Plan Review Details - Permit 07010479
| Plan Review Stops For Permit 07010479 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2007-03-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-03-14 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-03-14 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2007-03-14 16:55:14 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | 1.)PROVIDE ORIGINAL PRODUCT APPROVALS WITH ORIGINAL | | | ARCHITECT'S REVIEW STAMP.THE PRODUCT APPROVALS | | | SUBMITTED ARE NOT LEGIBLE. | | | | | | 2.)FLORIDA STATE PRODUCT APPROVAL REQUIRED FAC9B72. | | | WWW.FLORIDABUILDING.ORG | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-02-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-02-06 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-02-06 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2007-02-06 14:45:32 | REVISION, FLAT DECK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2007-02-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-02-01 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-02-01 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2007-02-01 09:33:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)SEE GENERAL LIMITATION #9 OF THE NOA.NO ENHANCED | | | FASTENING ALLOWED.FOR SYSTEMS REFERRING TO GENERAL | | | LIMITATION #7, ONLY CORNER AND PERIMETER ZONE ENHANCED | | | FASTENING (NOT IN THE FIELD, ZONE 1). | | | | | | 2.)PAPERWORK SUBMITTED IS ILLEGIBLE.SUBMIT ONLY | | | LEGIBLE DOCUMENTS. | | | | | | 3.)THE PAPERWORK IS TO INCLUDE ALL INFORMATION | | | REGARDING THE ASSEMBLY.ONLY THE SECOND SHEET OF THE | | | APPROVED ASSEMBLY WAS PROVIDED.FASTENING FOR THE | | | INSULATION IS ON THE FIRST SHEET.CODE COMPLIANCE | | | CANNOT BE DETERMINED WITHOUT COMPLETE AND LEGIBLE | | | PAPERWORK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-01-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-23 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-23 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-01-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-22 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-22 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2007-01-22 13:12:44 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 3RD REVIEW; FROM PREVIOUS LIST: | | | | | | 1.)SPECIFY ENHANCED FASTENING FOR PERIMETER ZONES | | | (CORNER AND PERIMETER, ZONES 2 AND 3).SUBMIT | | | CALCULATIONS IN ACCORDANCE WITH RAS117 AS PER GENERAL | | | LIMITATION #7 ON THE MIAMIDADE NOA. | | | | | | THIS IS BEING REQUESTED BECAUSE THE FASTENERS YOU HAVE | | | SPECIFIED ON THE HIGH VELOCITY HURRICANE ZONE UNIFORM | | | PERMIT APPLICATION FORM, 4 IN THE FIELD, 7 PERIMETER, | | | 10 CORNER DOES NOT APPEAR TO BE COMPLIANT.EXPLAIN HOW | | | YOU HAVE DETERMINED FOUR FASTENERS PER BOARD FOR THE | | | FIELD WHEN THE PRODUCT APPROVAL STATES ONE PER 2 SQUARE | | | FEET, AND THIS IS A 4X4 INSULATION BOARD.(4X4=16, | | | DIVIDED BY 2=8).PROVIDE CALCULATIONS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-01-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-12 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-12 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2007-01-12 09:36:30 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 2ND REVIEW; FROM PREVIOUS LIST: | | | | | | 1.)SPECIFY ENHANCED FASTENING FOR PERIMETER ZONES.A | | | NOTE WAS PUT ON THE PLAN, "FASTENING FLAT AREA, FIELD | | | 4", PERIMETER 6", CORNER 8", PERIMETER ALL AROUND 6'". | | | IT IS NOT CLEAR WHAT THIS IS FOR.THE FIELD HAS A | | | CLOSER FASTENING THAN CORNER AND PERIMETER BUT THE | | | CORNER AND PERIMETER ZONES HAVE A HIGHER PRESSURE. ALSO | | | FASTENING IS NOT CLEAR; YOU ARE USING INSULATION BOARD. | | | SUBMIT CALCULATIONS IN ACCORDANCE WITH RAS117 AS PER | | | GENERAL LIMITATION #7 ON THE MIAMIDADE NOA. | | | | | | 2.)PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER OF | | | RECORD, FBC*106.3.3.ENHANCED FASTENING TO BE REVIEWED | | | BY DOR.THE ARCHITECT STATES THAT THIS IS NOT AN | | | APPROVED PRODUCT AND APPROVES IT ONLY IF IT IS AN | | | EQUIVALENT.THE DOR IS TO MAKE THAT DETERMINATION; | | | PLAN REVIEW IS TO REVIEW FOR MINIMUM CODE. | | | | | | 3.)THE PLAN SHOWS A TILE ROOF.PROVIDE PRODUCT | | | APPROVALS, REVIEWED BY DOR.THE PRODUCT APPROVAL | | | SUBMITTED (HANSON) IS ACCEPTABLE, AS IS THE FASTENING | | | INDICATED, BUT WAS NOT REVIEWED BY DOR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-01-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-05 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-05 |
Time |
18:05 |
Sent To |
|
|
| Notes |
| 2007-01-05 18:08:57 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)SPECIFY ENHANCED FASTENING FOR PERIMETER ZONES. | | | | | | 2.)PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER OF | | | RECORD, FBC*106.3.3.ENHANCED FASTENING TO BE REVIEWED | | | BY DOR. | | | | | | 3.)THE PLAN SHOWS A TILE ROOF.PROVIDE PRODUCT | | | APPROVALS, REVIEWED BY DOR.INDICATE METHOD OF | | | FASTENING ON THE PRODUCT APPROVAL. | | | |
|
|
|