Plan Review Details - Permit 07010472
Plan Review Stops For Permit 07010472
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-07-24 Cont ID  
Sent By jwitmer Date 2008-07-24 Time 11:25 Rev Time 0.77
Received By jwitmer Date 2008-07-24 Time 11:25 Sent To PC
Notes
2008-07-24 11:26:45REVISON# 3 PR#10 - OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-03-24 Cont ID  
Sent By jwitmer Date 2008-03-24 Time 13:14 Rev Time 0.77
Received By jwitmer Date 2008-03-24 Time 13:14 Sent To  
Notes
2008-03-24 13:15:18SHOP DRAWINGS FL# 04-5854.1/ NOA 04-0227.02

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-02-26 Cont ID  
Sent By jwitmer Date 2008-02-26 Time 11:57 Rev Time 0.33
Received By jwitmer Date 2008-02-26 Time 11:57 Sent To  
Notes
2008-02-26 12:05:01BUILDING PLAN REVIEW
 PERMIT: 07010472
 ADD: 5205 GREENWOOD
 CONT: HEDRICK BROTHERS
 TEL: (561)242-4315
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
  
 SHOP DRAWING REVIEW: DENIED
  
 FL # 5854.1 / 04-0227.02 YKK35H MEDIUM STILE IMPACT
 DOOR:
  
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-02-26 Cont ID  
Sent By jwitmer Date 2008-02-26 Time 11:48 Rev Time 2.20
Received By jwitmer Date 2008-02-26 Time 11:08 Sent To  
Notes
2008-02-26 11:53:27BUILDING PLAN REVIEW
 PERMIT: 07010472
 ADD: 5205 GREENWOOD
 CONT: HEDRICK BROTHERS
 TEL: (561)242-4315
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
  
 SHEET GC-101, REVISION NEW PLAYGROUND. A SPERATE PERMIT
 WILL BE REQUIRED FOR ADA COMPLIANCE OF PLAYGROUND
 EQUIPMENT.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-10 Cont ID  
Sent By jwitmer Date 2007-10-10 Time 14:53 Rev Time 0.00
Received By rkussner Date 2008-02-21 Time 08:48 Sent To PC
Notes
2008-02-21 09:02:51BY MISTAKEWE INADVERTANTLY WENT INTO THE BLDG. REVIEW
 STOP AND IT SHOULD OF BEEN LANDSCAPING. ROBERT KUSSNER
 X1462 PER LUIS MARTINEZ
2007-10-10 14:54:39SF-103 & SF-505

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-26 Cont ID  
Sent By jwitmer Date 2007-08-26 Time 16:29 Rev Time 2.00
Received By jwitmer Date 2007-08-26 Time 16:29 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-14 Cont ID  
Sent By jwitmer Date 2007-06-14 Time 12:39 Rev Time 5.55
Received By jwitmer Date 2007-06-14 Time 07:59 Sent To PC
Notes
2007-06-14 12:47:55BUILDING PLAN REVIEW
 PERMIT: 07010472
 ADD: 5205 GREENWOOD AVE
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) 2ND REQUEST SHEET SS-002 LOADS AND DESIGN CRITERIA
 NOTE (D) TO PROVIDE GEOTECHNICAL REPORTS.THE REPORTS
 SUBMITTED ARE COPIES NOT THE ORIGINAL SIGNED AND SEALED
 REPORTS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL STATE
 STAT: 61G15-23.002 ENGINEERS.
 FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 5-6A) COMPLIED.
  
 6B) 2ND REQUEST,DETAIL # 2 INDICATES A MONOLITHIC
 FOOTER GOING PAST THE STEEL FRAME WALL BY SEVERAL
 INCHES, HOW WILL THIS BE WATERPROOFED SO WATER WILL NOT
 OSMOSIS UNDER THE BOTTOM TRACK TO THE INTERIOR OF THE
 BUILDING? SHEET DETAIL 8 /AF-510 INDICATES THE USE OF A
 MEMBRANE FLASHING APPLIED TO THE 5/8" EXTERIOR
 DENSEGLASSGOLD SHEATHING.
 1403.8
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
  
