| Plan Review Stops For Permit 07010601 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-03-29 |
Time |
07:20 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2007-03-29 |
Time |
07:20 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-03-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-03-06 |
Time |
11:12 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2007-03-06 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2007-03-06 11:13:18 | PERRMIT: 07010601 | | | ADD: 2247 PALM BCH LAKES # 206 | | | CONT: ANDREA CONSTRUCTION | | | TEL: (561)358-4797 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, | | | SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE | | | POSTING OF THE | | | NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE | | | THE | | | FIRST INSPECTION. | | | | | | 3) ARCHITECT ROGER MORSE, PLANS HAVE NOT BEEN DATED, | | | WHEN SIGNED AND SEALED. | | | 61G1-16.004 (4) TITLE BLOCK INFORMATION REQUIRED , THE | | | DATE THE PLANS ARE SIGNED AND SEALED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-01-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-01-22 |
Time |
07:45 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2007-01-22 |
Time |
07:26 |
Sent To |
|
|
| Notes |
| 2007-01-22 08:15:27 | BUILDING PLAN REVIEW | | | PERMIT: 07010601 | | | ADD: 2247 PALM BCH LAKES # 206 | | | CONT: ANDREA CONSTRUCTION | | | TEL: (561) 358-4797 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT | | | IS | | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | | RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING | | | OF THE NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE | | | BEFORE | | | THE FIRST INSPECTION. | | | | | | 3)EXAM ROOM# 1 & EXAM ROOM# 2: | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. FRONT APPROACH FIG. A. | | | MINIMUM MANEUVERING CLEARANCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARANCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 4) RESTROOM #1 THE DOOR SWINGS INTO | | | THE CLEAR FLOOR SPACE REQUIRED FOR THE LAVOTORY. | | | 11-4.22.2 | | | | | | 5) RESROOM# 1 PROVIDE THE FOLLOWING INFORMATION IN | | | REGARDS TO LAVATORIES: | | | 11-4.19.2 | | | HEIGHT AND CLEARANCES. | | | LAVATORIES SHALL BE MOUNTED WITH THE RIM OR COUNTER | | | SURFACE NO HIGHER THAN 34 INCHES (865 MM) ABOVE THE | | | FINISH FLOOR. PROVIDE A CLEARANCE OF AT LEAST 29 INCHES | | | (735 MM) ABOVE THE FINISH FLOOR TO THE BOTTOM OF THE | | | APRON. KNEE AND TOE CLEARANCE SHALL COMPLY WITH FIGURE | | | 11-31 . | | | | | | 6) RESTROOM# 1: | | | 11-4.19.3 CLEAR FLOOR SPACE. | | | A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY | | | 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE | | | PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD | | | APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR | | | OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM | | | OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE | | | FIGURE 11-32 ). | | | | | | 7) RESTROOM# 1: | | | 11-4.19.2 HEIGHT AND CLEARANCES. | | | LAVATORIES SHALL BE MOUNTED WITH THE RIM OR COUNTER | | | SURFACE NO HIGHER THAN 34 INCHES (865 MM) ABOVE THE | | | FINISH FLOOR. PROVIDE A CLEARANCE OF AT LEAST 29 INCHES | | | (735 MM) ABOVE THE FINISH FLOOR TO THE BOTTOM OF THE | | | APRON. KNEE AND TOE CLEARANCE SHALL COMPLY WITH FIGURE | | | 11-31 . | | | | | | 8) RESTROOM# 2: | | | 11-4.19.3 CLEAR FLOOR SPACE. (TURNING RADIUS) | | | A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY | | | 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE | | | PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD | | | APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR | | | OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM | | | OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE | | | FIGURE 11-32 ). | | | | | | 9) RESTROOM# 2: | | | 11-4.19.3 CLEAR FLOOR SPACE. | | | A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY | | | 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE | | | PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD | | | APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR | | | OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM | | | OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE | | | FIGURE 11-32 ). | | | | | | 10) RESTROOM# 2: | | | 11-4.19.2 HEIGHT AND CLEARANCES. | | | LAVATORIES SHALL BE MOUNTED WITH THE RIM OR COUNTER | | | SURFACE NO HIGHER THAN 34 INCHES (865 MM) ABOVE THE | | | FINISH FLOOR. PROVIDE A CLEARANCE OF AT LEAST 29 INCHES | | | (735 MM) ABOVE THE FINISH FLOOR TO THE BOTTOM OF THE | | | APRON. KNEE AND TOE CLEARANCE SHALL COMPLY WITH FIGURE | | | 11-31 . | | | | | | 11) BREAKROOM SINK: SINKS: | | | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | | BE MOUNTED WITH THE COUNTER NO HIGHER | | | THAN 34" ABOVE THE FINISH FLOOR. | | | 11-4.24.3 KNEE CLEARANCE THAT IS AT | | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | | SHALL BE PROVIDED UNDERNEATH SINKS. | | | 11-4.24.5 CLEAR FLOOR SPACE. | | | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES | | | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 | | | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD | | | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN | | | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 | | | INCHES (485 MM) UNDERNEATH THE SINK | | | | | | 12) PLEASE PROVIDE INFORMATIO TO THE RECEPTIONIST | | | COUNTER HEIGHT: | | | 11-7.2 SALES AND SERVICE COUNTERS, TELLER WINDOWS, | | | INFORMATION COUNTERS. | | | (1)IN DEPARTMENT STORES AND MISCELLANEOUS RETAIL | | | STORES WHERE COUNTERS HAVE CASH REGISTERS AND ARE | | | PROVIDED FOR SALES OR DISTRIBUTION OF GOODS OR SERVICES | | | TO THE PUBLIC, AT LEAST ONE OF EACH TYPE SHALL HAVE A | | | PORTION OF THE COUNTER WHICH IS AT LEAST 36 INCHES (915 | | | MM) IN LENGTH WITH A MAXIMUM HEIGHT OF 36 INCHES (915 | | | MM) ABOVE THE FINISH FLOOR. IT SHALL BE ON AN | | | ACCESSIBLE ROUTE COMPLYING WITH SECTION 11-4.3 . THE | | | ACCESSIBLE COUNTERS MUST BE DISPERSED THROUGHOUT THE | | | BUILDING OR FACILITY. IN ALTERATIONS WHERE IT IS | | | TECHNICALLY INFEASIBLE TO PROVIDE AN ACCESSIBLE | | | COUNTER, AN AUXILIARY COUNTER MEETING THESE | | | REQUIREMENTS MAY BE PROVIDED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-20 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-20 |
Time |
11:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-03-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-04 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-04 |
Time |
18:29 |
Sent To |
|
|
| Notes |
| 2007-03-04 18:33:40 | *** UNSAT*** | | | | | | | | | 1)NOTE:PLEASE KNOW TO QUALIFY UNDER "MANAGEMENT" | | | MUST HAVE "QUALIFIED PERSONNEL" AS DEFINED ON THE NEC | | | ART 100. | | | | | | 2) NOTE: PLEASE BE SURE TO STATE ALL MAXIMUM TIME FOR | | | OC TYPE DEVICES TO BE 30 MINS PER 13-415.1.ABC.1.1, NOT | | | STATED ON PLANS. | | | | | | 3) PLEASE SEE NO ENERGY CALCULATIONS/PERFORMANCE | | | CALCULATIONS, LIGHTING POWER DENSITIES SHOWN OR | | | SUBMITTED. | | | 13-415.1.AB.1.1, 13-415.2 | | | | | | ** PLEASE SEE THE PLANS WILL BE COMING BACK FOR OTHER | | | TRADES AS THE ARCHITECT DID NOT DATE PLANS AS REQUIRED | | | PER FS481.221 | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-01-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-15 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-15 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2007-01-15 08:22:52 | PLANS REMOVED FROM INCOMING FOR REVIEW, ROUTED BACK TO | | | INCOMING AWAITING SPACE ON THE BOB BOARD. | | 2007-01-15 08:22:42 | ** UNSAT ** | | | | | | 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON | | | PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. THIS IS | | | REQUIRED ON ARCH COVER SHEET AS WELL AS ON ELECTRICAL. | | | THE ELECTRICAL SHEET DOES CONTAIN SOME OF THESE | | | ALREADY, HOWEVER PLEASE SEE MISSING. | | | | | | PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER | | | DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE | | | RELEVANT. | | | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70 | | | (NEC). (THE 2005 NEC IS SHOWN) | | | 2002 NFPA-72 | | | 2003 NFPA-101. | | | | | | 2) NOTE: PLEASE SEE THE WATER HEATER SYMBOL WHICH | | | INDICATES A 60AMP MOLDED CASE SWITCH WHICH IS OK AS | | | 30AMP OCP IS SHOWN IN PANEL. PLEASE SUBMIT THE | | | MANUFACTURE?S SPECS/CUT SHEETS IF THIS IS A | | | INSTA-HOT/TANK-LESS WATER HEATER UNIT. IF A STORAGE | | | TYPE AS SHOWN ON PLUMBING PLANS THEN THE SPECS ARE NOTE | | | REQUIRED FOR ELECTRICAL REVIEW. PLEASE SEE 422.17 FOR | | | MINIMUM CLEARANCES AS THIS UNIT IS SHOWN AS 30 GALS AND | | | DOES NOT SEEM THAT IS MAY FIT UNDER A SINK AS SHOWN. | | | PLEASE BE SURE THE LISTING FROM A NATIONALLY RECOGNIZED | | | TESTING LABORATORY IS SHOWN. (NRTL). 