Plan Review Details - Permit 07010759
Plan Review Stops For Permit 07010759
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-05 Cont ID  
Sent By jwitmer Date 2007-02-05 Time 14:28 Rev Time 2.22
Received By jwitmer Date 2007-02-05 Time 14:28 Sent To  
Notes
2007-02-05 15:45:21BUILDING PLAN REVIEW
 PERMIT: 07010759
 ADD: 3901 S FLAGLER DR
 CONT: OPTIMAL ELECTRIC
 TEL: (407)323-0377
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET S-1 DESIGN CRITERIA:
 CORRECT (B) TO BUILDING CATEGORYIV
 DESIGNATED EMERGENCY PREPARDNESS, COMMUNICATION,
 REQUIRED FOR EMERGENCY RESPONSE.
 IV= 1.15
  
 4) A W SOLUTIONS STRUCTURAL ANALYSIS AND CALCULATIONS
 TO BE REVIEWED USING THE
 CRITERIA LISTED ABOVE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-31 Cont ID  
Sent By dpalmer Date 2007-01-31 Time 07:18 Rev Time 0.00
Received By dpalmer Date 2007-01-30 Time 18:46 Sent To  
Notes
2007-01-31 07:20:362007-01-31 07:20:36
 ** UNSAT **
  
  
 ** PLEASE SEE THESE SAME COMMENTS HAVE BEEN MADE ON
 SEVERAL OTHER PROJECTS LIKE THIS ONE, PLEASE CORRELATE
 PLANS, SCOPE OF WORK, VALUE, MANUFACTURES SPEC/CUT
 SHEETS BEFORE SUBMITTING.
  
  
 1) NOTE:PLEASE CORRELATE PLANS, PERMIT APPLICATION
 AND SUBMITTALS.
 PLEASE SEE PLANS INDICATE A DIESEL GEN, AND NATURAL GAS
 GEN. PLEASE SEE THE PERMIT APPLICATION INDICATES A
 DIESEL UNIT.
 PLEASE KNOW A DIESEL GENERATOR OR TANK FOR PROPANE WILL
 NOT BE PERMITTED ON THE ROOF TOP. PLEASE ALSO KNOW ANY
 SPECIAL PERMISSION FOR OTHER GENERATOR ON ROOF IS NOT
 APPROVED AT THIS TIME. PLEASE KNOW A CONFERENCE WITH
 THE FIRE MARSHAL AND PLAN REVIEW FOR POSSIBILITIES OF
 THE PERMITTING A NAT GAS GEN MUST BE HELD BEFORE
 PERMISSION WILL BE GRANTED. SHUT DOWN OF FUEL,
 GENERATOR, MOTOR AND SHUNT OF FEEDERS MAY ALL BE
 REQUIRED ON THE GROUND FLOOR OF BLDG.
 PLEASE KNOW AS MORE THAN ONE SIZE OF GEN AND TYPE FOR
 PRIME MOVER IS BEING SUBMITTED, A COMPLETE REVIEW CAN
 NOT BE DONE AT THIS TIME.
 PLEASE SEE NFPA-110 PLEASE SEE ALL OF CHAPTER 7. PLEASE
 KNOW, GAS FUEL LINE SHALL NOT BE GALVANIZED 7.9.3.1.
 PLEASE ALSO SEE 701.11(B)(3) FOR DUEL FUEL SUPPLIES
 REQUIRED. MAY NOT RELY ONLY ON THE UTILITY AND MUST
 SUPPLY *ON-SITE* FUEL SUPPLY.
  
 2) NOTE: PLEASE SEE THE VALUE AS SHOWN ON APPLICATION
 BASED ON THE SCOPE OF WORK IS EXTREMELY LOW AND A VALUE
 WILL BE ADJUSTED. THIS NEEDS TO INCLUDE ALL STRUCTURAL
 WORK, GAS/FUEL, TANKS ETC.
 **PLEASE KNOW, VALUE FOR COMPLETE SCOPE OF WORK SHALL
 INCLUDE ALL LABOR,
 MATERIALS, INSTALLATION OF GAS LINE/ TO ROOF TOP, GEN,
 ATS, STRUCTURAL WORK ETC.
 FBC 108.3
 THIS COMMENT HAS BEEN MADE ON EVERY OTHER PROJECT
 SUBMITTED FOR PERMIT IN THE CITY OF WEST PALM BEACH AND
 YET THE PERMIT APPLICATIONS ARE STILL BEING SUBMITTED
 WITH LOW VALUES.PLEASE KNOW THAT IF APPLICATIONS ARE
 RESUBMITTED WITHOUT AN APPROPRIATE VALUE BEING ASSESSED
 BY THE CONTRACTOR, THE PLANS MAY NOT BE ROUTED FOR PLAN
 REVIEW OR PROCESSING AND WILL BE PLACED OUT FOR PICK
 UP.
 PLEASE KNOW AS THIS A LEGAL DOCUMENT SIGNED BY THE
 CONTRACTOR LICENSED UNDER FS 468, THE APPLICATIONS ARE
 BEING RETAINED IN FILES FOR POSSIBLE REVIEW BY THE
 STATE CONTRACTORS LICENSING BOARD.
 PLEASE PLACE THE CORRECTED VALUES ON APPLICATIONS
 BEFORE PERMITS ARE APPLIED FOR AS STATED PREVIOUSLY.
  
