Plan Review Details - Permit 07010687
Plan Review Stops For Permit 07010687
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 11:23 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 11:23 Sent To P
Notes
2007-02-01 11:24:14TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-22 Cont ID  
Sent By mperson Date 2007-01-22 Time 16:41 Rev Time 0.00
Received By mperson Date 2007-01-16 Time 15:08 Sent To  
Notes
2007-01-16 15:09:10TO "P" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-02-08 Cont ID  
Sent By mperson Date 2007-02-08 Time 08:57 Rev Time 0.33
Received By mperson Date 2007-02-08 Time 08:57 Sent To  
Notes
2007-02-08 09:06:29 
 ****************PROVISO****************
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 (C) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (D) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By mperson Date 2007-01-22 Time 16:13 Rev Time 0.55
Received By mperson Date 2007-01-22 Time 16:13 Sent To PC
Notes
2007-01-22 16:41:31DENIED
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1,
 CITY OF WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106 CONSTRUCTION
 DOCUMENTS: SANITARY ISOMETRIC DIAGRAMS SUBMITTED IN
 PENCIL ARE NOT ALLOWED, THEY MUST BE IN INK. PLEASE
 CORRECT AND RESUBMIT.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4: ON ALL
 FOUR SUBMITTED SHEETS NOT ALL PIPES AND FIXTURE TRAPS
 ARE SIZED AS REQUIRED. PLEASE CORRECT AND RESUBMIT.
  
 3. SHEET 1 OF 4, PER FBC-2004 PLUMBING, SECTION 406.3:
 PLEASE INDICATE THE STANPIPE FOR THE WASHING MACHINE
 AND CORRECT THE TRAP SIZE TO TWO INCH (2"). PLEASE
 CORRECT AND RESUBMIT.
  
 4. SHEET 2 OF 4, PER FBC-2004 909.1 WET VENT PERMITTED:
 ONLY BATHROOM GROUPS ON THE SAME FLOOR ARE PERMITTED TO
 BE VENTED BY A WET VENT. PLEASE CORRECT AND RESUBMIT.
  
 5. SHEET 4 OF 4, PER FBC-2004 PLUMBING SECTION 1002.3:
 "S" TRAP PROHIBITED ON SECOND FLOOR COTTAGE LAV. VENT
 REQUIRED PER FBC-2004 PLUMBING SECTION 901.2.1.
  
 6. SHEET 4 OF 4 THERE IS AN UNIDENTIFIED FIXTURE
 INDICATED THAT IS ALSO NOT SIZED. PLEASE CORRECT AND
 RESUBMIT.
  
 7. SHEET 4 OF 4 LAUNDRY: PER FBC-2004 PLUMBING SECTION
 908.3 CONNECTION AT DIFFERENT LEVELS. WHERE FIXTURE
 DRAINS CONNECT AT DIFFERENT LEVELS, THE VENT SHALL
 CONNECT AS A VERTICAL EXTENSION OF THE VERTICAL DRAIN.
 THE UPPER FIXTURE SHALL NOT BE A WATER CLOSET. PLEASE
 CORRECT AND RESUBMIT.
  
 8. SHEET 4 OF 4, PER FBC-2004 PLUMBING, SECTION 406.3:
 PLEASE INDICATE THE STANDPIPE FOR THE WASHING MACHINE
 AND CORRECT THE TRAP SIZE TO TWO INCH (2").
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721