 WITH THIS TYPE OF CONSTRUCTION OR ALTRATION TO THE
 EXISTING BUILDING UNDER THE EXISTING CBS WITH STUCCO
 DIRECTLY APPLIED TO THE BLOCK, THE CODE WAS NOT
 CONCERNED WITH A 6" INSPECTION ZONE FOR TERMITES.WHEN
 APPLYING THE VENEER TO THE EXTERTIORTHIS CHANGES THE
 LEVEL OR GRADE ON THE EXTERIOR OF THE BUILDING. SHEET
 SB-502 DETAIL# 1 INDICATES THE FOOTING AND SLAB TOTAL
 12" IN THE VERTICAL DIMENSION. WITH THE 6" INSPECTION
 PANEL AND THE 12" MINIMUM REQUIREMENT FOR FOUNDATIONS
 THE MINIMUM VERTICAL HEIGHT OF THE FOUNDATION IS 18",
 PLEASE UPDATE THEA & S SHEETS.
  
 6C) 2ND REQUEST, BOTH DETAILS 1& 2 BOTH INDICATE THE
 USE OF STEEL NETWORKS VERTICLIP SLS & SLB , HOW ARE
 THEY FASTENED TO THE EXISTING STEEL DECK, SINCE THEY
 ARE PART OF CREATING THE EXTERIOR ENVELOPE (MAIN
 WINDFORCE-RESISTING SYSTEM) DO THEY HAVE ANY PRODUCT
 EVALUATION REPORTS?IF REPORTS ARE AVAILABLE HAVE
 THEY TAKEN A 1.33% IN WINDLOADS? PLEASE SEE ICC
 REPORT ERS 1903 FOR SL, SLB, SLS & SLT EXTERIOR CURTAIN
 WALL SYSTEM. PROVIDE PRODUCT APPROVALS.
  
 6D) 2ND REQUEST, THIS SAME DETAIL IT WOULD APPEAR THAT
 THERE IS A GAP BETWEEN THE EXISTING FLOOR SLAB AND THE
 NEWLY CREATED CURTAIN WALL SYSTEM, WHAT WILL BE USED TO
 STOP THE VOID IN THE WALL AT THE SLAB LEVEL, FIRE
 PROOFING MATERIALS? SHEET AF-302 INDICATE & PROVIDE
 DOCUMENTATION OFUL FIRE STOP SYSTEM? 717.2.3
 CONNECTIONS BETWEEN HORIZONTAL AND VERTICAL SPACES.
 FIREBLOCKING SHALL BE PROVIDED AT INTERCONNECTIONS
 BETWEEN CONCEALED VERTICAL STUD WALL OR PARTITION
 SPACES AND CONCEALED HORIZONTAL SPACES CREATED BY AN
 ASSEMBLY OF FLOOR JOISTS OR TRUSSES, AND BETWEEN
 CONCEALED VERTICAL AND HORIZONTAL SPACES SUCH AS OCCUR
 AT SOFFITS, DROP CEILINGS, COVE CEILINGS AND SIMILAR
 LOCATIONS.
 717.2.1 FIREBLOCKING MATERIALS.
 FIREBLOCKING SHALL CONSIST OF 2-INCH (51 MM) NOMINAL
 LUMBER OR TWO THICKNESSES OF 1-INCH (25 MM) NOMINAL
 LUMBER WITH BROKEN LAP JOINTS OR ONE THICKNESS OF
 0.719-INCH (18.3 MM) WOOD STRUCTURAL PANEL WITH JOINTS
 BACKED BY 0.719-INCH (18.3 MM) WOOD STRUCTURAL PANEL OR
 ONE THICKNESS OF 0.75-INCH (19 MM) PARTICLEBOARD WITH
 JOINTS BACKED BY 0.75-INCH (19 MM) PARTICLEBOARD.
 GYPSUM BOARD, CEMENT FIBER BOARD, BATTS OR BLANKETS OF
 MINERAL WOOL OR GLASS FIBER OR OTHER APPROVED MATERIALS
 INSTALLED IN SUCH A MANNER AS TO BE SECURELY RETAINED
 IN PLACE SHALL BE PERMITTED AS AN ACCEPTABLE FIREBLOCK.
 BATTS OR BLANKETS OF MINERAL OR GLASS FIBER OR OTHER
 APPROVED NONRIGID MATERIALS SHALL BE PERMITTED FOR
 COMPLIANCE WITH THE 10-FOOT (3048 MM) HORIZONTAL
 FIREBLOCKING IN WALLS CONSTRUCTED USING PARALLEL ROWS
 OF STUDS OR STAGGERED STUDS. LOOSE-FILL INSULATION
 MATERIAL SHALL NOT BE USED AS A FIREBLOCK UNLESS
 SPECIFICALLY TESTED IN THE FORM AND MANNER INTENDED FOR
 USE TO DEMONSTRATE ITS ABILITY TO REMAIN IN PLACE AND
 TO RETARD THE SPREAD OF FIRE AND HOT GASES. THE
 INTEGRITY OF FIREBLOCKS SHALL BE MAINTAINED.
 717.2.1.1 DOUBLE STUD WALLS. BATTS OR BLANKETS OF
 MINERAL OR GLASS FIBER OR OTHER APPROVED NONRIGID
 MATERIALS SHALL BE ALLOWED AS FIREBLOCKING IN WALLS
 CONSTRUCTED USING PARALLEL ROWS OF STUDS OR STAGGERED
 STUDS.
  
