Plan Review Details - Permit 07010693
Plan Review Stops For Permit 07010693
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-18 Cont ID  
Sent By jgomez Date 2007-01-18 Time 08:33 Rev Time 0.50
Received By jgomez Date 2007-01-18 Time 08:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-12 Cont ID  
Sent By jgomez Date 2007-01-12 Time 07:55 Rev Time 0.00
Received By jgomez Date 2007-01-12 Time 07:36 Sent To  
Notes
2007-01-12 16:00:53BUILDING REVIEW CHECKLIST:
 1- NOA #01-0424.03 SUBMITTED EXPIRED ON 03/08/2006.
 NEED TO PROVIDE CURRENT PRODUCT APPROVAL.
  
 2- SELECTED SYSTEM ON PAGE 26 IS LIMITED BY GENERAL
 LIMITATION #9. IT CAN BE USED IN THIS AREA BECAUSE THE
 DESIGN PRESSURES OF -45PSF ARE TOO LOW FOR THE REQUIRED
 DESIGN PRESSURES AT PERIMETER AND CORNER AREAS. SEE
 TABLE 1609.2.1(2) OF FBC 2004. SELECT ANOTHER APPROVED
 ASSEMBLY.
  
 3- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #7, THEN, PROVIDE ALL CALCULATIONS AS
 REQUIRED BY THIS LIMITATION.IF NOA REQUIRES
 CALCULATIONS TO BE DONE BY ARCHITECT, ENGINEER OR
 REGISTERED ROOF CONSULTANT, THEN PROVIDE SUCH SIGNED
 AND SEALED CALCULATIONS.SEE GENERAL LIMITATIONS ON
 PAGE 35 OF NOA 01-0424.03.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712