Plan Review Details - Permit 07010479
Plan Review Stops For Permit 07010479
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-03-14 Cont ID  
Sent By shill Date 2007-03-14 Time 16:51 Rev Time 0.00
Received By shill Date 2007-03-14 Time 16:51 Sent To  
Notes
2007-03-14 16:55:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PROVIDE ORIGINAL PRODUCT APPROVALS WITH ORIGINAL
 ARCHITECT'S REVIEW STAMP.THE PRODUCT APPROVALS
 SUBMITTED ARE NOT LEGIBLE.
  
 2.)FLORIDA STATE PRODUCT APPROVAL REQUIRED FAC9B72.
 WWW.FLORIDABUILDING.ORG
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-02-06 Cont ID  
Sent By shill Date 2007-02-06 Time 14:45 Rev Time 0.00
Received By shill Date 2007-02-06 Time 14:45 Sent To  
Notes
2007-02-06 14:45:32REVISION, FLAT DECK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-02-01 Cont ID  
Sent By shill Date 2007-02-01 Time 09:26 Rev Time 0.00
Received By shill Date 2007-02-01 Time 09:26 Sent To  
Notes
2007-02-01 09:33:48****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)SEE GENERAL LIMITATION #9 OF THE NOA.NO ENHANCED
 FASTENING ALLOWED.FOR SYSTEMS REFERRING TO GENERAL
 LIMITATION #7, ONLY CORNER AND PERIMETER ZONE ENHANCED
 FASTENING (NOT IN THE FIELD, ZONE 1).
  
 2.)PAPERWORK SUBMITTED IS ILLEGIBLE.SUBMIT ONLY
 LEGIBLE DOCUMENTS.
  
 3.)THE PAPERWORK IS TO INCLUDE ALL INFORMATION
 REGARDING THE ASSEMBLY.ONLY THE SECOND SHEET OF THE
 APPROVED ASSEMBLY WAS PROVIDED.FASTENING FOR THE
 INSULATION IS ON THE FIRST SHEET.CODE COMPLIANCE
 CANNOT BE DETERMINED WITHOUT COMPLETE AND LEGIBLE
 PAPERWORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-01-23 Cont ID  
Sent By shill Date 2007-01-23 Time 12:00 Rev Time 0.00
Received By shill Date 2007-01-23 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-01-22 Cont ID  
Sent By shill Date 2007-01-22 Time 11:48 Rev Time 0.00
Received By shill Date 2007-01-22 Time 11:48 Sent To  
Notes
2007-01-22 13:12:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 3RD REVIEW; FROM PREVIOUS LIST:
  
 1.)SPECIFY ENHANCED FASTENING FOR PERIMETER ZONES
 (CORNER AND PERIMETER, ZONES 2 AND 3).SUBMIT
 CALCULATIONS IN ACCORDANCE WITH RAS117 AS PER GENERAL
 LIMITATION #7 ON THE MIAMIDADE NOA.
  
 THIS IS BEING REQUESTED BECAUSE THE FASTENERS YOU HAVE
 SPECIFIED ON THE HIGH VELOCITY HURRICANE ZONE UNIFORM
 PERMIT APPLICATION FORM, 4 IN THE FIELD, 7 PERIMETER,
 10 CORNER DOES NOT APPEAR TO BE COMPLIANT.EXPLAIN HOW
 YOU HAVE DETERMINED FOUR FASTENERS PER BOARD FOR THE
 FIELD WHEN THE PRODUCT APPROVAL STATES ONE PER 2 SQUARE
 FEET, AND THIS IS A 4X4 INSULATION BOARD.(4X4=16,
 DIVIDED BY 2=8).PROVIDE CALCULATIONS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-12 Cont ID  
Sent By shill Date 2007-01-12 Time 09:36 Rev Time 0.00
Received By shill Date 2007-01-12 Time 09:36 Sent To  
Notes
2007-01-12 09:36:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 2ND REVIEW; FROM PREVIOUS LIST:
  
 1.)SPECIFY ENHANCED FASTENING FOR PERIMETER ZONES.A
 NOTE WAS PUT ON THE PLAN, "FASTENING FLAT AREA, FIELD
 4", PERIMETER 6", CORNER 8", PERIMETER ALL AROUND 6'".
 IT IS NOT CLEAR WHAT THIS IS FOR.THE FIELD HAS A
 CLOSER FASTENING THAN CORNER AND PERIMETER BUT THE
 CORNER AND PERIMETER ZONES HAVE A HIGHER PRESSURE. ALSO
 FASTENING IS NOT CLEAR; YOU ARE USING INSULATION BOARD.
 SUBMIT CALCULATIONS IN ACCORDANCE WITH RAS117 AS PER
 GENERAL LIMITATION #7 ON THE MIAMIDADE NOA.
  
 2.)PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC*106.3.3.ENHANCED FASTENING TO BE REVIEWED
 BY DOR.THE ARCHITECT STATES THAT THIS IS NOT AN
 APPROVED PRODUCT AND APPROVES IT ONLY IF IT IS AN
 EQUIVALENT.THE DOR IS TO MAKE THAT DETERMINATION;
 PLAN REVIEW IS TO REVIEW FOR MINIMUM CODE.
  
 3.)THE PLAN SHOWS A TILE ROOF.PROVIDE PRODUCT
 APPROVALS, REVIEWED BY DOR.THE PRODUCT APPROVAL
 SUBMITTED (HANSON) IS ACCEPTABLE, AS IS THE FASTENING
 INDICATED, BUT WAS NOT REVIEWED BY DOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-05 Cont ID  
Sent By shill Date 2007-01-05 Time 18:05 Rev Time 0.00
Received By shill Date 2007-01-05 Time 18:05 Sent To  
Notes
2007-01-05 18:08:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)SPECIFY ENHANCED FASTENING FOR PERIMETER ZONES.
  
 2.)PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC*106.3.3.ENHANCED FASTENING TO BE REVIEWED
 BY DOR.
  
 3.)THE PLAN SHOWS A TILE ROOF.PROVIDE PRODUCT
 APPROVALS, REVIEWED BY DOR.INDICATE METHOD OF
 FASTENING ON THE PRODUCT APPROVAL.
  