXTURES.
 THESE ARE SHOWN AS COMPACT FLUORESCENT ON THE IDR.IN
 FACT ALL FIXTURES ARE SHOWN AS COMPACT FLUORESCENT.
 SEE TRACK LIGHTING WHICH IS ON PLANS IS STILL NOT
 INCLUDED.
 ** THERE IS SOME SORT OF NOTE WHICH WAS CUT IN HALF BY
 PRINTING WHICH NOTES THESE AS EXISTING HOWEVER THIS IS
 NOT THE CASE.
 PLEASE SEE THE *A* FIXTURES ANDVERIFY THESE ARE SHOWN
 AS DUAL 26W TROFFERS. SEE LITHONIA LIGHTING AS THESE
 ARE NOT LISTED W/ COMPANY. THESE ARE SHOWN ON THE IDR
 AS COMPACT FLUORESCENT ALSO.
 PLEASE SEE THE FIXTURES ON PLANS FOR 2-PERSON BOOTH
 LOCATIONS ARE NOT ON FIXTURE LEGEND NOR ARE THEY ON
 CALCULATIONS.
  
 2) NOTE: THIS REVIEWER HAS CALLED AND SPOKEN TO
 ENGINEER?S OFFICE SEVERAL TIMES AND YET PLANS AND
 CALCULATIONS ARE STILL NOT BEING CORRECTED.A MEETING
 WITH THE OWNER AND CONTRACTOR BEING PRESENT IS BEING
 REQUESTED BEFORE NEW PLANS OR CALCULATIONS ARE
 SUBMITTED.
 PLANS ARE ONCE AGAIN BEING RETAINED AND MAY BE
 SUBMITTED TO THE FLORIDA BOARD OF ENGINEERS.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2008-03-21 Cont ID  
Sent By dpalmer Date 2008-03-21 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2008-03-21 Time 11:44 Sent To B
Notes
2008-03-21 11:44:12** DENIEDREVISIONS FOR THE FIFTH REVIEW **
  
 *** PLEASE SEE THE SAME COMMENTS AS PREVIOUSLY
 MENTIONED STILL ARE IN NEED OF ADDRESSING.
  
  
 1) NOTE:PLEASE SEE FBC 13-400.3.A, 13-415.2,
 13-415.2.ABC.1.1, .1.2, .1.3 AS ALL LIGHTING ON PLANS
 NEEDS TO CORRELATE WITH THE INPUT DATA REPORT AND
 ENERGY CALCULATIONS.
 PLEASE SEE FIXTURES ON PLANS SUCH AS EXTERIOR LIGHTS
 ARE NEW ON-SITE AND ARE NOT EXISTING AS SHOWN ON PLANS.
 IN EITHER CASE IF USING METHOD *A*, ALL KNOWN IS
 REQUIRED. HOW CAN THE EXTERIOR FIXTURES SHOWN ON THE
 IDR BE 12W FIXTURES? THE WATTAGE FOR ALL LIGHTS IS
 BASED ON FIXTURE WATTAGE, NOT BULBS. THE EXTERIOR
 FIXTURES ARE NOT 12W FIXTURES.
 PLEASE SEE THE INTERIOR LIGHTS ALSO DO NOT MATCH. THERE
 ARE SEVERAL FIXTURES ON PLANS WHICH ARE NOT IN THE
 IDR.
 PLEASE COMPLETE THE FIXTURES LEGEND FOR ALL FIXTURES AS
 THIS LOCATION HAS ALL NEW INSTALLED.THIS SHOULD
 INCLUDE TRACK FIXTURES, OUTSIDE ETC.
 ** CALCULATIONS ARE REQUIRED TO BE SIGNED BY THE
 PREPARER AND ALSO SIGNED BY THE OWNER AGENT. PLEASE DO
 NOT TYPE/PRINT THE PREPARERS NAME AND HAVE THE OWNER
 AGENT SPACE SIGNED BY PREPARER.
 FBC 13-103.1.1.1
  
 2) NOTE: PLEASE SEE NEW SHEETS E-2 ARE MISSING TITLE
 BLOCKS FOR FIRM.
 FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE THE BUILDING COMPONENTS ON PLANS
 SHALL ALSO MATCH THE PLANS FOR COMPLIANCE IN METHOD *A*
 CALCULATIONS.
 PLEASE KNOW ITEMS SUCH AS INSULATION ETC DO NOT MATCH
 THE IDR. THIS WILL PART OF THE BUILDING REVIEW
 COMMENTS.
  
 4) NOTE: THIS REVIEW CALLED ENGINEERING OFFICE AND
 ENGINEER OF RECORD AND WENT OVER COMMENTS ONCE AGAIN.
  
 5) NOTE: PLEASE SEE THE PAGES BEING REVISED ARE $10 PER
 PAGE AND CALCULATIONS COUNT AS ONE PAGE ALSO.
 FEE WILL BE DUE WHEN RESUBMITTING NEW PLANS.
  
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-03-14 Cont ID  
Sent By dpalmer Date 2008-03-14 Time 12:33 Rev Time 0.00
Received By dpalmer Date 2008-03-14 Time 12:33 Sent To  
Notes
2008-03-14 12:33:16** DENIEDREVIEW **
  
 ** PLEASE SEE THE NOTES BELOW WHICH ARE FROMTHREE
 PREVIOUS REVIEWS WHICH STILL NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE FBC 13-415.2.ABC.1.1, .1.2 AND
 .1.3. PLEASE SEE THE LIGHTING WHICH IS SHOWN ON THE
 PLANS DOES NOT MATCH WITH THE LIGHTING SHOWN ON THE
 INPUT DATA REPORTS OR ENERGY CALCULATIONS.
 FOR EXAMPLE; THE IDR DOES NOT SHOW ANY OUTSIDE LIGHTS.
 HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY SHOW
 OUTSIDE LIGHTS.
 PLEASE SEE THE IDR SHOWS METAL BLDG, HOWEVER THE PLANS
 DOES NOT SHOW A METAL BUILDING. ETC.
 PLEASE SEE COMMENTS FROM BUILD REVIEWER AS ALL
 INSULATION COMPONENTS, ROOFING ETC NEEDS TO CORRELATE.
 THE INSULATION RATINGS ETC.
 13-415.2, 13-400.3.A.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-03-04 Cont ID  
Sent By dpalmer Date 2008-03-04 Time 14:49 Rev Time 0.00
Received By dpalmer Date 2008-03-04 Time 14:49 Sent To PC
Notes
2008-03-04 14:50:04** DENIEDREVIEW **
  
 ** PLEASE SEE MANY COMMENTS FROM THE PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE:PLEASE SEE VALUE WAS STILL NOT INCREASED FOR
 THE INCREASED SCOPE OF WORK. PLEASE SUBMIT COMPLETE
 CONTRACTS FOR SCOPE OF WORK WITH CORPORATE OR A VALUE
 WILL BE ASSESSED.
 FBC 108.3
 PLEASE SEE ATTACHED NOTES FROM PREVIOUS REVIEW.
  