  
 3) NOTE: PLEASE SEE THE CODE CITED ON PLANS FOR THE
 NFPA-70 SHOULD READ THE 2005. PLEASE KNOW THAT THE
 STATE OF FLORIDA ADOPTED THE 2005 NEC ON DECEMBER 8TH,
 2006.
 PLEASE ALSO STATE THE 2006 REVISIONS TO THE 2004 FBC
 WHICH ALSO CHANGED ON THAT DATE.
  
 4) NOTE: PLEASE KNOW DUE TO THE AMOUNT OF STRUCTURAL
 WORK IN SCOPE A GC WILL BE REQUIRED FOR THIS SCOPE AS
 IT IS NOT IN THE SCOPE OF AN ELECTRICAL CONTRACTOR.
 PLEASE KNOW THIS WORK IS STILL PENDING ON THE LOCATION
 OF THE GENERATOR AND WHETHER OR NOT THIS WILL BE
 LOCATED ON THE GROUND.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-30 18:53:212007-01-30 18:53:21
 NOTES TO FOLLOW.
 WILL BE IN *F* STATUS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-26 Cont ID  
Sent By mawillia Date 2007-02-26 Time 17:46 Rev Time 0.00
Received By mawillia Date 2007-02-26 Time 17:46 Sent To  
Notes
2007-02-26 17:56:23*****DENIED*****
  
  
 PLEASE SEE ELECTRICAL PLAN REVIEW COMMENTS
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
 OR FOR FURTHER CLARIFICATION CONTACT
  
 MIKE CARSILLO
 WPB FIRE MARSHAL
 561-804-4709
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-02-21 Cont ID  
Sent By kstevens Date 2007-02-21 Time 09:56 Rev Time 0.00
Received By kstevens Date 2007-02-21 Time 09:56 Sent To  
Notes
2007-02-21 09:57:23SUBMITTAL INDICATES DIESEL FUEL ONLY. NO GAS REVIEW
 REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-26 Cont ID  
Sent By mawillia Date 2007-02-26 Time 18:01 Rev Time 0.00
Received By mawillia Date 2007-01-18 Time 09:06 Sent To  
Notes
2007-01-30 09:26:16TO "COMM" BD#25
2007-01-18 09:06:36WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-22 Cont ID  
Sent By tgordon Date 2007-02-22 Time 08:20 Rev Time 0.30
Received By tgordon Date 2007-02-22 Time 08:20 Sent To  
Notes
2007-02-22 08:33:11*** DENIED ***
 1) PERMIT APPLICATION IS FOR A NATURAL GAS GENERATOR,
 AND THE MANUFACTURER'S SPECIFICATIONS SUBMITTED ARE FOR
 A DIESEL GENERATOR, PLEASE CORRECT.
  
 2) SEE ELECTRICAL REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-02 Cont ID  
Sent By jbabcock Date 2007-02-02 Time 16:05 Rev Time 0.00
Received By jbabcock Date 2007-02-02 Time 16:04 Sent To I
Notes
2007-02-02 16:05:061. PROVIDE FULL SIZE SITE PLANS, A SIGNED AND SEALED
 SURVEY, LANDSCAPE DETAILS, AND AN ELEVATION DETAIL (OF
 THE SCREENING REQUIREMENT)IN ORDER TO ILLUSTRATE
 COMPLIANCE WITH THE FOLLOWING STANDARDS:
  
 SECTION 94-305 (4) MECHANICAL EQUIPMENT. MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN FOUR FEET INTO A
 SETBACK. WINDOW AIR-CONDITIONING UNITS MAY NOT PROJECT
 MORE THAN 18 INCHES INTO A REQUIRED SIDE SETBACK.
  
 SECTION 94-444 (B) STATES THAT ALL MECHANICAL EQUIPMENT
 SHALL BE SCREENED.
  
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS.