Plan Review Details - Permit 07010762
Plan Review Stops For Permit 07010762
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-23 Cont ID  
Sent By jwitmer Date 2007-02-23 Time 10:27 Rev Time 2.22
Received By jwitmer Date 2007-02-23 Time 10:27 Sent To  
Notes
2007-02-23 11:30:28BUILDING PLAN REVIEW
 PERMIT: 07010762
 ADD: 1750 FLORIDA MANGO RD
 CONT: OPTIMAL ELECTRIC
 TEL: (407)323-5321
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) SHEET E-2 INDICATES THIS LOCATION IS IN A "B" FLOOD
 ZONE, PLEASE CORRECT TO
 FLOOD ZONE A-9, MINIMUM FLOOD ELEVATION FOR FINISH SLAB
 IS 13'-6".
  
 3) SHEET S-2 FOUNDATION NOTE# 10 INDICATES TESTING FOR
 THE MINIMUM SAFE BEARING VALUE OF THE SOIL. FBC
 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 4)SHEET S-2 WIND DESIGN CRITERIA, PLEASE CORRECT THE
 IMPORTANCE FACTOR,
 ASCE 7-02 TABLE 1-1DESIGNATED EMERGENCY PREPAREDNESS,
 COMMUNICATIONS AND OPERATING CENTERS AND OTHER
 FACILITIES REQUIRED FOR EMERGENCY RESPONSE.
 CATEGORY IV/TABLE 6-1- IV=1.5
  
 5) VALUE FOR THE SCOPE OF WORK TO INCLUDE MATERIALS AND
 LABOR. THE VALUE OF THIS PROJECT IS UNDER THE COST OF
 THE GENERATOR ITSELF.
 108.3*BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED.FOR PERMITTINGPURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BYTHE INTERNATIONAL CODE
 CONGRESS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-30 Cont ID  
Sent By dpalmer Date 2007-01-30 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2007-01-30 Time 18:36 Sent To  
Notes
2007-01-30 18:39:36*** UNSAT ***
  
 1) NOTE: PLEASE SEE THE CODE CITED ON PLANS FOR THE
 NFPA-70 SHOULD READ THE 2005. PLEASE KNOW THAT THE
 STATE OF FLORIDA ADOPTED THE 2005 NEC ON DECEMBER 8TH,
 2006.
 PLEASE ALSO STATE THE 2006 REVISIONS TO THE 2004 FBC
 WHICH ALSO CHANGED ON THAT DATE.
  
 2) NOTE: PLEASE PROVIDE THE CORRECT VALUE AMOUNT FOR
 THE SCOPE OF WORK WHICH SHALL INCLUDE ALL LABOR AND
 MATERIALS EVEN IF ANY EQUIPMENT IS OWNER SUPPLIED.
 FBC 108.3
 THIS COMMENT HAS BEEN MADE ON EVERY OTHER PROJECT
 SUBMITTED FOR PERMIT IN THE CITY OF WEST PALM BEACH AND
 YET THE PERMIT APPLICATIONS ARE STILL BEING SUBMITTED
 WITH LOW VALUES.
 PLEASE KNOW AS THIS A LEGAL DOCUMENT SIGNED BY THE
 CONTRACTOR LICENSED UNDER FS 468, THE APPLICATIONS ARE
 BEING RETAINED IN FILES FOR POSSIBLE REVIEW BY THE
 STATE CONTRACTORS LICENSING BOARD.
 PLEASE PLACE THE CORRECTED VALUES ON APPLICATIONS
 BEFORE PERMITS ARE APPLIED FOR.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-02-22 Cont ID  
Sent By mawillia Date 2007-02-22 Time 22:03 Rev Time 0.00
Received By mawillia Date 2007-02-22 Time 19:18 Sent To  
Notes
2007-02-22 22:11:24*****APPROVED*****W/REMINDER
  
  
 1.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE ACCESS TO THE BUILDING/PROPERTY
 OR THE VICINITY THEREOF (INCLUDING FIRE LANES).
  
 TO BE STAMPED WHEN ALL PLAN REVIEWS HAVE BEEN SATISFIED

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-23 Cont ID  
Sent By jwitmer Date 2007-02-23 Time 11:32 Rev Time 0.00
Received By jwitmer Date 2007-01-18 Time 09:03 Sent To  
Notes
2007-01-30 09:23:02TO "COMM" BD#1
2007-01-18 09:04:03WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-02-15 Cont ID  
Sent By rregueir Date 2007-02-15 Time 08:05 Rev Time 0.00
Received By rregueir Date 2007-02-14 Time 15:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-02 Cont ID  
Sent By jbabcock Date 2007-02-02 Time 14:43 Rev Time 0.00
Received By jbabcock Date 2007-02-02 Time 14:38 Sent To I
Notes
2007-02-02 14:42:52PLANNING AND ZONING ***FAILED***
  
 1. PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
  
 2. PROVIDE FULL SIZE SITE PLANS, A SIGNED AND SEALED
 SURVEY, LANDSCAPE DETAILS, AND AN ELEVATION DETAIL (OF
 THE SCREENING REQUIREMENT)IN ORDER TO ILLUSTRATE
 COMPLIANCE WITH THE FOLLOWING STANDARDS:
  
 SECTION 94-305 (4) MECHANICAL EQUIPMENT. MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN FOUR FEET INTO A
 SETBACK. WINDOW AIR-CONDITIONING UNITS MAY NOT PROJECT
 MORE THAN 18 INCHES INTO A REQUIRED SIDE SETBACK.
  
 SECTION 94-444 (B) STATES THAT ALL MECHANICAL EQUIPMENT
 SHALL BE SCREENED.
  
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS.