Plan Review Details - Permit 07010601
Plan Review Stops For Permit 07010601
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-29 Cont ID  
Sent By jwitmer Date 2007-03-29 Time 07:20 Rev Time 0.33
Received By jwitmer Date 2007-03-29 Time 07:20 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-06 Cont ID  
Sent By jwitmer Date 2007-03-06 Time 11:12 Rev Time 0.55
Received By jwitmer Date 2007-03-06 Time 11:12 Sent To  
Notes
2007-03-06 11:13:18PERRMIT: 07010601
 ADD: 2247 PALM BCH LAKES # 206
 CONT: ANDREA CONSTRUCTION
 TEL: (561)358-4797
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE
 POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE
 FIRST INSPECTION.
  
 3) ARCHITECT ROGER MORSE, PLANS HAVE NOT BEEN DATED,
 WHEN SIGNED AND SEALED.
 61G1-16.004 (4) TITLE BLOCK INFORMATION REQUIRED , THE
 DATE THE PLANS ARE SIGNED AND SEALED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By jwitmer Date 2007-01-22 Time 07:45 Rev Time 1.22
Received By jwitmer Date 2007-01-22 Time 07:26 Sent To  
Notes
2007-01-22 08:15:27BUILDING PLAN REVIEW
 PERMIT: 07010601
 ADD: 2247 PALM BCH LAKES # 206
 CONT: ANDREA CONSTRUCTION
 TEL: (561) 358-4797
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT
 IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING
 OF THE NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE
 BEFORE
 THE FIRST INSPECTION.
  
 3)EXAM ROOM# 1 & EXAM ROOM# 2:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. FRONT APPROACH FIG. A.
 MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 4) RESTROOM #1 THE DOOR SWINGS INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR THE LAVOTORY.
 11-4.22.2
  
 5) RESROOM# 1 PROVIDE THE FOLLOWING INFORMATION IN
 REGARDS TO LAVATORIES:
 11-4.19.2
 HEIGHT AND CLEARANCES.
 LAVATORIES SHALL BE MOUNTED WITH THE RIM OR COUNTER
 SURFACE NO HIGHER THAN 34 INCHES (865 MM) ABOVE THE
 FINISH FLOOR. PROVIDE A CLEARANCE OF AT LEAST 29 INCHES
 (735 MM) ABOVE THE FINISH FLOOR TO THE BOTTOM OF THE
 APRON. KNEE AND TOE CLEARANCE SHALL COMPLY WITH FIGURE
 11-31 .
  
 6) RESTROOM# 1:
 11-4.19.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR
 OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM
 OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 11-32 ).
  
 7) RESTROOM# 1:
 11-4.19.2 HEIGHT AND CLEARANCES.
 LAVATORIES SHALL BE MOUNTED WITH THE RIM OR COUNTER
 SURFACE NO HIGHER THAN 34 INCHES (865 MM) ABOVE THE
 FINISH FLOOR. PROVIDE A CLEARANCE OF AT LEAST 29 INCHES
 (735 MM) ABOVE THE FINISH FLOOR TO THE BOTTOM OF THE
 APRON. KNEE AND TOE CLEARANCE SHALL COMPLY WITH FIGURE
 11-31 .
  
 8) RESTROOM# 2:
 11-4.19.3 CLEAR FLOOR SPACE. (TURNING RADIUS)
 A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR
 OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM
 OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 11-32 ).
  
 9) RESTROOM# 2:
 11-4.19.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR
 OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM
 OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 11-32 ).
  
 10) RESTROOM# 2:
 11-4.19.2 HEIGHT AND CLEARANCES.
 LAVATORIES SHALL BE MOUNTED WITH THE RIM OR COUNTER
 SURFACE NO HIGHER THAN 34 INCHES (865 MM) ABOVE THE
 FINISH FLOOR. PROVIDE A CLEARANCE OF AT LEAST 29 INCHES
 (735 MM) ABOVE THE FINISH FLOOR TO THE BOTTOM OF THE
 APRON. KNEE AND TOE CLEARANCE SHALL COMPLY WITH FIGURE
 11-31 .
  