110.3, 90.7 | | | | | | 3) NOTE: PLEASE BE SURE TO INDICATE ALL CIRCUITS ON | | | PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. | | | PLEASE LABEL ALL LOCATIONS ON PANELS WHICH CORRELATE TO | | | ROOMS/AREAS WHICH ARE BEING FED. THIS SHOULD BE MORE | | | SPECIFIC. IE; OFFICE 1 RECEPTS,INTAKE RECEPTS, | | | CONFERENCE RM ETC. | | | THIS CAN BE DONE AT THIS TIME OR IT WILL BE REQUIRED | | | BEFORE INSPECTION FOR FINAL. | | | 106.1.2, 106.3.5.1.2 | | | NEC 408.4, 310.16, 240.4 FOR VERIFICATION. | | | | | | 4) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR HORN, | | | STROBES AND/OR HORN STROBE DEVICES PER FBC 11-4.28.1, | | | .2 AND .3(4). | | | PLEASE SEE LOBBY AREA WHICH DOES NOT SEEM TO INDICATE A | | | DEVICE. 11-4.28.2 PLEASE SEE ANY OTHER LOCATIONS WHICH | | | MAY BE BROUGHT UP BY FIRE MARSHAL' REVIEW. | | | THE INSTALLATION OF ANY ADDITIONAL DEVICES TO THE | | | EXISTING FIRE ALARM SYSTEM WILL BE REQUIRED UNDER | | | SEPARATE PLANS, PERMIT, HOWEVER THESE REQUIRED LEVELS | | | ARE TO BE SHOWN ON BASE PLANS. | | | | | | 5) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER | | | 13-415.1.AB.1, PERFORMANCE CALCULATIONS PER 13-415.2. | | | THESE ARE REQUIRED TO BE SIGNED DATED AND SEALED BY THE | | | DESIGNER OF RECORD. | | | PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES | | | TO BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION | | | ON PLANS. PLEASE BE SURE TO CORRELATE WITH THE | | | PERFORMANCE CALCULATIONS AND ENERGY CALCULATIONS. | | | PLEASE SEE THE 2006 REVISIONS TO THE 2004 FBC CHAPTER | | | 13. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | PLEASE SUBMIT AUTOMATED LIGHTING CONTROL METHODS, | | | SCHEDULING, DEVICES AND TYPES OF DEVICES. | | | PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE | | | DEVICES. (30 MINS FOR OCCUPANCY TYPE AND 4HRS MAX FOR | | | TIMER TYPE. THE TIMES ARE NOTED, HOWEVER ANY NEW | | | DEVICES IF TYPICAL THEN WOULD CONTAIN THE SAME | | | IDENTIFICATION. | | | PLEASE KNOW THAT MOST ARE SHOWN; HOWEVER PLEASE SEE | | | MISSING AT ENTRANCE INTO SPACE. | | | PLEASE PROVIDE A DETAIL FOR THE CIRCUITING THE | | | EMERGENCY AND EXIT LIGHTS. (THERE IS A NOTE ON PLANS, | | | HOWEVER SUBMIT DETAIL AS NUMEROUS SITUATIONS IN THE | | | JURISDICTION HAS HAD THESE FIXTURES BEING WIRED ON THE | | | LOAD SIDE OF THESE DEVICES. | | | PLEASE KNOW AS NO INFORMATION WAS SUBMITTED FOR REVIEW, | | | A COMPLETE REVIEW FOR COMPLIANCE CAN NOT BE DONE AT | | | THIS TIME. | | | | | | | | | 6) NOTE: PLEASE CLARIFY THE LOCATIONS O THE PANELS AS | | | NOTED. PLEASE ALSO CLARIFY WHERE PANEL COVER MENTIONS | | | THE COVERS ARE NOT LOCKABLE? | | | PLEASE PROVIDE INFORMATION ON PLANS WHETHER BUILDING IS | | | UNDER MANAGEMENT OF QUALIFIED PERSONNEL. | | | 240.24, (A), (B), (C). | | | | | | | | | 7) NOTE: PLEASE CLARIFY IN SERVICE CALCULATIONS ARE | | | SHOWN AT 125% FOR CONTINUOUS LOADS. | | | 215.3, 230.42 ETC. | | | 220.12, 220.14, 220.43, 220.44 ETC. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-03-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-22 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-22 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2007-03-22 11:40:37 | *****APPROVED***** | | | | | | ALL PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN | | | ADDRESSED;PLAN SHEETS A-102 AND E-101 WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | | | | | | | PLEASE BE ADVISED THAT AT THE TIME OF FIRE INSPECTION | | | FOR BUSINESS TAX SIGNOFF BY WEST PALM BEACH FIRE | | | PREVENTION BUREAU, A FIRE EXTINGUISHER SHALL BE | | | REQUIRED IN THE TENANT SPACE. | | | | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-03-13 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-13 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-13 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2007-03-13 12:21:17 | *****UNSAT***** | | | | | | COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE BEEN | | | SATISFIED WITH THE EXCEPTION OF THE FOLLOWING WHICH | | | STILL NEED TO BE ADDRESSED: | | | | | | | | | 01.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE, | | | SHALL BE REFERENCED.ON SHEET A-001 UNDER CODE | | | CLASSIFICATION,ADD "NFPA 101 2003 EDITION" | | | | | | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ON | | | SHEET A-001 UNDER CODE CLASSIFICATION, ADD "NFPA 241" | | | | | | 08.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR | | | WALL AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, | | | AND IN ALL OTHER AREAS.AS PER NFPA 101: 38.3.3.1 - | | | INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE | | | CLASS A OR B IN EXITS AND EXIT ACCESS CORRIDORS AND | | | SHALL BE CLASS A, B, OR C IN ALL OTHER AREAS.PLEASE | | | SPECIFY | | | | | | 09.INDICATE THE LOCATION OF THE 2A:10BC FIRE | | | EXTINGUISHER WHICH SATIFIES THE 75' TRAVEL DISTANCE | | | REQUIREMENT.PLEASE BE ADVISED THAT AT THE TIME OF | | | FIRE INSPECTION FOR BUSINESS TAX SIGNOFF BY WEST PALM | | | BEACH FIRE PREVENTION BUREAU, A FIRE EXTINGUISHER WILL | | | BE LOCATED IN THE TENANT SPACE. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE (ON THE | | | PLAN) EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-01-24 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-24 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2007-01-24 16:56:29 | *****DENIED***** | | | | | | | | | 01.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE, | | | SHALL BE REFERENCED. | | | | | | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. | | | | | | 04.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INERFERE OR | | | HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE. | | | | | | 05.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR | | | THIS TENANT SPACE. | | | | | | 06.FIRE ALARM STROBE NEEDED IN THE CONFERENCE ROOM. | | | | | | 07.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM IS | | | MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE SHOP | | | DRAWINGS/PLANS AND PERMIT WILL BE REQUIRED. | | | | | | 08.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR | | | WALL AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, | | | AND IN ALL OTHER AREAS. | | | | | | 09.INDICATE THE LOCATION OF THE 2A:10BC FIRE | | | EXTINGUISHER WHICH SATIFIES THE 75' TRAVEL DISTANCE | | | REQUIREMENT. | | | | | | 10.PROVIDE THE TRAVEL DISTANCE TO THE EXIT MEASURED | | | ON THE FLOOR OR OTHER WALKING SURFACE AS PER NFPA 101, | | | 7.6 | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-04-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-25 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-25 |
Time |
09:30 |
Sent To |
M |
|
| Notes |
| 2007-04-25 09:31:02 | TO "M"BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-04-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-13 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-13 |
Time |
16:13 |
Sent To |
M |
|
| Notes |
| 2007-04-13 16:14:03 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-04-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-09 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-09 |
Time |
13:31 |
Sent To |
M |
|
| Notes |
| 2007-04-09 13:32:12 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-03-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-20 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-20 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2007-03-20 09:44:26 | TO "BOB"#5 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-02 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-02 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2007-03-02 09:16:56 | TO "BOB"#12 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-01-24 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-10 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2007-01-17 08:55:30 | TO "BOB"#9 | | 2007-01-10 10:59:53 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-04-26 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-04-26 |
Time |
09:02 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-04-26 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2007-04-26 09:03:26 | REVISION TO MECH. PLANS PAGE M-101. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-04-16 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-04-16 |
Time |
11:11 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-04-16 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2007-04-16 11:12:48 | REVISION TO MECH. PLANS PAGE M-101. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-04-10 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-04-10 |
Time |
09:23 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-04-10 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2007-04-10 09:36:18 | REVISION TO MECHANICAL PLANS PAGE M-101 | | | *** DENIED *** | | | 1) ROBERT F. PETERSON IS NOT THE ENGINEER WHO SEALED | | | THE ORIGINAL MECHANICAL PLANS, BRUCE E. MILLER WAS SO | | | ONLY HE MAY MAKE REVISION TO THEM OR HE MAY SUBMIT A | | | LETTER REMOVING HIMSELF FROM THE PROJECT OR STATING HE | | | IS WITH THE ENGINEERING BUSINESS DYANKI INC.. | | | | | | 2) INFORMATION MISSING FROM TITLE BLOCK, ENGINEER'S | | | ADDRESS. | | | SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET | | | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE | | | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND | | | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS | | | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. | | | | | | 3) AN ENGINEERING CERTIFICATE #0000 9666 (FL) IS IN THE | | | TITLE BLOCK, SEE FAC 61G15-23.002 (2) REGARDING | | | ENGINEERING BUSINESS'S INFORMATION IN TITLE BLOCK, | | | PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2007-01-17 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-01-17 |
Time |
11:09 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-01-17 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-03-26 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-03-26 |
Time |
07:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-03-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-03-10 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-03-10 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2007-03-10 11:23:18 | DENIED; | | | | | | 1. ( NOT ADDRESSED LAST REVIEW) HANDICAP CODE SECTION | | | 11-4.1.3(11), IF BATHROOMS ARE INSTALLED THEN THEY WILL | | | BE ACCESSABLE. PLEASE SHOW DIMENSIONS OF BATHROOMS, | | | TURNING RADIUS AND CLEAR FOR SPACE. DETAIL REQUIRED | | | COMPLY WITH SECTIONS11-4.22.1 THRU 11-4.22.7. | | | 2. PAGE P-001 WATER HEATER DETAIL; SHOW TERMINATION | | | POINT FOR RELIEF AND PAN DRAIN LINES PER SECTIONS | | | 504.6.1RELIEF AND 504.7.2 PAN DRAIN. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-01-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-01-20 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-01-20 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2007-01-20 11:40:44 | DENIED; | | | 1. FBC-2004 BUILDING CHAPTER 11 SECTION 11-4.1.3(11) | | | TOILET FACILITIES, TOILET ROOMS SHALL BE ACCESSIBLE SEE | | | SECTIONS 11-4.22.1 THRU 11-4.22.7. SHOW DETAIL ON PLANS | | | WITH ALL REQUIRED MEASUREMENTS. | | | 2. FBC PLUMBING TABLE 403.1 MINIMUM PLUMBING | | | FIXTURES(2B) REQUIRES A DRINKING FOUNTAIN THATMUST | | | COMPLY WITH HANDICAP CODE SECTION 11-4.1.3(10) AND | | | SECTIONS 11-4.15.1 THRU 11-4.15.5. SHOW DETAIL ON | | | PLANS. | | | 3.BREAKSINK TO COMPLY WITH 11-4.24.1 THRU 11-4.24.7 | | | SHOW DETAIL ON PLANS. | | | 4. SHOW CLEAR FLOOR SPACE AND TURNING RADIUS ON FLOOR | | | PLAN. | | | 5. WATER ISOMETRIC; IF DISHWASHER OR ICE MAKER ARE | | | INSTALLED WATER HAMMER ARRESTORS ARE REQUIRED PER | | | SECTION 604.9. SHOW ON DIAGRAM AND LIST TYPE ON PLANS. | | | 6.THERMAL EXPANTION CONTROL IS REQUIRED ON WATER HEATER | | | PER SECTION 607.3. | | | 7.SHOW A DETAIL OF WATER HEATER THAT SHOWS A HEATER | | | PAN, DRAIN AND TERMINATION OF HEATER PLAN DRAIN PER. | | | SECTIONS 504.6.2, 504.7.1 AND 504.7.2. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|