 2) NOTE: PLEASE SEE THE SAME ENERGY CALCULATIONS OF
 METHOD *A* ARE BEING SUBMITTED. THESE ARE INCOMPLETE AS
 NO INPUT DATA REPORT WAS SUBMITTED.
 PLEASE ALSO KNOW THAT USING METHOD *A* REQUIRES
 BUILDING COMPLIANCE FOR ALL COMPONENTS INCLUDING A/C.
 HOWEVER THESE ARE STILL NOT COMPLETE AND NOT ALL
 COMPONENTS ON PLANS ARE SHOWN TO VERIFY.
 PLEASE SEE THAT LIGHTING PERFORMANCE CALCULATIONS STILL
 NEED TO MEET 13-415.2, 13-415.2.ABC.1.1 AND
 13-415.2.ABC.1.3.
 13-400.3.A, 13-400.3.B, 13-400.3.C, 13-415.1.A,
 13-415.1.B, 13-415.1.C ETC
  
 3) NOTE: PLEASE SEE THE NEW ELECTRICAL SHEETS SUBMITTED
 ARE NOT SEALED WITH RAISED SEAL AS REQUIRED PER FS
 471.025 AND FAC 61G15-23.002
  
 4) NOTE: PLEASE SEE COMMENTS FROM MECHANICAL WITH
 RESPECT TO ENERGY CALCULATIONS.
  
 5) NOTE: PLEASE SEE NOTES STATED ON PREVIOUS REVIEW.
 PLEASE REMOVED ALL OLD/VOIDED SHEETS AND BE SURE SETS
 ONLY CONTAIN NEW SHEETS IN COMPLETE SETS FOR REVIEW AND
 STAMPING.
 AS STATED ON PREVIOUS REVIEW PLEASE DO NOT ATTACH
 SUPPORTING DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS.
  
 6) NOTE: PLEASE KNOW AS MANY ITEMS ARE BEING REPEATED,
 ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE.
  
  
 *** AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR
 REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-01-30 Cont ID  
Sent By dpalmer Date 2008-01-30 Time 17:26 Rev Time 0.00
Received By dpalmer Date 2008-01-30 Time 17:26 Sent To  
Notes
2008-01-30 17:26:34** DENIED REVIEW **
  
 *** PLEASE SEE MOST COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING AND SEVERAL NEW COMMENTS
 BASED ON SUBSTANTIAL AMOUNT OF CHANGES NOW MADE WHICH
 WERE NOT ON PREVIOUS PLANS SUBMITTED.
  
 ** DENIED REVISION **
  
  
 1) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK AT SITE IS TO BE REVISED.
 THE REVISED VALUE HAS BEEN INCREASED TO $119,000
 HOWEVER SCOPE OF WORK AT SITE HAS NOW INCREASED ONCE
 AGAIN ON PLANS WHICH EXCEED PREVIOUS PLANS SCOPE OF
 WORK.
 PLEASE SUBMIT SIGNED CONTRACTS FOR WORK DONE AT
 LOCATION.
 PLEASE SEE FBC 108.3 AS THE VALUE IS TO INCLUDE ALL
 LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC.
  
 2) NOTE:PLEASE SEE PREVIOUS NOTE #2. PLEASE SEE A
 METHOD *A* IS STILL BEING SUBMITTED. PLEASE SEE
 13-101.1.3
 PLEASE SEE THE INPUT DATA REPORT AS REQUIRED TO BE PART
 OF THE ENERGY CALCULATIONS IS STILL NOT BEING
 SUBMITTED. THE REVIEW AND SIGN OFF FROM OTHER REVIEW
 TRADE(S) HAS BEEN VOIDED.
 THIS WOULD REQUIRE THE ENTIRE STRUCTURE TO BE BROUGHT
 INTO COMPLIANCE. PLEASE SUBMIT COMPLETED ENERGY
 CALCULATIONS AS NO INPUT DATA REPORT WAS SUBMITTED
 WHICH IS REQUIRED TO BE PART OF THE ENERGY
 CALCULATIONS.
 13-415.1.A, 13-415.2, 13-415.1.B,13-415.1.ABC.1.3 ETC
  
 3) NOTE: PLEASE SEE 13-413.1.ABC.1.1, .1.2 AND PROVIDE
 NOTES ON PLANS.
  
 4) NOTE: PLEASE BE SURE TO REMOVE OLD/VOIDED SHEETS
 FROM SETS. PLEASE ALSO DO NOT ATTACH SUPPORTING
 DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS.
  
 5) NOTE: PLEASE SEE THE ELECTRICAL RISER HAS NOW BEEN
 COMPLETELY REVISED.
 PLEASE SUBMIT COMPLETED INFORMATION FOR THE FOLLOWING:
 PLEASE SUBMIT AIC RATINGS PER 110.9
 PLEASE SEE 250.6, 250.24 AS NO *EQUIPMENT GROUNDING
 CONDUCTORS* ARE PERMITTED BEFORE THE FIRST MEANS OF
 DISCONNECT.
 PLEASE SEE THE RISER SHOWS NEW 400AMP MAIN PANEL YET NO
 INFORMATION IS SHOWN. IN FACT THE RISER SHOWS NEW
 200AMP DISCONNECT AND NEW 200AMP MCB.???
 PLEASE SEE NO CHANGE WAS MADE FROM PREVIOUS METER CAN.
 THE OLD METER CAN WAS LESS IN AMPERAGE.
 PLEASE SEE THE RISER ALSO SHOWS NEW EQUIPMENT GROUNDING
 CONDUCTORS TO FPL WHICH ARE NOT PERMITTED.
 PLEASE SEE PLANS DO NOT SHOW LOCATIONS OF THE NEW
 SERVICE EQUIPMENT.
 PLEASE SEE THE MAINS CAN NOT BE CONFIRMED TO BE
 GROUPED.
 PLEASE SEE NO NEW LOCATION FOR COMPLETE GROUNDING
 ELECTRODE SYSTEM AS SERVICE HAS NOW BEEN INCREASED AND
 CHANGED.
 AT THIS TIME THERE ARE TOO MANY CODE SECTIONS TO BE
 GIVEN.
 PLEASE SEE 230.70, 230.71, 230.72, 110.26, 240.4,
 250.50, ETC ONLY A FEW ARE NOTED, PLEASE SEE 2005
 NFPA-70
  
 6) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2004 FBC W/2006 REVISIONS.
 ** THIS IS REQUIRED ON ELECTRICAL PLANS.
  
 7) NOTE: PLEASE COMPLETE ELECTRICAL PLANS FOR ALL
 LIGHTING ETC FOR INSIDE AS WELL AS OUTSIDE. THE
 EXTERIOR LIGHTING AS SHOWN ON ARCHITECTURAL SHEETS AS
 WELL AS LIGHTING LOCATED ON-SITE IS NOT BEING SHOWN.
 PLEASE COMPLETE.
 NEC 2005
 FBC 106.5.1.2, 106.1.2
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 14:50 Sent To  
Notes
2007-12-03 14:50:13 
 ** DENIED REVISION **
  
  
 1) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK AT SITE IS TO BE REVISED.
 THE WORK AT SITE HAS GONE WAY BEYOND THE OLD APPLIED
 VALUE OF $40K.
 PLEASE SEE FBC 108.3 AS THE VALUE IS TO INCLUDE ALL
 LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC.
  
 2) NOTE: PLEASE SEE A METHOD *A* IS BEING SUBMITTED FOR
 WHOLE BUILDING COMPLIANCE. THIS WOULD REQUIRE THE
 ENTIRE STRUCTURE TO BE BROUGHT INTO COMPLIANCE. PLEASE
 SUBMIT COMPLETED ENERGY CALCULATIONS AS NO INPUT DATA
 REPORT WAS SUBMITTED WHICH IS REQUIRED TO BE PART OF
 THE ENERGY CALCULATIONS.
 13-415.1.A, 13-415.2, 13-415.1.ABC.1.3 ETC
  
 3) NOTE: PLEASE SEE 13-413.1.ABC.1.1, .1.2 AND PROVIDE
 NOTES ON PLANS.
  
 4) NOTE: PLEASE PROVIDE DOCUMENTATION FOR NEW DESIGNERS
 OF RECORD.
 FAC 61G15, FS 471.025
  
 5) NOTE: PLEASE SEE SOME SHEETS ARE MISSING TITLE
 BLOCKS PER FAC 61G15-23.002
  
 6) NOTE: PLEASE SEE 250.6 AND 250.24 AS *EQUIPMENT
 GROUNDING CONDUCTORS* ARE NOT INSTALLED BEFORE THE
 FIRST MEANS OF DISCONNECT.
  
 7) NOTE: PLEASE PROVIDE COMPLETED ELECTRICAL PLANS FOR
 THE ENTIRE SCOPE OF ELECTRICAL WORK ONSITE-.
 THE NEW REVISED ELECTRICAL PLANS DO NOT REFLECT WORK AT
 SITE WHICH HAS BEEN VIEWED BY THIS REVIEWER.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-13 Cont ID  
Sent By dpalmer Date 2007-09-13 Time 11:34 Rev Time 0.00
Received By dpalmer Date 2007-09-13 Time 11:34 Sent To B
Notes
2007-09-13 11:35:18PLANS REMOVED FROM INCOMING BY LM, ROUTED BACK TO LM.
 ELEC OK.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-04 Cont ID  
Sent By dpalmer Date 2007-07-04 Time 10:29 Rev Time 0.00
Received By dpalmer Date 2007-07-04 Time 10:00 Sent To I
Notes
2007-07-04 10:29:522007-07-04 10:29:52
  
 ** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE ONE OF THE COMMENTS MADE AND NOTED
 AS **IMPORTANT** ON PREVIOUS REVIEW WAS NOT DONE.
 PLEASE SEE THE NOTE REQUESTED FOR ALL OLD/VOIDED SHEETS
 TO BE *REMOVED* FROM SETS. IT ALSO REQUESTED FOR ONLY
 THE NEW SHEETS TO BE INSERTED INTO COMPLETED SETS FOR
 REVIEW AND STAMPING. PLEASE SEE NOTE WHICH THEN
 REQUESTED FOR ONLY ONE SET/COPY OF THE *OLD/VOIDED*
 SHEETS TO BE SUBMITTED FOR REFERENCE ONLY.
 PLEASE SEE ALL OF THE OLD/VOIDED SHEETS WERE LEFT IN
 SETS. PLEASE REMOVE.
  
  
 2) NOTE:PLEASE SEE PREVIOUS NOTE MENTIONED FOR MORE
 INFORMATION ON FIXTURES AND TO COMPLETE FIXTURE LEGEND.
 THIS NEEDED TO CORRELATE WITH PLANS FOR ALL FIXTURES AS
 SHOWN ON ARCHITECTURAL AND ELECTRICAL PLANS. PLEASE SEE
 THE FIXTURE LEGEND IS NOT COMPLETE AS NO INFORMATION
 WAS PROVIDED.
  
 ** PREVIOUS NOTES #3 AND #4**
 ** PLEASE SEE ELECTRICAL PLANS INDICATE SEVERAL
 *J-BOXES* FOR WHAT IS SHOWN AS LIGHT FIXTURES ON
 ARCHITECTURAL SHEETS. PLEASE SHOW LIGHT FIXTURES,
 PLEASE LABEL AND PROVIDE INFORMATION ON FIXTURE LEGEND
 WITH OTHER FIXTURES.
 FBC 106.1.2 ADMIN SECTON.
  
