Plan Review Details - Permit 07010583
Plan Review Stops For Permit 07010583
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-02-12 Cont ID  
Sent By btrobaug Date 2007-02-12 Time 16:05 Rev Time 0.50
Received By btrobaug Date 2007-02-12 Time 15:56 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-16 Cont ID  
Sent By btrobaug Date 2007-01-16 Time 08:03 Rev Time 0.33
Received By btrobaug Date 2007-01-16 Time 07:46 Sent To I
Notes
2007-01-16 08:02:05 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66. SHOW GEC SYSTEM ON THE PLAN.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-06 Cont ID  
Sent By adarroug Date 2007-02-06 Time 08:59 Rev Time 0.00
Received By adarroug Date 2007-02-06 Time 08:58 Sent To E
Notes
2007-02-06 08:59:18TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-16 Cont ID  
Sent By btrobaug Date 2007-01-16 Time 08:03 Rev Time 0.00
Received By btrobaug Date 2007-01-12 Time 10:15 Sent To PC
Notes
2007-01-12 10:15:58TO "E" BOX