Plan Review Details - Permit 07010580
Plan Review Stops For Permit 07010580
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-19 Cont ID  
Sent By rmcdouga Date 2007-06-19 Time 14:45 Rev Time 0.00
Received By rmcdouga Date 2007-06-19 Time 14:45 Sent To  
Notes
2007-06-19 15:21:151) BUILDING REVIEW STATUS IS FAILED,UNTIL THE
 HISTORIC PRESERVATION ISSUES ARE ADDRESSED.
  
 2) THE NOC HAS EXPIRED AND WILL NEED TO BE RERECORDED
 BEFORE THE PERMIT IS ISSUED. FLORIDA STATUTES REQUIRE
 THE WORK TO START WITHIN 90 DAYS OF RECORDING THE NOC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-09 Cont ID  
Sent By rmcdouga Date 2007-04-09 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2007-04-09 Time 07:14 Sent To  
Notes
2007-04-09 13:37:24DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)THE NEW PLAN SHEETS ARE REQUIRED TO BE RESTAMPED BY
 THE HISTORICAL REVIEW DEPARTMENT.
  
 3) THE NOTE ON WALL SECTION 2 ON SHEET A3 OF THE PLANS
 SPECIFIES A HORIZONTAL SLIDING WINDOW AT THE KITCHEN
 AND THE WINDOW SCHEDULE ON A4 SPECIFIES A CASEMENT
 WINDOW AT THIS LOCATION. PLEASE CLARIFY.
  
 4) THE PRODUCT APPROVALS SUBMITTED FOR THE HORIZONTAL
 SLIDING WINDOW HAVE BEEN REVSED. PLEASE SUBMIT THE NEW
 FL COVERSHEET WITH NUMBER FL242-R5 AND NOA #
 03-0612.06.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-21 Cont ID  
Sent By rmcdouga Date 2007-02-21 Time 18:19 Rev Time 0.00
Received By rmcdouga Date 2007-02-21 Time 18:19 Sent To  
Notes
2007-02-21 19:06:09DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE WORK DESCRIPTION ON THE APPLICATION IS FOR
 INTERIOR REMDELING. THE PLANS SHOW NEW EXTERIOR WALLS
 AND INCREASING OPENING SIZE, IN ADDITION TO REPLACING
 WINDOWS AND DOORS. PLEASE REVISE WORK DESCRIPTION ON
 THE APPLICATION.
  
 3) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. SEE
 2004 FBC EXISTING BUILDING CHAPTER 3.
  
 4)PROVIDE AT LEAST ONE BATHROOM, LOCATED WITH MAXIMUM
 POSSIBLE PRIVACY, WHERE BATHROOMS ARE PROVIDED ON
 HABITABLE GRADE LEVELS, WITH A DOOR THAT HAS A 29-INCH
 (737 MM) CLEAR OPENING AS REQUIRED BY R322.1.1 AND FBC
 CHAPTER 11.
  
 5) THE PLANS SPECIFY MARVIN WINDOWS AND DOORS ON A4 AND
 A5 AND DO NOT SPECIFY OR EQUAL. THE PRODUCT APPROVALS
 SUBMITTED ARE FOR PGT WINDOWS AND DOORS. PLEASE REVISE
 PLANS.
  
 6) THE MASTER BEDROOM WINDOW IS LABELED"C" ON SHEET
 A1 AND THE WINDOW SCHEDULE ON A4 HAS "D" FOR THIS
 WINDOW. PLEASE CORRECT.
  
 7) THE NEW MASTER BEDROOM WINDOW IS REQUIRED TO COMPLY
 WITH R310.1 FOR EMERGENCY ESCAPE AND RESCUE OPENINGS.
 SHOW COMPLIANCE.
  
 8) ON A3 THE REAR (WEST) ELEVATION IS INCORRECTLY
 LABELED. PLEASE CORRECT.
  
 9) PROVIDE WINDOW AND DOOR BUCK DETAILS ON THE PLANS.
 SPECIFY THE FASTENERS AND SPACING.
  
 10) PROVIDE A STRUCTURAL DETAIL AT THE ENLARGED OPENING
 FOR THE NEW FRENCH DOOR. SPECIFY WALL AND BEAM
 REINFORCEMENT.
  
 11) PROVIDE STRUCTURAL DETAILS FOR THE NEW CBS IN-FILL
 WALLS AT THE MASTER BEDROOM ALCOVE AND AT THE FAMILY
 ROOM. SPECIFY REINFORCEMENT, TIE TO EXISTING STRUCTURE,
 LINTELS, BEAMS, ETC.
  
 12) PROVIDE STRUCTURAL DETAILS FOR THE CONSTRUCTION OF
 THE ARCH ABOVE THE NEW ARCH TOP WINDOW AT MASTER
 BEDROOM ALCOVE.
  
 13) SUBMIT 2 CURRENT PRODUCT APPROVALS FOR STRUCTURAL
 MULLIONS.
  
 14)PRODUCT APPROVALS WERE SUBMITTED FOR SINGLE HUNG
 WINDOWS AND HORIZONTAL SLIDING WINDOWS WHICH ARE NOT
 THE TYPES OF WINDOWS SPECIFIED ON THE PLANS AS BEING
 REPLACED. THE PLANS APPEAR TO SPECIFY THE NEW WINDOWS
 AS CASEMENT AND FIXED WINDOWS. PLEASE CLARIFY WINDOW
 TYPES, SIZES AND LOCATIONS..
  
 15) THE PRDOUCT APPROVALS FOR THE PGT HORIZONTAL SLIDER
 HAS BEEN REVISED. SUBMIT NOA 03-0612.06 WITH STATE
 COVERSHEET.
  
 16) THE COVERSHEET FOR THE PGT FIXED WINDOWS IS FOR THE
 2001 CODE AND HAS BEEN REVISED. REPLACE PAGE 6 OF THE
 NOA WHICH IS ILLEGIBLE.
  
 17) THE COVERSHEET FOR THE PGT CASEMENTWINDOWS IS FOR
 THE 2001 CODE AND HAS BEEN REVISED. THE NOA HAS BEEN
 REVISED TO 05-1129.11. SUBMIT CURRENT COPIES OF BOTH.
  
 18) THE NOA FOR THE PGT FRENCH DOORS IS EXPIRED. SUBMIT
 CURRENT NOA. SEE WWW,FLORIDABUILDING .ORG.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-01-12 Cont ID  
Sent By btrobaug Date 2007-01-12 Time 07:40 Rev Time 0.75
Received By btrobaug Date 2007-01-12 Time 06:38 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-05-21 Cont ID  
Sent By mperson Date 2007-05-21 Time 13:15 Rev Time 0.33
Received By mperson Date 2007-05-21 Time 13:15 Sent To B
Notes
2007-05-21 13:20:28NOTE: GAS PERMIT REQUIRED
  
 ****************PROVISO****************
 THE CORRECT TABLE FOR UNDERGROUND POLYETHLENE (PE)
 NATURAL GAS PIPE FOR A 0.5 PSI IS 402.4(20)
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 2,500 CUBIC FEET REQUIRED.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-04-03 Cont ID  
Sent By mperson Date 2007-04-03 Time 11:02 Rev Time 0.45
Received By mperson Date 2007-04-03 Time 11:02 Sent To B
Notes
2007-04-03 11:48:32DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **OK**
  
 3. **OK**
  
 NOW THAT THE ABOVE GROUND GAS PIPING HAS BEEN
 ESTABLISHED AS BEING GALVANIZED STEEL ON THE
 RESUBMITTAL THE FOLLOWING ARE NEW COMMENTS:
  
 4. SHEET P-3 ISOMETRIC GAS RISER DIAGRAM: GAS PIPE TO
 19O,000 BTU TANKLESS W/HTR. NEEDS TO BE INCREASED TO
 ONE INCH (1") PER FBC-2004 FUEL GAS TABLE 402.4 (2).
 PLEASE REFERENCE THE ATTACHED GAS SIZING TABLES TO THE
 GAS COMMENTS INDICATING THE NEED FOR THE PIPING
 INCREASE.
  