 ** PLEASE SEE PLANS MENTIONS THAT THE EXISTING CIRCUITS
 WILL BE UTILIZED FOR NEW LIGHTS, HOWEVER BASES ON THE
 WATTAGES OF THE EXISTING FIXTURES BEING REMOVED AND THE
 UNKNOWN OF THE NEW FIXTURES AND LIGHTING BEING
 INSTALLED, PLEASE PROVIDE THIS INFORMATION ON THE
 NUMBER OF EXISTING CIRCUITS WHICH WILL BE USED. THIS
 WILL BE CONFIRMED WITH THE FIXTURES AND WATTAGES.
 106.1.2, 106.5.3.1.2.
 NEC 240.4, 310.16, 410, 110.3 ETC.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE #5 BELOW REQUESTED
 THE INSTALLATION OF WINDOW RECEPTACLES DIRECTLY ABOVE
 WINDOWS. THE RESPONSE LETTER MENTIONS TO SEE SHEET
 E-1.0, HOWEVER NONE ARE LOCATED ON PLANS AS MENTIONED.
 THE SAME NOTE APPLIES.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE VERIFY IF THERE ARE NEW OR EXISTING WINDOW
 RECEPTACLES PER 210.62/220.12
 FBC 106.1.2
  
 4) NOTE:PLEASE SEE PREVIOUS NOTE #7 AS IT REQUESTED
 LIGHTING CLARIFICATION FOR THE EXISTING BATH ROOMS AS
 THEY INDICATED EM TYPE LIGHT FIXTURES, HOWEVER SEE THE
 PLANS NOW DO NOT SHOWOR INDICATE ANY LIGHTING IN THE
 BATHROOMS AND ONLY SHOWS *J* FOR JUNCTION BOX. THIS IS
 NOT ACCEPTABLE TO THE LIFE SAFETY CODE, THIS OFFICE OR
 THE FIRE MARSHAL OFFICE.
 PLEASE INDICATE SOME SORT OF LIGHT FIXTURES IN THE
 BATHROOMS WHICH WILL BE REQUIRED.
  
 ** PREVIOUS NOTE #7**
 PLEASE SHOW NEW OR EXISTING EMERGENCY AND EXIT LIGHTS
 PER NFPA-101 7.8 AND 7.9.
 PLEASE SEE THAT MINIMUM LEVELS OF LIGHTING ARE REQUIRED
 TO THE PUBLIC RIGHT OF WAY OUT OF BUILDING UNDER
 EMERGENCY CONDITIONS.
 IF EXISTING, PLEASE SHOW.
 PLEASE SEE THE NEW REMODELED BATHROOMS INDICATE TYPE
 *EM* FIXTURES, ARE THESE BATTERY BACK UP?
  
 5) NOTE: PLEASE BE SURE TO CORRELATE ALL ELECTRICAL ON
 ARCHITECTURAL SHEETS WITH THAT AS SHOWN ON THE
 ELECTRICAL SHEETS.
 PLEASE SEE THESE ARE DIFFERENT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-04 10:02:422007-07-04 10:02:42
 PLANS REMOVED FROM INCOMING. PLANS WILL RETURN TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW
 IS COMPLETED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-04 Cont ID  
Sent By dpalmer Date 2007-02-04 Time 18:25 Rev Time 0.00
Received By dpalmer Date 2007-02-04 Time 18:03 Sent To  
Notes
2007-02-04 18:25:04 
 ** UNSAT **
  
 1) NOTE: PLEASE SEE THE CODES ADOPTED AND IN DESIGN
 SHALL BE STATED ON THE PLANS.
 PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE STATE OF
 FLORIDA ADOPTED THE 2006 REVISIONS TO THE 2004 FBC AND
 THE 2005 NFPA-70.
 PLEASE BE SURE TO STATE THE FOLLOWING ON THE PLANS AT A
 MINIMUM AND ANY OTHERS WHICH MAY BE MENTIONED BY OTHER
 TRADES.
 2004 FBC W/2006 REVISONS)
 2005 NFPA-70 NEC.
 2002 NFPA-72 (IF APPLICABLE)
 2003 NFPA-101 LIFE SAFETY CODE.
  
 2) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH WHAT
 APPEARS TO BE *INITIALS* FROM THE DESIGN PROFESSIONAL.
 IF THIS IS INDEED THE LEGAL SIGNATURE OF THE SAID
 DESIGNER OF RECORD, PLEASE SUBMIT A SIGNED, DATED,
 SEALED AND NOTARIZED LETTER FOR LEGAL SIGNATURE
 VERIFICATION.
 FAC 61G15-23.002, AND FS 471.025
 PLEASE BE SURE THE NOTARY FOLLOWS THE GUIDELINES AS SET
 FORTH IN FS 117.05 FOR CORRECT STATEMENT ON LETTER.
  
 3) NOTE: PLEASE SEE ELECTRICAL PLANS INDICATE SEVERAL
 *J-BOXES* FOR WHAT IS SHOWN AS LIGHT FIXTURES ON
 ARCHITECTURAL SHEETS. PLEASE SHOW LIGHT FIXTURES,
 PLEASE LABEL AND PROVIDE INFORMATION ON FIXTURE LEGEND
 WITH OTHER FIXTURES.
 FBC 106.1.2 ADMIN SECTON.
  
 4) NOTE: PLEASE SEE PLANS MENTIONS THAT THE EXISTING
 CIRCUITS WILL BE UTILIZED FOR NEW LIGHTS, HOWEVER BASES
 ON THE WATTAGES OF THE EXISTING FIXTURES BEING REMOVED
 AND THE UNKNOWN OF THE NEW FIXTURES AND LIGHTING BEING
 INSTALLED, PLEASE PROVIDE THIS INFORMATION ON THE
 NUMBER OF EXISTING CIRCUITS WHICH WILL BE USED. THIS
 WILL BE CONFIRMED WITH THE FIXTURES AND WATTAGES.
 106.1.2, 106.5.3.1.2.
 NEC 240.4, 310.16, 410, 110.3 ETC.
  