 6E) PROVISO: STEEL SHOP DRAWINGS TO BE REVIEWED BY
 DESIGN PROFESSIONALBEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT.
  
 6F) COMPLIED.
  
 7) SHEET AF-302
 7A)(1) THE QUESTION ASKED WAS WHAT TYPE OF MATERIAL WAS
 TO BE USED FOR THE EXTERIOR TRIM ON THE BUILDING.
 RESPONSE COMMENTS ARE THIS IS TO BE A DRYVIT INFINITY
 SYSTEM. SUBMITTED WASA
 FLORIDA COVERSHEET 2030- R1, WHEN YOU LOOK INTO THE
 REPORT THE BACK UP INFORMATION IS SUPPOSE TO BE A
 MIAMI-DADE REPORT NOA 01-0614.14 SUCH REPORT WAS NOT
 SUBMITTED.
 7A)(2) THERE ARE TWO ISSUE WITH THE USE OF EFIS WALL
 SYSTEMS AND THE USE OF EFIS TO BE USED AS TRIM.
 EFIS WALL SYSTEMS:2603.3
 SURFACE-BURNING CHARACTERISTICS.
 UNLESS OTHERWISE INDICATED IN THIS SECTION,
 FOAM PLASTIC INSULATION AND FOAM PLASTIC CORES OF
 MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 75 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450
 WHERE TESTED IN THE MAXIMUM THICKNESS INTENDED FOR USE
 IN ACCORDANCE WITH ASTM E 84. LOOSE FILL-TYPE FOAM
 PLASTIC INSULATION SHALL
 BE TESTED AS BOARD STOCK FOR THE FLAME SPREAD
 INDEX AND SMOKE-DEVELOPED INDEX.
 EFIS EXTERIOR TRIM:2603.5.4 FLAME
 SPREAD AND SMOKE-DEVELOPED INDEXES. FOAM PLASTIC
 INSULATION, EXTERIOR COATINGS AND FACINGS SHALL BE
 TESTED SEPARATELY IN THE THICKNESS
 INTENDED FOR USE, BUT NOT TO EXCEED 4 INCHES
 (102 MM), AND SHALL EACH HAVE A FLAME SPREAD INDEX OF
 25 OR LESS AND A SMOKE-DEVELOPED INDEX OF 450 OR LESS
 AS DETERMINED IN
 ACCORDANCE WITH ASTM E 84.
 2603.5 EXTERIOR WALLS OF BUILDINGS
 OF ANY HEIGHT.
 EXTERIOR WALLS OF BUILDINGS OF TYPE I, II, III
 OR IV CONSTRUCTION OF ANY HEIGHT SHALL COMPLY WITH
 SECTIONS 2603.5.1 THROUGH 2603.5.7 . EXTERIOR WALLS OF
 COLD STORAGE BUILDINGS REQUIRED TO
 BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS,
 WHERE THE BUILDING IS MORE THAN ONE STORY IN HEIGHT,
 SHALL ALSO COMPLY WITH THE PROVISIONS OF SECTIONS
 2603.5.1 THROUGH 2603.5.7 .
 EXTERIOR WALLS OF BUILDINGS OF TYPE V
 CONSTRUCTION SHALL COMPLY WITH SECTIONS 2603.2 , 2603.3
 AND 2603.4 .
  
 7B) COMPLIED.
  
