| 2007-01-31 07:20:36 | 2007-01-31 07:20:36 |
| | ** UNSAT ** |
| | |
| | |
| | ** PLEASE SEE THESE SAME COMMENTS HAVE BEEN MADE ON |
| | SEVERAL OTHER PROJECTS LIKE THIS ONE, PLEASE CORRELATE |
| | PLANS, SCOPE OF WORK, VALUE, MANUFACTURES SPEC/CUT |
| | SHEETS BEFORE SUBMITTING. |
| | |
| | |
| | 1) NOTE:PLEASE CORRELATE PLANS, PERMIT APPLICATION |
| | AND SUBMITTALS. |
| | PLEASE SEE PLANS INDICATE A DIESEL GEN, AND NATURAL GAS |
| | GEN. PLEASE SEE THE PERMIT APPLICATION INDICATES A |
| | DIESEL UNIT. |
| | PLEASE KNOW A DIESEL GENERATOR OR TANK FOR PROPANE WILL |
| | NOT BE PERMITTED ON THE ROOF TOP. PLEASE ALSO KNOW ANY |
| | SPECIAL PERMISSION FOR OTHER GENERATOR ON ROOF IS NOT |
| | APPROVED AT THIS TIME. PLEASE KNOW A CONFERENCE WITH |
| | THE FIRE MARSHAL AND PLAN REVIEW FOR POSSIBILITIES OF |
| | THE PERMITTING A NAT GAS GEN MUST BE HELD BEFORE |
| | PERMISSION WILL BE GRANTED. SHUT DOWN OF FUEL, |
| | GENERATOR, MOTOR AND SHUNT OF FEEDERS MAY ALL BE |
| | REQUIRED ON THE GROUND FLOOR OF BLDG. |
| | PLEASE KNOW AS MORE THAN ONE SIZE OF GEN AND TYPE FOR |
| | PRIME MOVER IS BEING SUBMITTED, A COMPLETE REVIEW CAN |
| | NOT BE DONE AT THIS TIME. |
| | PLEASE SEE NFPA-110 PLEASE SEE ALL OF CHAPTER 7. PLEASE |
| | KNOW, GAS FUEL LINE SHALL NOT BE GALVANIZED 7.9.3.1. |
| | PLEASE ALSO SEE 701.11(B)(3) FOR DUEL FUEL SUPPLIES |
| | REQUIRED. MAY NOT RELY ONLY ON THE UTILITY AND MUST |
| | SUPPLY *ON-SITE* FUEL SUPPLY. |
| | |
| | 2) NOTE: PLEASE SEE THE VALUE AS SHOWN ON APPLICATION |
| | BASED ON THE SCOPE OF WORK IS EXTREMELY LOW AND A VALUE |
| | WILL BE ADJUSTED. THIS NEEDS TO INCLUDE ALL STRUCTURAL |
| | WORK, GAS/FUEL, TANKS ETC. |
| | **PLEASE KNOW, VALUE FOR COMPLETE SCOPE OF WORK SHALL |
| | INCLUDE ALL LABOR, |
| | MATERIALS, INSTALLATION OF GAS LINE/ TO ROOF TOP, GEN, |
| | ATS, STRUCTURAL WORK ETC. |
| | FBC 108.3 |
| | THIS COMMENT HAS BEEN MADE ON EVERY OTHER PROJECT |
| | SUBMITTED FOR PERMIT IN THE CITY OF WEST PALM BEACH AND |
| | YET THE PERMIT APPLICATIONS ARE STILL BEING SUBMITTED |
| | WITH LOW VALUES.PLEASE KNOW THAT IF APPLICATIONS ARE |
| | RESUBMITTED WITHOUT AN APPROPRIATE VALUE BEING ASSESSED |
| | BY THE CONTRACTOR, THE PLANS MAY NOT BE ROUTED FOR PLAN |
| | REVIEW OR PROCESSING AND WILL BE PLACED OUT FOR PICK |
| | UP. |
| | PLEASE KNOW AS THIS A LEGAL DOCUMENT SIGNED BY THE |
| | CONTRACTOR LICENSED UNDER FS 468, THE APPLICATIONS ARE |
| | BEING RETAINED IN FILES FOR POSSIBLE REVIEW BY THE |
| | STATE CONTRACTORS LICENSING BOARD. |
| | PLEASE PLACE THE CORRECTED VALUES ON APPLICATIONS |
| | BEFORE PERMITS ARE APPLIED FOR AS STATED PREVIOUSLY. |
| | |
| | |
| | 3) NOTE: PLEASE SEE THE CODE CITED ON PLANS FOR THE |
| | NFPA-70 SHOULD READ THE 2005. PLEASE KNOW THAT THE |
| | STATE OF FLORIDA ADOPTED THE 2005 NEC ON DECEMBER 8TH, |
| | 2006. |
| | PLEASE ALSO STATE THE 2006 REVISIONS TO THE 2004 FBC |
| | WHICH ALSO CHANGED ON THAT DATE. |
| | |
| | 4) NOTE: PLEASE KNOW DUE TO THE AMOUNT OF STRUCTURAL |
| | WORK IN SCOPE A GC WILL BE REQUIRED FOR THIS SCOPE AS |
| | IT IS NOT IN THE SCOPE OF AN ELECTRICAL CONTRACTOR. |
| | PLEASE KNOW THIS WORK IS STILL PENDING ON THE LOCATION |
| | OF THE GENERATOR AND WHETHER OR NOT THIS WILL BE |
| | LOCATED ON THE GROUND. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-01-30 18:53:21 | 2007-01-30 18:53:21 |
| | NOTES TO FOLLOW. |
| | WILL BE IN *F* STATUS. |