 5) NOTE: PLEASE VERIFY IF THERE ARE NEW OR EXISTING
 WINDOW RECEPTACLES PER 210.62/220.12
 FBC 106.1.2
  
 6) NOTE: PLEASE VERIFY NEW OR EXISTING SIGN CIRCUIT PER
 600.5.
 FBC 106.1.2
  
 7) NOTE: PLEASE SHOW NEW OR EXISTING EMERGENCY AND EXIT
 LIGHTS PER NFPA-101 7.8 AND 7.9.
 PLEASE SEE THAT MINIMUM LEVELS OF LIGHTING ARE REQUIRED
 TO THE PUBLIC RIGHT OF WAY OUT OF BUILDING UNDER
 EMERGENCY CONDITIONS.
 IF EXISTING, PLEASE SHOW.
 PLEASE SEE THE NEW REMODELED BATHROOMS INDICATE TYPE
 *EM* FIXTURES, ARE THESE BATTERY BACK UP?
  
 ** PLEASE BE AWARE OF ANY POSSIBLE COMMENTS WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-04-23 Cont ID  
Sent By mwennerg Date 2008-04-23 Time 16:09 Rev Time 0.00
Received By mwennerg Date 2008-04-23 Time 16:09 Sent To  
Notes
2008-04-23 16:09:50SHEET A-3.0 STAMPED, SIGNED AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-12-31 Cont ID  
Sent By mawillia Date 2007-12-31 Time 10:42 Rev Time 0.00
Received By mawillia Date 2007-12-31 Time 10:33 Sent To  
Notes
2007-12-31 10:42:28*****PROVISO*****
  
 REVISED PLAN SHEETSA-3.0 (WHICH WAS VOIDED) NEEDS TO
 BE FIRE-STAMPED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-09-13 Cont ID  
Sent By mawillia Date 2007-09-13 Time 13:14 Rev Time 0.00
Received By mawillia Date 2007-09-13 Time 12:27 Sent To  
Notes
2007-09-13 12:43:28*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE REVIEWS HAVE BEEN
 SATISFIED;PLAN SHEETS A-1.0, A-3.0, AND E-1.0 WERE
 STAMPED, INITIALED, AND DATED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 14:06 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 13:44 Sent To  
Notes
2007-07-26 14:01:44*****UNSAT*****
  
 ALL OF THE COMMENTS FROM THE PREVIOUS FIRE REVIEW HAVE
 BEEN SATISFIED EXCEPT FOR THE FOLLOWING:
  
  
 8.PLEASE SHOW THE LOCATION OF THE FIRE
 EXTINGUISHER(S) FOR THE STRUCTURE WHICH SATIFIES THE
 75' TRAVEL DISTANCE
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-28 Cont ID  
Sent By mawillia Date 2007-02-28 Time 17:40 Rev Time 0.00
Received By mawillia Date 2007-02-28 Time 17:40 Sent To  
Notes
2007-02-28 18:24:16*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, AND
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 SAID PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.THE BUILDING OR PORTIONS OF THE BUILDING WILL BE
 PERMITTED TO BE OCCUPIED DURING THE SCOPE OF WORK ONLY
 WHERE THE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 PROTECTION ARE IN PLACE AND MAINTAINED.
  
 6.ON THE APPROPIATE PLAN SHEETS, FURTHER SPECIFY
 NORTH, SOUTH , EAST, AND WEST EXTERIOR ELEVATIONS FOR
 THIS STRUCTURE.
  
 7.ON SHEET A-3.0, POST THE NUMERICAL ADDRESS ON THE
 FRONT SIDE (EAST) ELEVATION.AS PER WEST PALM BEACH
 CODE , THOSE NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT
 AND NO LESS THAN 1"IN WIDTH.
  
 8.PLEASE SHOW THE LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHER(S) FOR THE STRUCTURE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-07-23 Cont ID  
Sent By adarroug Date 2008-07-23 Time 13:33 Rev Time 0.00
Received By adarroug Date 2008-07-23 Time 13:32 Sent To B
Notes
2008-07-23 13:33:20TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-07-22 Cont ID  
Sent By adarroug Date 2008-07-22 Time 09:37 Rev Time 0.00
Received By adarroug Date 2008-07-22 Time 09:37 Sent To M
Notes
2008-07-22 09:37:49TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-07-22 Cont ID  
Sent By adarroug Date 2008-07-22 Time 09:11 Rev Time 0.00
Received By adarroug Date 2008-07-22 Time 09:11 Sent To P
Notes
2008-07-22 09:11:48TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-07-18 Cont ID  
Sent By adarroug Date 2008-07-18 Time 10:53 Rev Time 0.00
Received By adarroug Date 2008-07-18 Time 10:53 Sent To M
Notes
2008-07-18 10:54:07TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 10:49 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 10:49 Sent To B
Notes
2008-07-11 10:50:02TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-06-26 Cont ID  
Sent By shill Date 2008-06-26 Time 17:09 Rev Time 0.00
Received By shill Date 2008-06-26 Time 17:09 Sent To E
Notes
2008-06-26 17:09:38TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-04-18 Cont ID  
Sent By adarroug Date 2008-04-18 Time 11:16 Rev Time 0.00
Received By adarroug Date 2008-04-18 Time 11:16 Sent To  
Notes
2008-04-18 11:20:25TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-03-31 Cont ID  
Sent By adarroug Date 2008-03-31 Time 14:41 Rev Time 0.00
Received By adarroug Date 2008-03-31 Time 14:41 Sent To E
Notes
2008-03-31 14:42:17TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-03-19 Cont ID  
Sent By shill Date 2008-03-19 Time 14:56 Rev Time 0.00
Received By shill Date 2008-03-19 Time 14:56 Sent To E
Notes
2008-03-19 14:56:47TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 15:04 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 15:04 Sent To  
Notes
2008-03-10 16:26:01TO "COMM" BD#9
2008-03-07 15:05:07WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 08:34 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 08:34 Sent To  
Notes
2008-02-20 08:37:29TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-23 Cont ID  
Sent By adarroug Date 2008-01-23 Time 10:31 Rev Time 0.00
Received By adarroug Date 2008-01-23 Time 10:31 Sent To  
Notes
2008-01-23 10:39:22TO "COMM" BD#39

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 16:18 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 16:18 Sent To  
Notes
2007-11-30 13:38:58TO "COMM" BD#41
2007-11-15 16:18:31WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 11:51 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 11:51 Sent To Z
Notes
2007-10-03 11:52:07TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-04 Cont ID  
Sent By adarroug Date 2007-09-04 Time 12:07 Rev Time 0.00
Received By adarroug Date 2007-09-04 Time 12:07 Sent To  
Notes
2007-09-04 12:07:52WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 17:49 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 17:49 Sent To  
Notes
2007-07-09 15:28:01TO "COMM" BD#35
2007-06-24 17:49:48WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-07 Cont ID  
Sent By jwitmer Date 2007-03-07 Time 16:31 Rev Time 0.00
Received By jwitmer Date 2007-01-18 Time 16:41 Sent To  
Notes
2007-01-30 10:01:06TO "COMM" BD#20/4 APPL'S
2007-01-18 16:47:50WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-02-27 Cont ID  
Sent By rkussner Date 2008-02-27 Time 09:28 Rev Time 0.00
Received By rkussner Date 2008-02-27 Time 09:27 Sent To  
Notes
2008-02-27 09:25:44PROVISO:AN IRRIGATION PLAN SHALL BE SUBMITTED AND
 APPROVED UNDER A SEPARATE IRRIGATION PERMIT PRIOR TO
 INSTALLATION OF IRRIGATION SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2008-07-22 Cont ID  
Sent By tgordon Date 2008-07-22 Time 14:57 Rev Time 0.30
Received By tgordon Date 2008-07-22 Time 14:57 Sent To  
Notes
2008-07-22 14:59:07MECHANICAL REVISION ROOF CURB DETAIL.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status F Date 2008-07-18 Cont ID  
Sent By tgordon Date 2008-07-18 Time 15:50 Rev Time 0.45
Received By tgordon Date 2008-07-18 Time 15:50 Sent To B
Notes
2008-07-18 15:57:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION (ROOF CURB DETAIL).
  
 *** DENIED ***
  
 1) PER 2004 FBC 1509.7 THE 24"X24" FRESH AIR DUCT WILL
 NEED TO HAVE A MINIMUM OF 18 INCHES OF CLEARANCE ABOVE
 THE ROOF SURFACE. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-04-23 Cont ID  
Sent By tgordon Date 2008-04-23 Time 15:45 Rev Time 0.30
Received By tgordon Date 2008-04-23 Time 15:45 Sent To  
Notes
2008-04-23 15:46:30REVISION TO MECH. PLANS, ENERGY CAL'S, AND COOLING LOAD
 CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-04-07 Cont ID  
Sent By tgordon Date 2008-04-07 Time 10:54 Rev Time 0.30
Received By tgordon Date 2008-04-07 Time 10:54 Sent To B
Notes
2008-04-07 10:59:38REVISED MECHANICAL PLANS ARE CODE COMPLIANT. ENERGY
 CALCULATIONS WILL NEED CORRECTIONS, SEE ELECTRICAL
 REVIEW NOTES FROM 4/4/08.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-03-11 Cont ID  
Sent By tgordon Date 2008-03-11 Time 13:45 Rev Time 0.30
Received By tgordon Date 2008-03-11 Time 13:45 Sent To  
Notes
2008-03-11 13:46:37REVISION TO MECHANICAL PLANS, ENERGY CAL'S, AND COOLING
 LOAD CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-03-04 Cont ID  
Sent By tgordon Date 2008-03-04 Time 15:21 Rev Time 0.20
Received By tgordon Date 2008-03-04 Time 15:21 Sent To  
Notes
2008-03-04 15:26:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS
  
 *** DENIED ***
 ** NOT NOTICED IN LAST REVIEW **
 1) SEE ELECTRICAL REVIEW NOTE #2 REGARDING THE INPUT
 DATA REPORT MISSING FROM THE ENERGY CALCULATIONS,
 PLEASE CORRECT.
  
 2) SEE ELECTRICAL REVIEW NOTE #1 REGARDING PERMIT
 VALUE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-03-04 Cont ID  
Sent By tgordon Date 2008-01-28 Time 11:21 Rev Time 0.45
Received By tgordon Date 2008-01-28 Time 11:21 Sent To  
Notes
2008-01-28 11:23:39** REVISION TO MECHANICAL PLANS **
  
 1) SEE REVIER NOTE 3-4-08.
  
 ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (A) WALK-IN-COOLER
 (B) KITCHEN HOOD
 (C) FIRE SUPPRESSION
 ** SUBMIT PLANS WITH PERMIT APPLICATION. PLAN FOR
 KITCHEN HOOD W/MASTER.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-12-03 Cont ID  
Sent By tgordon Date 2007-12-03 Time 13:49 Rev Time 0.35
Received By tgordon Date 2007-12-03 Time 13:49 Sent To  
Notes
2007-12-03 14:12:49PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) SEE PLAN PAGE M-2. THE 3" WATER HEATER VENT PIPE MAY
 NOT BE WITHIN 10 FT. OF THE OUTDOOR AIR INTAKE, SEE
 2004 FBC/M 401.5.1
  
 2) SEE PLAN PAGE M-2 DUCT SUPPORT ON ROOF DETAIL, STATE
 TYPE AND SIZE OF ANCHORS TO SECURE THE DUCT SUPPORT TO
 THE ROOF.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-07-17 Cont ID  
Sent By tgordon Date 2007-07-17 Time 13:36 Rev Time 0.20
Received By tgordon Date 2007-07-17 Time 13:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-21 Cont ID  
Sent By tgordon Date 2007-02-21 Time 16:12 Rev Time 0.25
Received By tgordon Date 2007-02-21 Time 16:12 Sent To  
Notes
2007-02-21 16:14:02*** DENIED ***
 1) SEE PLUMBING REVIEW NOTE #1, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-07-23 Cont ID  
Sent By mperson Date 2008-07-23 Time 10:16 Rev Time 0.00
Received By mperson Date 2008-07-23 Time 10:16 Sent To B
Notes
2008-07-23 10:19:45REVISION SHEET A-6.1: "OK" ADDED TEMPERING VALVE FOR
 BATHROOM SINKS.
 NOTE: RED LINE CORRECTION TO REVISION NUMBER FOR THE
 ADDED TEMPERING VALVE.**MRPERSON.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-14 Cont ID  
Sent By kstevens Date 2007-12-14 Time 18:27 Rev Time 0.00
Received By kstevens Date 2007-12-14 Time 18:27 Sent To  
Notes
2007-12-14 18:28:11REVISION APPROVED 1 SHEET