 11) BREAKROOM SINK: SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK
  
 12) PLEASE PROVIDE INFORMATIO TO THE RECEPTIONIST
 COUNTER HEIGHT:
 11-7.2 SALES AND SERVICE COUNTERS, TELLER WINDOWS,
 INFORMATION COUNTERS.
 (1)IN DEPARTMENT STORES AND MISCELLANEOUS RETAIL
 STORES WHERE COUNTERS HAVE CASH REGISTERS AND ARE
 PROVIDED FOR SALES OR DISTRIBUTION OF GOODS OR SERVICES
 TO THE PUBLIC, AT LEAST ONE OF EACH TYPE SHALL HAVE A
 PORTION OF THE COUNTER WHICH IS AT LEAST 36 INCHES (915
 MM) IN LENGTH WITH A MAXIMUM HEIGHT OF 36 INCHES (915
 MM) ABOVE THE FINISH FLOOR. IT SHALL BE ON AN
 ACCESSIBLE ROUTE COMPLYING WITH SECTION 11-4.3 . THE
 ACCESSIBLE COUNTERS MUST BE DISPERSED THROUGHOUT THE
 BUILDING OR FACILITY. IN ALTERATIONS WHERE IT IS
 TECHNICALLY INFEASIBLE TO PROVIDE AN ACCESSIBLE
 COUNTER, AN AUXILIARY COUNTER MEETING THESE
 REQUIREMENTS MAY BE PROVIDED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-03-26 Cont ID  
Sent By dpalmer Date 2007-03-20 Time 11:27 Rev Time 0.00
Received By dpalmer Date 2007-03-20 Time 11:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-04 Cont ID  
Sent By dpalmer Date 2007-03-04 Time 18:33 Rev Time 0.00
Received By dpalmer Date 2007-03-04 Time 18:29 Sent To  
Notes
2007-03-04 18:33:40*** UNSAT***
  
  
 1)NOTE:PLEASE KNOW TO QUALIFY UNDER "MANAGEMENT"
 MUST HAVE "QUALIFIED PERSONNEL" AS DEFINED ON THE NEC
 ART 100.
  
 2) NOTE: PLEASE BE SURE TO STATE ALL MAXIMUM TIME FOR
 OC TYPE DEVICES TO BE 30 MINS PER 13-415.1.ABC.1.1, NOT
 STATED ON PLANS.
  
 3) PLEASE SEE NO ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS, LIGHTING POWER DENSITIES SHOWN OR
 SUBMITTED.
 13-415.1.AB.1.1, 13-415.2
  
 ** PLEASE SEE THE PLANS WILL BE COMING BACK FOR OTHER
 TRADES AS THE ARCHITECT DID NOT DATE PLANS AS REQUIRED
 PER FS481.221
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-15 Cont ID  
Sent By dpalmer Date 2007-01-15 Time 08:21 Rev Time 0.00
Received By dpalmer Date 2007-01-15 Time 07:30 Sent To  
Notes
2007-01-15 08:22:52PLANS REMOVED FROM INCOMING FOR REVIEW, ROUTED BACK TO
 INCOMING AWAITING SPACE ON THE BOB BOARD.
2007-01-15 08:22:42** UNSAT **
  
 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON
 PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. THIS IS
 REQUIRED ON ARCH COVER SHEET AS WELL AS ON ELECTRICAL.
 THE ELECTRICAL SHEET DOES CONTAIN SOME OF THESE
 ALREADY, HOWEVER PLEASE SEE MISSING.
  
 PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER
 DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE
 RELEVANT.
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70
 (NEC). (THE 2005 NEC IS SHOWN)
 2002 NFPA-72
 2003 NFPA-101.
  
 2) NOTE: PLEASE SEE THE WATER HEATER SYMBOL WHICH
 INDICATES A 60AMP MOLDED CASE SWITCH WHICH IS OK AS
 30AMP OCP IS SHOWN IN PANEL. PLEASE SUBMIT THE
 MANUFACTURE?S SPECS/CUT SHEETS IF THIS IS A
 INSTA-HOT/TANK-LESS WATER HEATER UNIT. IF A STORAGE
 TYPE AS SHOWN ON PLUMBING PLANS THEN THE SPECS ARE NOTE
 REQUIRED FOR ELECTRICAL REVIEW. PLEASE SEE 422.17 FOR
 MINIMUM CLEARANCES AS THIS UNIT IS SHOWN AS 30 GALS AND
 DOES NOT SEEM THAT IS MAY FIT UNDER A SINK AS SHOWN.
 PLEASE BE SURE THE LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY IS SHOWN. (NRTL). 110.3, 90.7
  
 3) NOTE: PLEASE BE SURE TO INDICATE ALL CIRCUITS ON
 PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE.
 PLEASE LABEL ALL LOCATIONS ON PANELS WHICH CORRELATE TO
 ROOMS/AREAS WHICH ARE BEING FED. THIS SHOULD BE MORE
 SPECIFIC. IE; OFFICE 1 RECEPTS,INTAKE RECEPTS,
 CONFERENCE RM ETC.
 THIS CAN BE DONE AT THIS TIME OR IT WILL BE REQUIRED
 BEFORE INSPECTION FOR FINAL.
 106.1.2, 106.3.5.1.2
 NEC 408.4, 310.16, 240.4 FOR VERIFICATION.
  