 8) COMPLIED.
  
 9A) PARTIALLY COMPLIED WE ARE STILL MISSING PRODUCT
 APPROVALS. ) 1609.1.4 PROTECTION OF OPENINGS. IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BEOPENINGS AND
 THE BALANCE OF GLAZED OPENINGS IN THE REST OF THE
 BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT
 RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 AND ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.GLAZED
 OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL
 MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. 2.
 GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) ABOVE
 GRADE SHALL MEET THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 9B) PARTIALLY COMPLIED.PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICA TION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 9C) PARTIALLY COMPLIED.) WPB ADMIN CODE 106.3*
 PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9D) FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 1. WINDOWS
 A. FIXED -OK
 B) STOREFRONT - NOT SUBMITTED
 C) CIRCULAR FIXED FRAME- NOT SUBMITTED
 D) CURTAIN WALL
 2) GLAZED DOORS
 A) KANEER IR-350 NOT SUBMITTED
 B) HOLLOW METAL DOOR- OK
 3) TRANSOM NOT SUBMITTED
 4) SIDELIGHTS- NOT SUBMITTED
 5) MULLIONS
 6) LOUVERS- STATED NONE IN BUILDING?
 7) EFIS SYSTEMS WRONG BACK UP REPORT
 8) ROOF ASSEMBLIES
 A) MAIN ROOF FIRESTONE ULTRAPLY - NO ENHANCED
 FASTENING REQUIRES ENGINEERS SEAL AND SIGNATURE
 B) ROOF TILE OK
 C) STANDING SEAM- OK
 D) UNDERLAYMENTS- OK
 E) ROOF INSULATION- OK
 F) ROOF HATCH EXISTING
 G) PRE-MANUFACTURED A/C STANDS NEW COMMENT
  
 10) COMPLIED.
  
 11) 2ND REQUEST,BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-02 Cont ID  
Sent By jwitmer Date 2007-02-02 Time 14:11 Rev Time 5.55
Received By jwitmer Date 2007-02-02 Time 08:51 Sent To  
Notes
2007-02-02 17:01:53 
 BUILDING PLAN REVIEW
 PERMIT: 07010472
 ADD: 5205 GREENWOOD AVE
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET SB-101 THE PLANS DO NOT INDICATE THE USE OF
 TERMITE TREATMENT FOR THE NEW CONCRETE SLAB. 1816.1.1
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, THE INITIAL CHEMICAL SOIL TREATMENT INSIDE
 THE FOUNDATION PERIMETER SHALL BE DONE AFTER ALL
 EXCAVATION, BACKFILLING AND COMPACTION IS COMPLETE.
  
 1816.1.2
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, SOIL AREA DISTURBED AFTER INITIAL CHEMICAL
 SOIL TREATMENT SHALL BE RETREATED WITH A CHEMICAL SOIL
 TREATMENT, INCLUDING SPACES BOXED OR FORMED.
  
 1816.1.3
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, SPACE IN CONCRETE FLOORS BOXED OUT OR
 FORMED FOR THE SUBSEQUENT INSTALLATION OF PLUMBING
 TRAPS, DRAINS OR ANY OTHER PURPOSE SHALL BE CREATED BY
 USING PLASTIC OR METAL PERMANENTLY PLACED FORMS OF
 SUFFICIENT DEPTH TO ELIMINATE ANY PLANNED SOIL
 DISTURBANCE AFTER INITIAL CHEMICAL SOIL TREATMENT.
  
 1816.1.4
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CHEMICALLY TREATED SOIL SHALL BE PROTECTED
 WITH A MINIMUM 6 MILLIMETER VAPOR RETARDER TO PROTECT
 AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE
 VAPOR RETARDER PLACEMENT, RETREATMENT IS REQUIRED. ANY
 WORK, INCLUDING PLACEMENT OF REINFORCING STEEL, DONE
 AFTER CHEMICAL TREATMENT UNTIL THE CONCRETE FLOOR IS
 POURED, SHALL BE DONE IN SUCH MANNER AS TO AVOID
 PENETRATING OR DISTURBING TREATED SOIL.
  
 1816.1.5
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CONCRETE OVERPOUR OR MORTAR ACCUMULATED
 ALONG THE EXTERIOR FOUNDATION PERIMETER SHALL BE
 REMOVED PRIOR TO EXTERIOR CHEMICAL SOIL TREATMENT, TO
 ENHANCE VERTICAL PENETRATION OF THE CHEMICALS.
  