 5. SHEET P-3 ISOMETRIC GAS RISER DIAGRAM GAS PIPING TO
 THE NEW RANGE IS CONFUSING, ISOMETRIC IS INDICATING
 THREE SEPERATE CONNECTIONS TO THE APPLIANCE WITH A BTU
 LOAD OF 44,000 BTU'S. SHEET A-1 IS INDICATING A NEW GAS
 RANGE WITHPOSSIBLY SIX BURNERS (FOUR INDIVIDUAL
 BURNERS AND POSSIBLY TWO SIDE BURNERS FOR A SIDE
 GRIDDLE OR GRILL, INDIVIDUAL BURNER BTU LOAD IS AT
 15,000 WITH A TOTAL BTU LOAD INCLUDING THE OVENS IS
 POSSIBLY 137,000 BTU,S)PLEASE SUBMIT MANUFACTURER
 SPECIFICATIONS OF ALL APPLIANCES (GRILL, TANKLESS WATER
 HEATER, AND NEW GAS RANGE) VERIFYING THE BTU LOADS WITH
 THE ISOMETRIC AND SHOWING LISTINGS FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (NRTL).
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By mperson Date 2007-01-22 Time 08:59 Rev Time 0.33
Received By mperson Date 2007-01-22 Time 08:59 Sent To B
Notes
2007-01-22 09:24:43DENIED
 REFERENCE: FBC-2004 FUEL GAS AND THE CITY OF WEST PALM
 BEACH GAS PERMIT APPLICATION REQUIREMENTS.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE REQUIREMENTS:
  
 1.SHEET P-3 GAS ISOMETRIC: PLEASE INDICATE ALL PIPING
 MATERIAL BEING USED. THE ONLY GAS PIPE MATERIAL
 INDICATED AS BEING USED IS PE FOR THE UNDERGROUND. WHAT
 PIPING MATERIAL IS BEING USED ABOVE GROUND?
  
 2. SHEET P-3 GAS ISOMETRIC: THE TOTAL DISTANCE IS
 INDICATED WRONG AS 51'. THE CORRECT TOTAL DISTANCE IS
 SIXTY SEVEN FEET SIX INCHES (67'-6")PLEASE CORRECT ON
 THE RESUBMITTAL.
  
 3. SHEET P-3 GAS ISOMETRIC: PLEASE CLARIFY CHIMNEY
 50,000 BTU'S. IS THERE A FIRE PLACE, IF SO WHERE IS THE
 GAS PIPING?
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2007-06-19 Cont ID  
Sent By bpowell Date 2007-06-19 Time 14:35 Rev Time 0.00
Received By bpowell Date 2007-06-19 Time 14:34 Sent To  
Notes
2007-06-19 14:37:11RECONSIDER DECORATIVE NICHE DESIGN ANDONE WINDOW

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2007-01-09 Cont ID  
Sent By swurafti Date 2007-01-09 Time 12:18 Rev Time 0.00
Received By swurafti Date 2007-01-09 Time 12:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 13:55 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 13:54 Sent To G
Notes
2007-05-08 13:55:30TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 16:24 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 16:24 Sent To P
Notes
2007-03-16 16:24:37TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-22 Cont ID  
Sent By rmcdouga Date 2007-02-22 Time 10:31 Rev Time 0.00
Received By rmcdouga Date 2007-01-11 Time 16:44 Sent To  
Notes
2007-01-11 16:45:10TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-01-12 Cont ID  
Sent By tgordon Date 2007-01-12 Time 14:26 Rev Time 0.30
Received By tgordon Date 2007-01-12 Time 14:26 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-05-21 Cont ID  
Sent By mperson Date 2007-05-21 Time 13:12 Rev Time 0.20
Received By mperson Date 2007-05-21 Time 13:12 Sent To G
Notes
2007-05-21 13:14:32NOTE: PLUMBING PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-03 Cont ID  
Sent By mperson Date 2007-04-03 Time 11:01 Rev Time 0.20
Received By mperson Date 2007-04-03 Time 11:01 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By mperson Date 2007-01-22 Time 08:33 Rev Time 0.55
Received By mperson Date 2007-01-22 Time 08:33 Sent To G
Notes
2007-01-22 08:58:03DENIED
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1,
 CITY OF WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET P-3 SANITARY ISOMETRIC: A} PER FBC-2004
 CHAPTER 1, SECTION 106.3.5.4, PLEASE SIZE ALL FIXTURE
 TRAPS. B} PER FBC-2004 PLUMBING SECTION406.3 WASTE
 CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. C} PER FBC-2004 PLUMBING SECTION 708.9 ACCESS
 SHALL BE PROVIDED TO ALL CLEANOUTS. PLEASE INDICATE THE
 CLEANOUT FOR THE WASHING MACHINE AT FOUR FEET ABOVE
 FINNISH FLOOR (4' A.F.F.) ON THE RESUBMITTAL.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721