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-07-17 Cont ID  
Sent By kstevens Date 2007-07-17 Time 11:01 Rev Time 0.00
Received By kstevens Date 2007-07-17 Time 11:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-21 Cont ID  
Sent By kstevens Date 2007-02-21 Time 12:47 Rev Time 0.00
Received By kstevens Date 2007-02-21 Time 12:47 Sent To  
Notes
2007-02-21 12:52:25DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS. THE SIGNATURE OF THE ENGINEER OF RECORD
 IS REQUIRED WHEN THE SEAL IS AFFIXED. INITIALS ARE NOT
 APPROVED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ENGINEER OF RECORD, THEN A SIGNED, SEALED, DATED,
 NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE SHALL
 BE SUBMITTED FOR OUR RECORD. FAC 61G15-23.002(2) & FS
 471.025
  
 2. PLUMBING PLANS ARE OTHERWISE CODE COMPLIANT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 9 Status N Date 2008-03-14 Cont ID  
Sent By adavila Date 2008-03-14 Time 19:08 Rev Time 0.00
Received By adavila Date 2008-03-14 Time 19:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 8 Status P Date 2008-03-14 Cont ID  
Sent By adavila Date 2008-02-27 Time 08:52 Rev Time 0.00
Received By adavila Date 2008-02-26 Time 16:49 Sent To  
Notes
2008-03-14 08:53:38PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 7 Status F Date 2008-01-25 Cont ID  
Sent By adavila Date 2008-01-25 Time 18:01 Rev Time 0.00
Received By adavila Date 2008-01-25 Time 12:21 Sent To  
Notes
2008-01-25 18:01:49PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. ACCORDING TO THE RESUBMITTED PACKET, THE VALUE OF
 THE PROPOSED WORK INCREASED TO $119,700, WHICH EXCEEDS
 THE VALUE OF THE STRUCTURE PER THE PALM BEACH COUNTY
 PROPERTY APPRAISER?S OFFICE ($108,249).
  
 2. REPEAT COMMENT - PER SECTION 94-441(C) OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, RENOVATIONS, REPAIRS,
 ALTERATIONS OR REDEVELOPMENTS WHICH EXCEED 50 PERCENT
 OF THE VALUE OF THE STRUCTURE SHALL COMPLY WITH THE
 PROVISIONS OF ARTICLE XIV, LANDSCAPING, LAND CLEARING,
 AND TREE PROTECTION, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
 A. A LANDSCAPE PLAN, PREPARED, SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT, AND MEETING THE
 PROVISIONS OF ARTICLE XIV, LANDSCAPING, LAND CLEARING,
 AND TREE PROTECTION, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS SHALL BE PROVIDED.
 B. THE LANDSCAPE REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM.
 C. PLEASE CONTACT ROBERT KUSSNER, LANDSCAPE PLANNER,
 FOR LANDSCAPE REQUIREMENTS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
2008-01-25 12:21:14IN ZONING FOR REVIEW.

Review Stop Z ZONING
Rev No 6 Status F Date 2007-12-04 Cont ID  
Sent By adavila Date 2007-12-04 Time 12:34 Rev Time 0.00
Received By adavila Date 2007-12-04 Time 12:34 Sent To  
Notes
2007-12-04 12:34:37PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. IT CAME TO STAFF'S ATTENTION THAT THE WORK VALUE
 APPLIED FOR THIS SITE HAS INCREASED, AND MAY EXCEED 50
 PERCENT OF THE IMPROVEMENT VALUE OF THE STRUCTURE.
 PLEASE PROVIDE THE NEW WORK VALUE FOR THIS PERMIT, AS
 WELL AS THE TOTAL VALUE OF ALL PERMITS APPLIED FOR THIS
 SITE (AWNINGS, SIGN, REPLACEMENT OF KITCHEN HOOD,
 ETC.).
  
 A. PLEASE NOTE THAT PER SECTION 94-441(C) OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, RENOVATIONS, REPAIRS,
 ALTERATIONS OR REDEVELOPMENTS WHICH EXCEED 50 PERCENT
 OF THE VALUE OF THE STRUCTURE SHALL COMPLY WITH THE
 PROVISIONS OF ARTICLE XIV, LANDSCAPING, LAND CLEARING,
 AND TREE PROTECTION, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
 I. A LANDSCAPE PLAN, PREPARED, SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT, AND MEETING THE
 PROVISIONS OF ARTICLE XIV, LANDSCAPING, LAND CLEARING,
 AND TREE PROTECTION, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS SHALL BE PROVIDED.
 II. THE LANDSCAPE REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 5 Status P Date 2007-11-20 Cont ID  
Sent By adavila Date 2007-11-20 Time 08:41 Rev Time 0.00
Received By adavila Date 2007-11-20 Time 08:41 Sent To  
Notes
2007-11-20 08:41:43PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 4 Status P Date 2007-10-03 Cont ID  
Sent By adavila Date 2007-10-03 Time 14:24 Rev Time 0.00
Received By adavila Date 2007-10-03 Time 14:24 Sent To  
Notes
2007-10-03 14:24:30PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-09-10 Cont ID  
Sent By adavila Date 2007-09-10 Time 11:44 Rev Time 0.00
Received By adavila Date 2007-09-06 Time 17:44 Sent To  
Notes
2007-09-10 11:46:32PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.NONE OF THE COMMENTS FROM THE JULY 16, 2007, REVIEW
 WERE ADDRESSED.ALL COMMENTS SHALL BE ADDRESSED PRIOR
 TO BUILDING PERMIT APPROVAL.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  
 ***FROM 07/16/2007***
  
 1. PROVIDE A CURRENT SURVEY OF THE PROPERTY.
  
 2. HANDICAP AND STANDARD PARKING DETAILS DO NOT MATCH
 THE PARKING SPACES ON THE SITE PLAN.
 A. PARKING STALL DETAILS SHALL BE DELINEATED AT THE
 SAME DIMENSIONS, ANGLE AND DIRECTION AS THEY ARE SHOWN
 ON THE SITE PLAN.
  