 4) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR HORN,
 STROBES AND/OR HORN STROBE DEVICES PER FBC 11-4.28.1,
 .2 AND .3(4).
 PLEASE SEE LOBBY AREA WHICH DOES NOT SEEM TO INDICATE A
 DEVICE. 11-4.28.2 PLEASE SEE ANY OTHER LOCATIONS WHICH
 MAY BE BROUGHT UP BY FIRE MARSHAL' REVIEW.
 THE INSTALLATION OF ANY ADDITIONAL DEVICES TO THE
 EXISTING FIRE ALARM SYSTEM WILL BE REQUIRED UNDER
 SEPARATE PLANS, PERMIT, HOWEVER THESE REQUIRED LEVELS
 ARE TO BE SHOWN ON BASE PLANS.
  
 5) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER
 13-415.1.AB.1, PERFORMANCE CALCULATIONS PER 13-415.2.
 THESE ARE REQUIRED TO BE SIGNED DATED AND SEALED BY THE
 DESIGNER OF RECORD.
 PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES
 TO BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION
 ON PLANS. PLEASE BE SURE TO CORRELATE WITH THE
 PERFORMANCE CALCULATIONS AND ENERGY CALCULATIONS.
 PLEASE SEE THE 2006 REVISIONS TO THE 2004 FBC CHAPTER
 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SUBMIT AUTOMATED LIGHTING CONTROL METHODS,
 SCHEDULING, DEVICES AND TYPES OF DEVICES.
 PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE
 DEVICES. (30 MINS FOR OCCUPANCY TYPE AND 4HRS MAX FOR
 TIMER TYPE. THE TIMES ARE NOTED, HOWEVER ANY NEW
 DEVICES IF TYPICAL THEN WOULD CONTAIN THE SAME
 IDENTIFICATION.
 PLEASE KNOW THAT MOST ARE SHOWN; HOWEVER PLEASE SEE
 MISSING AT ENTRANCE INTO SPACE.
 PLEASE PROVIDE A DETAIL FOR THE CIRCUITING THE
 EMERGENCY AND EXIT LIGHTS. (THERE IS A NOTE ON PLANS,
 HOWEVER SUBMIT DETAIL AS NUMEROUS SITUATIONS IN THE
 JURISDICTION HAS HAD THESE FIXTURES BEING WIRED ON THE
 LOAD SIDE OF THESE DEVICES.
 PLEASE KNOW AS NO INFORMATION WAS SUBMITTED FOR REVIEW,
 A COMPLETE REVIEW FOR COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
  
  
 6) NOTE: PLEASE CLARIFY THE LOCATIONS O THE PANELS AS
 NOTED. PLEASE ALSO CLARIFY WHERE PANEL COVER MENTIONS
 THE COVERS ARE NOT LOCKABLE?
 PLEASE PROVIDE INFORMATION ON PLANS WHETHER BUILDING IS
 UNDER MANAGEMENT OF QUALIFIED PERSONNEL.
 240.24, (A), (B), (C).
  
  
 7) NOTE: PLEASE CLARIFY IN SERVICE CALCULATIONS ARE
 SHOWN AT 125% FOR CONTINUOUS LOADS.
 215.3, 230.42 ETC.
 220.12, 220.14, 220.43, 220.44 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-03-22 Cont ID  
Sent By mawillia Date 2007-03-22 Time 11:55 Rev Time 0.00
Received By mawillia Date 2007-03-22 Time 11:31 Sent To  
Notes
2007-03-22 11:40:37*****APPROVED*****
  
 ALL PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED;PLAN SHEETS A-102 AND E-101 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
  
 PLEASE BE ADVISED THAT AT THE TIME OF FIRE INSPECTION
 FOR BUSINESS TAX SIGNOFF BY WEST PALM BEACH FIRE
 PREVENTION BUREAU, A FIRE EXTINGUISHER SHALL BE
 REQUIRED IN THE TENANT SPACE.
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-03-13 Cont ID  
Sent By mawillia Date 2007-03-13 Time 12:21 Rev Time 0.00
Received By mawillia Date 2007-03-13 Time 11:12 Sent To  
Notes
2007-03-13 12:21:17*****UNSAT*****
  
 COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE BEEN
 SATISFIED WITH THE EXCEPTION OF THE FOLLOWING WHICH
 STILL NEED TO BE ADDRESSED:
  
  
 01.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE,
 SHALL BE REFERENCED.ON SHEET A-001 UNDER CODE
 CLASSIFICATION,ADD "NFPA 101 2003 EDITION"
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ON
 SHEET A-001 UNDER CODE CLASSIFICATION, ADD "NFPA 241"
  
 08.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR
 WALL AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS.AS PER NFPA 101: 38.3.3.1 -
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR B IN EXITS AND EXIT ACCESS CORRIDORS AND
 SHALL BE CLASS A, B, OR C IN ALL OTHER AREAS.PLEASE
 SPECIFY
  
 09.INDICATE THE LOCATION OF THE 2A:10BC FIRE
 EXTINGUISHER WHICH SATIFIES THE 75' TRAVEL DISTANCE
 REQUIREMENT.PLEASE BE ADVISED THAT AT THE TIME OF
 FIRE INSPECTION FOR BUSINESS TAX SIGNOFF BY WEST PALM
 BEACH FIRE PREVENTION BUREAU, A FIRE EXTINGUISHER WILL
 BE LOCATED IN THE TENANT SPACE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE (ON THE
 PLAN) EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-24 Cont ID  
Sent By mawillia Date 2007-01-24 Time 16:33 Rev Time 0.00
Received By mawillia Date 2007-01-24 Time 16:18 Sent To  
Notes
2007-01-24 16:56:29*****DENIED*****
  
  
 01.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE,
 SHALL BE REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 04.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INERFERE OR
 HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE.
  
 05.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR
 THIS TENANT SPACE.
  
 06.FIRE ALARM STROBE NEEDED IN THE CONFERENCE ROOM.
  
 07.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM IS
 MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE SHOP
 DRAWINGS/PLANS AND PERMIT WILL BE REQUIRED.
  
 08.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR
 WALL AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS.
  
 09.INDICATE THE LOCATION OF THE 2A:10BC FIRE
 EXTINGUISHER WHICH SATIFIES THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 10.PROVIDE THE TRAVEL DISTANCE TO THE EXIT MEASURED
 ON THE FLOOR OR OTHER WALKING SURFACE AS PER NFPA 101,
 7.6
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-25 Cont ID  
Sent By adarroug Date 2007-04-25 Time 09:30 Rev Time 0.00
Received By adarroug Date 2007-04-25 Time 09:30 Sent To M
Notes
2007-04-25 09:31:02TO "M"BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-13 Cont ID  
Sent By adarroug Date 2007-04-13 Time 16:13 Rev Time 0.00
Received By adarroug Date 2007-04-13 Time 16:13 Sent To M
Notes
2007-04-13 16:14:03TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-09 Cont ID  
Sent By adarroug Date 2007-04-09 Time 13:31 Rev Time 0.00
Received By adarroug Date 2007-04-09 Time 13:31 Sent To M
Notes
2007-04-09 13:32:12TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-20 Cont ID  
Sent By adarroug Date 2007-03-20 Time 09:44 Rev Time 0.00
Received By adarroug Date 2007-03-20 Time 09:41 Sent To  
Notes
2007-03-20 09:44:26TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-02 Cont ID  
Sent By adarroug Date 2007-03-02 Time 09:16 Rev Time 0.00
Received By adarroug Date 2007-03-02 Time 09:16 Sent To  
Notes
2007-03-02 09:16:56TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-24 Cont ID  
Sent By mawillia Date 2007-01-24 Time 16:17 Rev Time 0.00
Received By mawillia Date 2007-01-10 Time 10:56 Sent To  
Notes
2007-01-17 08:55:30TO "BOB"#9
2007-01-10 10:59:53WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-04-26 Cont ID  
Sent By tgordon Date 2007-04-26 Time 09:02 Rev Time 0.25
Received By tgordon Date 2007-04-26 Time 09:02 Sent To  
Notes
2007-04-26 09:03:26REVISION TO MECH. PLANS PAGE M-101.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-04-16 Cont ID  
Sent By tgordon Date 2007-04-16 Time 11:11 Rev Time 0.20
Received By tgordon Date 2007-04-16 Time 11:11 Sent To  
Notes
2007-04-16 11:12:48REVISION TO MECH. PLANS PAGE M-101.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-04-10 Cont ID  
Sent By tgordon Date 2007-04-10 Time 09:23 Rev Time 0.30
Received By tgordon Date 2007-04-10 Time 09:23 Sent To  
Notes
2007-04-10 09:36:18REVISION TO MECHANICAL PLANS PAGE M-101
 *** DENIED ***
 1) ROBERT F. PETERSON IS NOT THE ENGINEER WHO SEALED
 THE ORIGINAL MECHANICAL PLANS, BRUCE E. MILLER WAS SO
 ONLY HE MAY MAKE REVISION TO THEM OR HE MAY SUBMIT A
 LETTER REMOVING HIMSELF FROM THE PROJECT OR STATING HE
 IS WITH THE ENGINEERING BUSINESS DYANKI INC..
  
 2) INFORMATION MISSING FROM TITLE BLOCK, ENGINEER'S
 ADDRESS.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 3) AN ENGINEERING CERTIFICATE #0000 9666 (FL) IS IN THE
 TITLE BLOCK, SEE FAC 61G15-23.002 (2) REGARDING
 ENGINEERING BUSINESS'S INFORMATION IN TITLE BLOCK,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-01-17 Cont ID  
Sent By tgordon Date 2007-01-17 Time 11:09 Rev Time 0.30
Received By tgordon Date 2007-01-17 Time 11:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-03-26 Cont ID  
Sent By jleech Date 2007-03-26 Time 07:33 Rev Time 0.00
Received By jleech Date 2007-03-26 Time 07:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-10 Cont ID  
Sent By jleech Date 2007-03-10 Time 11:01 Rev Time 0.00
Received By jleech Date 2007-03-10 Time 11:01 Sent To  
Notes
2007-03-10 11:23:18DENIED;
  
 1. ( NOT ADDRESSED LAST REVIEW) HANDICAP CODE SECTION
 11-4.1.3(11), IF BATHROOMS ARE INSTALLED THEN THEY WILL
 BE ACCESSABLE. PLEASE SHOW DIMENSIONS OF BATHROOMS,
 TURNING RADIUS AND CLEAR FOR SPACE. DETAIL REQUIRED
 COMPLY WITH SECTIONS11-4.22.1 THRU 11-4.22.7.
 2. PAGE P-001 WATER HEATER DETAIL; SHOW TERMINATION
 POINT FOR RELIEF AND PAN DRAIN LINES PER SECTIONS
 504.6.1RELIEF AND 504.7.2 PAN DRAIN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-20 Cont ID  
Sent By jleech Date 2007-01-20 Time 11:18 Rev Time 0.00
Received By jleech Date 2007-01-20 Time 11:18 Sent To  
Notes
2007-01-20 11:40:44DENIED;
 1. FBC-2004 BUILDING CHAPTER 11 SECTION 11-4.1.3(11)
 TOILET FACILITIES, TOILET ROOMS SHALL BE ACCESSIBLE SEE
 SECTIONS 11-4.22.1 THRU 11-4.22.7. SHOW DETAIL ON PLANS
 WITH ALL REQUIRED MEASUREMENTS.
 2. FBC PLUMBING TABLE 403.1 MINIMUM PLUMBING
 FIXTURES(2B) REQUIRES A DRINKING FOUNTAIN THATMUST
 COMPLY WITH HANDICAP CODE SECTION 11-4.1.3(10) AND
 SECTIONS 11-4.15.1 THRU 11-4.15.5. SHOW DETAIL ON
 PLANS.
 3.BREAKSINK TO COMPLY WITH 11-4.24.1 THRU 11-4.24.7
 SHOW DETAIL ON PLANS.
 4. SHOW CLEAR FLOOR SPACE AND TURNING RADIUS ON FLOOR
 PLAN.
 5. WATER ISOMETRIC; IF DISHWASHER OR ICE MAKER ARE
 INSTALLED WATER HAMMER ARRESTORS ARE REQUIRED PER
 SECTION 604.9. SHOW ON DIAGRAM AND LIST TYPE ON PLANS.
 6.THERMAL EXPANTION CONTROL IS REQUIRED ON WATER HEATER
 PER SECTION 607.3.
 7.SHOW A DETAIL OF WATER HEATER THAT SHOWS A HEATER
 PAN, DRAIN AND TERMINATION OF HEATER PLAN DRAIN PER.
 SECTIONS 504.6.2, 504.7.1 AND 504.7.2.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved