Plan Review Details - Permit 07010758
Plan Review Stops For Permit 07010758
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-23 Cont ID  
Sent By rmcdouga Date 2007-02-23 Time 13:47 Rev Time 0.00
Received By rmcdouga Date 2007-02-22 Time 18:57 Sent To  
Notes
2007-02-23 13:47:02DENIED BY BUILDING
  
 1) PLANS ARE REQUIRED TO HAVE THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THEM. FBC* 106.
  
 2) FBC * 106.1.1 REQUIRES CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 3) FBC * 106.1.3 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
  
 4) FBC R312 AND FBC CHAPTER 11 REQUIRES AT LEAST ONE
 BATHROOM, LOCATED WITH MAXIMUM POSSIBLE PRIVACY, WHERE
 BATHROOMS ARE PROVIDED ON HABITABLE GRADE LEVELS, WITH
 A DOOR THAT HAS A 29-INCH (737 MM) CLEAR OPENING.
 HOWEVER, IF ONLY A TOILET ROOM IS PROVIDED AT GRADE
 LEVEL, SUCH TOILET ROOMS SHALL HAVE A CLEAR OPENING OF
 NOT LESS THAN 29 INCHES (737 MM). NEW MASTER BATH IS
 REQUIRED TO COMPLY.
  
 5) PLANS NEED TO SPECIFY THE WINDOW TYPE (I.E. SINGLE
 HUNG, FIXED, ETC.), LOCATION OF EACH, ETC. AND WHICH
 ONES ARE BEING REPLACED.
  
 6) SPECIFY WHICH EXTERIOR DOORS ARE BEING REPLACED.
  
 7) PLANS NEED TO SPECIFY THE LOCATIONS WHERE THE
 DRYWALL IS BEING REPLACED. IF ALL THE WALLS AND CEILING
 DRYWALL IS BEING REPLACED SPECIFY THAT ON THE PLANS.
  
 8) PLANS NEED TO SPECIFY WHICH WALLS ARE NEW AND WHICH
 ARE EXISTING.
  
 9) PLANS NEED TO SPECIFY THE R-VALUE OF THE INSULATION
 AND THE LOCATIONS OF WHERE EACH TYPE IS BEING
 INSTALLED.
  
 10) ENERGY CALC. FORM SPECIFIES EXTERIOR MASONRY WALLS
 WITH R-11 INSULATION. TYPICALLY MASONRY WALLS ARE
 INSULATED WITH R-5. SPECIFY HOW THE EXTERIOR MASORY
 WALLS ARE BEING INSULATED TO ACHIEVE R-11.
  
 11) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE
 STORM PANELS. SPECIFY THE FASTENER TYPE AND SPACING,
 THE CONNECTION TYPE, THE EDGE DISTANCE, WIND PRESSURE,
 SEPARATION DISTANCE, SPANS, ETC. CIRCLE THE APPROPRIATE
 ITEMS ON THE NOA AND FILL OUT ATTACHED INSTALLATION
 SCHEDULE OR PROVIDE ONE OF YOUR OWN
  
 12) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL WINDOW
 MULLIONS.
  
  
 13) ON THE PRODUCT APPROVAL FOR THE GAF MODIFIED ROOF
 SYSTEM INDICATE WHICH ONE OF THE APPROVED SYSTEMS WILL
 BE INSTALLED. SEE PAGES 9-31 OF NOA. INDICATE THE
 FASTENING OPTION AND DESIGN PRESSURE THAT WILL BE USED
 TO INSTALL THE SYSTEM. IF ENHANCED FASTENING IS
 REQUIRED TO INCREASE THE DESIGN PRESSURES AT THE
 PERIMETER AND CORNER AREAS, SUBMIT RAS 117 CALCULATIONS
 AS REQUIRED BY LIMITATION #7. SEE PAGE 32.
  
 14) THE FL COVER SHEET SUBMITTED FOR THE GAF MODIFIED
 ROOF SYSTEM IS NOT THE CORRECT ONE. THE CORRECT ONE IS
 FL 617-R1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-31 Cont ID  
Sent By btrobaug Date 2007-01-31 Time 09:18 Rev Time 0.50
Received By btrobaug Date 2007-01-31 Time 07:22 Sent To P
Notes
2007-01-31 08:00:45 
  
  
 NONCOMPLIANT
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC AS
 AMENDED. THIS ARTICLE ALSO IS AN EXTRACTION FROM THE
 EXEMPTION IN CHAPTER 471 OF THE FLORIDA STATUTES ,
 471.003, ALLOWING THE CONTRACTOR TO DRAW THEIR OWN
 PLANS. THE EXEMPTION INDICATES THE CONTRACTOR THAT IS
 INSTALLING THE WORK IS THE ONE COVERED UNDER THE
 EXEMPTION, 471.003(H).IN THE CASE OF THE ELECTRICAL
 PLANS , PLEASE HAVE THAT CONTRACTOR SUBMIT PLANS.
  
 2} IT IS UNCLEAR IF THE SERVICE IS BEING REPLACED,
 UPGRADED OR EXISTING. IF NEW, PLEASE SUBMI TA RISER
 DIAGRAM PER 215.5 AND PROVIDE AIC RATINGS FOR SAME PER
 110.9 & 10.
  
 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE.
  
 4} THE ELECTRICALPANEL LOCATED IN THE KITCHEN MUST
 COMPLY WITH THE CLEARANCE REQUUIREMENTS OF 110.26, THAT
 INCLUDES THE PROXIMETY TO THE COUNTER.
  
 5} PER 210.8(A)(6) ALL COUNTERTOP RECEPTACLES IN THE
 KITCHEN MUST BE GFCI PROTECTED.
  
 6} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-23 Cont ID  
Sent By rmcdouga Date 2007-02-23 Time 13:47 Rev Time 0.00
Received By rmcdouga Date 2007-01-20 Time 12:07 Sent To  
Notes
2007-01-20 12:09:26TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By tgordon Date 2007-02-06 Time 14:01 Rev Time 0.25
Received By tgordon Date 2007-02-06 Time 14:01 Sent To B
Notes
2007-02-06 14:07:15*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW.
 PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC
 WPB AMEND. 106.3.5.4 (10).AS MECHANICAL PERMIT NUMBER
 07010782 HAS BEEN APPLIED FOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-03 Cont ID  
Sent By jleech Date 2007-02-03 Time 10:09 Rev Time 0.00
Received By jleech Date 2007-02-03 Time 10:09 Sent To M
Notes
2007-02-03 10:17:41DENIED;
 1.PERSON TAKING RESPONSIBILITY FOR PLANS MUST SIGN AND
 PRINT NAME ON SAME. SEC.106.3.4.2.
 2. SANITARY RISER DIAGRAM REQUIRED. MUST SHOW ALL NEW
 WORK TO BE INSTALLED. SIZE ALL PIPES, SHOW VENTS AND
 WERE THEY TERMINATE, AND HOW NEW WORK TIRS INTO
 EXISTING BUILDING SEWER .
 3. NOT ENOUGH INFORMATION; SHOW ALL THE PLUMBING WORK
 TO BE DONE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695