 3. PARKING ANGLE SHALL BE INDICATED ON THE SITE PLAN.
  
 4. HANDICAP SYMBOL SHALL BE 2 FEET FROM THE OPEN END OF
 THE PARKING SPACE.
  
 5. PURSUANT TO SECTION 94-443(C)(5)(B) OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, WHEEL STOPS SHALL BE
 2 FEET FROM THE CURB TO THE BACK OF THE WHEEL STOP.
  
 6. HANDICAP AND REGULAR PARKING STALLS SHALL COMPLY
 WITH SECTION 94-485(J) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
 A. HANDICAP PARKING SPACE, AND REGULAR PARKING SPACES
 IN FRONT OF THE EXISTING STORAGE ROOM SHALL HAVE A
 STALL DEPTH OF 19 FEET 10 INCHES IF PARKING SPACES ARE
 AT A 60 DEGREE ANGLE.
 B. ALL REGULAR PARKING SPACES SHALL BE DELINEATED BY 4
 INCH WHITE DOUBLE STRIPED LINES.
  
 7. PLANTERS ALONG THE EAST SIDE OF THE BUILDING SHALL
 BE DELINEATED ON THE SITE PLAN.
  
 8. PROVIDE SQUARE FOOTAGE OF THE PLANTERS.PLEASE NOTE
 THAT IF PLANTERS ARE TO BE REMOVED, THE SAME AMOUNT OF
 LANDSCAPE SQUARE FOOTAGE SHALL BE RELOCATED ELSEWHERE
 ON SITE.
  
 9. IF IT DOES NOT CURRENTLY EXIST, A SHADE OR FLOWERING
 TREE SHALL BE PROVIDED ON THE TERMINAL ISLAND NEXT TO
 THE HANDICAP PARKING SPACE.
  
 10. PLEASE NOTE THAT ANY REVISION TO THE LANDSCAPE, TO
 INCLUDE THE ADDITION OF THE TREE REQUIRES A LANDSCAPE
 PLAN CREATED BY A REGISTERED LANDSCAPE ARCHITECT.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-07-16 Cont ID  
Sent By adavila Date 2007-07-16 Time 14:47 Rev Time 0.00
Received By adavila Date 2007-07-12 Time 08:25 Sent To  
Notes
2007-07-16 14:47:44PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE A CURRENT SURVEY OF THE PROPERTY.
  
 2. HANDICAP AND STANDARD PARKING DETAILS DO NOT MATCH
 THE PARKING SPACES ON THE SITE PLAN.
 A. PARKING STALL DETAILS SHALL BE DELINEATED AT THE
 SAME DIMENSIONS, ANGLE AND DIRECTION AS THEY ARE SHOWN
 ON THE SITE PLAN.
  
 3. PARKING ANGLE SHALL BE INDICATED ON THE SITE PLAN.
  
 4. HANDICAP SYMBOL SHALL BE 2 FEET FROM THE OPEN END OF
 THE PARKING SPACE.
  
 5. PURSUANT TO SECTION 94-443(C)(5)(B) OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, WHEEL STOPS SHALL BE
 2 FEET FROM THE CURB TO THE BACK OF THE WHEEL STOP.
  
 6. HANDICAP AND REGULAR PARKING STALLS SHALL COMPLY
 WITH SECTION 94-485(J) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
 A. HANDICAP PARKING SPACE, AND REGULAR PARKING SPACES
 IN FRONT OF THE EXISTING STORAGE ROOM SHALL HAVE A
 STALL DEPTH OF 19 FEET 10 INCHES IF PARKING SPACES ARE
 AT A 60 DEGREE ANGLE.
 B. ALL REGULAR PARKING SPACES SHALL BE DELINEATED BY 4
 INCH WHITE DOUBLE STRIPED LINES.
  
 7. PLANTERS ALONG THE EAST SIDE OF THE BUILDING SHALL
 BE DELINEATED ON THE SITE PLAN.
  
 8. PROVIDE SQUARE FOOTAGE OF THE PLANTERS.PLEASE NOTE
 THAT IF PLANTERS ARE TO BE REMOVED, THE SAME AMOUNT OF
 LANDSCAPE SQUARE FOOTAGE SHALL BE RELOCATED ELSEWHERE
 ON SITE.
  
 9. IF IT DOES NOT CURRENTLY EXIST, A SHADE OR FLOWERING
 TREE SHALL BE PROVIDED ON THE TERMINAL ISLAND NEXT TO
 THE HANDICAP PARKING SPACE.
  
 10. PLEASE NOTE THAT ANY REVISION TO THE LANDSCAPE, TO
 INCLUDE THE ADDITION OF THE TREE REQUIRES A LANDSCAPE
 PLAN CREATED BY A REGISTERED LANDSCAPE ARCHITECT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-02-27 Cont ID  
Sent By adavila Date 2007-02-01 Time 09:35 Rev Time 0.00
Received By adavila Date 2007-01-31 Time 08:33 Sent To  
Notes
2007-02-01 09:44:24PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. AN ASPHALT SURVEY SHALL BE PROVIDED.
  
 3. PROVIDE PARKING LOT AND STALL DETAILS, INCLUDING
 HANDICAPPED PARKING SPACES (PLEASE REFER TO SECTION
 94-485(J) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS).
  
 4. ALL NEW SIGNS SHALL BE APPROVED ON A SEPARATE
 BUILDING PERMIT.
  
  
 QUESTIONS/CONCERNS, CONTACT ANDREINA DAVILA Q. AT (561)
 822-1435.