 4)SHEET SS-002 LOADS AND DESIGN CRITERIA NOTE D) TO
 PROVIDE GEOTECHNICAL REPORT. FBC 1802.2.1
 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 5) SHEET SF-101:
 5A) THIS SHEET INDICATES A DETAIL# 1/ SB502 THIS DETAIL
 IS OF A EXPANDED FOOTER THE WIDTH IS PROVIDED BUT NOT
 THE LENGTH. THE DEPTH AND NUMBER OF STEELBARS AND SIZE
 OF BARS IS PROVIDED IN THE DETAIL. PLEASE PROVIDE THE
 LENGTH.
  
 6) SHEET SF-102:
  
 6A) DETAIL# 1/SF-504 DOESN'T INDICATE IF THE EXISTING
 PARAPET WALL WILL BE CUT AWAY AT THIS NEW ROOF AREA OR
 WILL THIS AREA NEED DRAINAGE AND EMERGENCY OVERFLOWS,
 FOR BOTH SIDES OF THE BUILDING? ADITIONAL INFORMATION
 REQUIRED?
  
 6B) DETAIL # 2 INDICATES A MONOLITHIC FOOTER GOING PAST
 THE STEEL FRAME WALL BY SEVERAL INCHES, HOW WILL THIS
 BE WATERPROOFED SO WATER WILL NOT OSMOSIS UNDER THE
 BOTTOM TRACK TO THE INTERIOR OF THE BUILDING? SHEET
 DETAIL 8 /AF-510 INDICATES THE USE OF A MEMBRANE
 FLASHING APPLIED TO THE 5/8" EXTERIOR DENSEGLASSGOLD
 SHEATHING.
 1403.8
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
  
 6C) BOTH DETAILS 1& 2 BOTH INDICATE THE USE OF STEEL
 NETWORKS VERTICLIP SLS & SLB , HOW ARE THEY FASTENED TO
 THE EXISTING STEEL DECK, SINCE THEY ARE PART OF
 CREATING THE EXTERIOR ENVELOPE (MAIN
 WINDFORCE-RESISTING SYSTEM) DO THEY HAVE ANY PRODUCT
 EVALUATION REPORTS?IF REPORTS ARE AVAILABLE HAVE
 THEY TAKEN A 33%
 IN WINDLOADS?
  
 6D) THIS SAME DETAIL IT WOULD APPEAR THAT THERE IS A
 GAP BETWEEN THE EXISTING FLOOR SLAB AND THE NEWLY
 CREATED CURTAIN WALL SYSTEM, WHAT WILL BE USED TO STOP
 THE VOID IN THE WALL AT THE SLAB LEVEL, FIRE PROOFING
 MATERIALS? SHEET AF-302 INDICATES UL FIRE STOP SYSTEM?
 711.3 FIRE-RESISTANCE RATING.
 THE FIRE-RESISTANCE RATING OF FLOOR AND ROOF ASSEMBLIES
 SHALL NOT BE LESS THAN THAT REQUIRED BY THE BUILDING
 TYPE OF CONSTRUCTION. WHERE THE FLOOR ASSEMBLY
 SEPARATES MIXED OCCUPANCIES, THE ASSEMBLY SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN THAT REQUIRED
 BY SECTION 302.3.2 BASED ON THE OCCUPANCIES BEING
 SEPARATED. WHERE THE FLOOR ASSEMBLY SEPARATES A SINGLE
 OCCUPANCY INTO DIFFERENT FIRE AREAS, THE ASSEMBLY SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN THAT
 REQUIRED BY SECTION 706.3.7 . FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDING OR
 SLEEPING UNITS IN OCCUPANCIES IN GROUP R-1, HOTEL
 OCCUPANCIES, R-2 AND I-1 SHALL BE A MINIMUM OF 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION.
  
 6E) DETAIL # 1/ SF-505INDICATES AN EXISTING W16X26
 AND A NEW BEAM W14X26. THE DETAIL INDICATES THE W14X26
 WITH CONNECTION PLATES THAT ARE BOLTEDONTO THE W14X26,
 BOLT SIZE IS NOT PROVIDED, ALSO THE CONNECTION PLATE
 SIZE OR TYPE OF CONFIGURATION ISN'T PROVIDED NOR THE
 CONNECTION TO BEAM W16X26?
 106.1.2. ADDITIONAL INFORMATION REQUIRED.
  
 6E) AT THE END OF THE SAME CANOPY THERE IS A SECTION
 THROUGH THE NEW W14X26 BUT NO DETAIL OF HOW THIS WILL
 BE ASSEMBLED?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 7) SHEET AF-302
  
 7A)SHEET AF-302 DETAILS 1& 2 BOTH INDICATE EXTERIOR
 MOLDING OR TRIM ON THE EXTERIOR OF THE BUILDING, WHAT
 TYPE OF TRIMWILL BE USED AND HOW WILL IT BE
 ATTACHED?
  
 106.1.2 ADDITIONAL INFROMATIOIN
  
 7B) SHEET AF-302 BOTH DETAILS INDICATE SECTION 1/
 AF-510 A 2 1/2" STRUCTURAL METAL STUD GAUGE OF
 STREUCTURAL STUD IS NOT PROVIDED. SHEET SF-504 DOESN'T
 INDICATE GAUGE OF 2 1/2 STRUCTURAL STUD OR HOW IT WILL
 BE TIED BACK TO THE 6" / 20 GAUGE METAL STUD WALL?
  
 8) SHEET AF-303 DETAIL# 4 INDICATES THE USE OF STANDING
 SEAM METAL ROOF SYSTEM, DETAIL# 8 OF SF-501 INDICATES A
 SSTRUCTURAL DECK OF1 1/2" B METAL DECK,
 PLEASE PROVIDE COMPLIANCE WITH 1507.4.2. THIS ROOF HAS
 LESS THAN A 2:12 SLOPE.
 1507.4.2 DECK SLOPE.
 THE MINIMUM SLOPE FOR LAPPED, NONSOLDERED SEAM METAL
 ROOFS WITHOUT APPLIED LAP SEALANT SHALL BE THREE UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (25-PERCENT SLOPE). THE
 MINIMUM SLOPE FOR LAPPED, NONSOLDERED SEAM METAL ROOFS
 WITH APPLIED LAP SEALANT SHALL BE ONE-HALF VERTICAL
 UNIT IN 12 UNITS HORIZONTAL (4-PERCENT SLOPE). THE
 MINIMUM SLOPE FOR STANDING SEAM OF ROOF SYSTEMS SHALL
 BE ONE-QUARTER UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE).
  
 9A)1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 9B)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT WWW.
 FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9C)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9D)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 WINDOWS:
 FIXED WINDOWS STORE FRONT
 CURTAINWALL
 DOORS:
 GLAZED DOORS
 HOLLOW METAL FRAME DOORS
 TRANSOMS
 SIDELIGHTS
 MULLIONS
 VERTICAL
 HORIZONTAL
 LOUVERS WALL
 EFIS SYSTEMS
 ROOFING ASSEMBLIES
 UNDERLAYMENTS
 ROOFING INSULATION
 STANDING SEAM METAL ROOFING
 ROOF HATCHES IF NEW OR REPLACED
  
 9E ) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 __X__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _X_ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 _NOT KNOWN__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 _NOT KNOWN__THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 10) PLEASE PROVIDE THE APPROPRIATE INFORMATION FOR
 EITHER OF THE FOLLOWING:
 13-400.2A.2 SHELL BUILDING
 14-400.0..C.4 RENOVATED BUILDINGS
 13-400.0 COMPLIANCE CRITERIA
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 7 Status N Date 2008-02-14 Cont ID  
Sent By dpalmer Date 2008-02-14 Time 10:11 Rev Time 0.00
Received By dpalmer Date 2008-02-14 Time 10:11 Sent To  
Notes
2008-02-14 10:15:02** REVISED PLANS ALREADY REVIEWED AND STAMPED SHEETS.
 TWO ROLLS OF REVISIONS SUBMITTED. ONE ROLL CONTAINS
 STAMPS FROM ELECTRICAL REVIEW WHICH IS THE CONTRACTORS
 COPY FOR ON-SITE.
 THE SECOND ROLL CONTAINS ALL NEW SHEETS WHICH ARE THE
 SAME AS THE ORIGINAL REVISION AND ROLLS.
 THESE NEW SHEETS ARE NOT NEEDED. THE FILE ROLL ALREADY
 CONTAINS THE REVISIONS FROM PREVIOUS SUBMITTEED
 REVISIONS PASSED ON NOV 29, 2007. DO NOT NEED ANY OTHER
 SHEETS. NONE STAMPED SHEETS WILL BE RETURNED TO
 CONTRACTOR ALONG WITH PREVIOUS STAMPED CONTRACTORS
 COPY.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6717

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-11-29 Cont ID  
Sent By dpalmer Date 2007-11-29 Time 16:02 Rev Time 0.00
Received By dpalmer Date 2007-11-29 Time 16:02 Sent To  
Notes
2007-11-29 16:02:40REV #4 FOR PHASE #2, HARVEST PUMP

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-09-23 Cont ID  
Sent By dpalmer Date 2007-09-23 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2007-09-23 Time 07:38 Sent To PC
Notes
2007-09-23 08:46:24*** INSERTED NEW SHEETS INTO COMPLETE SETS, STAMPED ALL
 SHEETS, STAMPED PRODUCT APPROVALS, STRUCTURAL SHOP
 DRAWINGS, AND ALL SUPPORTING DOCUMENTS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-09-15 Cont ID  
Sent By dpalmer Date 2007-09-15 Time 18:16 Rev Time 0.00
Received By dpalmer Date 2007-09-15 Time 17:09 Sent To PC
Notes
2007-09-15 18:18:332007-09-15 18:18:33
  
 ** TEMPORARY FAILED STATUS***
  
 NEEDS TWO COMPLETE SETS OF PLANS BEFORE PROCESSING AND
 ISSUANCE OF PERMIT.
 CONTACT AHS BEEN MADE WITH THE ARCHITECT AND CONTRACTOR
 BY PHONE AND E-MAIL.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT:
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALMBEACH
 561-805-6717
 [email protected]
2007-09-15 17:09:532007-09-15 17:09:53
  
 IN ELECTRIC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-07 Cont ID  
Sent By dpalmer Date 2007-07-07 Time 19:07 Rev Time 0.00
Received By dpalmer Date 2007-07-07 Time 15:49 Sent To I
Notes
2007-07-07 19:28:222007-07-07 19:28:22
 *** NOTE ADDED **
  
 1) NOTE THIS COMMENT IS FOR THE LANDSCAPE PLANS AND
 DESIGNER OF RECORD FOR THESE SHEETS.
 PLEASE SEE THE SEAL IN USE ON LANDSCAPE PLANS IS
 REQUIRED TO MEET FAC 61G1-16.002. THIS IS REQUIRED
 WHETHER OR NOT COMMENT IS MADE BY OTHER.
 THIS IS A NEW COMMENT AND WAS NOTICE WHEN PLANS WERE
 BEING ROLLED. PLEASE SEE ZONING FOR POSSIBLE COMMENTS
 EITHER ON PREVIOUS OR PRESENT REVIEW.
2007-07-07 19:08:062007-07-07 19:08:06
 **** UNSAT3RDREVIEW ****
  
 ** PLEASE SEE THERE ARE STILL SEVERAL ITEMS FROM THE
 TWO PREVIOUS REVIEWS WHICH STILL NEED TO BE ADDRESSED.
  
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON
 CHANGES AND REVISIONS NOW MADE TO PLANS WHICH WERE NOT
 ON PREVIOUS REVIEWED PLANS.
  
  
 1) NOTE:PLEASE SEE BOTH PREVIOUS REVIEWS REQUESTED
 FOR THE REQUIRED CODES TO BE STATED ON BOTH THE
 ARCHITECTURAL AND ELECTRICAL PLANS. PLEASE SEE THE ONLY
 CHANGE WAS MADE TO THE ARCHITECTURAL SHEETS AND THE
 ELECTRICAL SHEETS STILL CONTAIN THE SAME GENERAL
 STATEMENT.
 PLEASE SEE THAT RELEVANT CODES UNDER A DESIGN OF ANY
 PROJECT SHALL BE STATED ON PLANS AS REQUIRED UNDER THE
 FBC.
 PLEASE BE SURE THE FOLLOWING IS STATED ON THE
 ELECTRICAL SHEETS:
 2005 NFPA-70 (NEC
 2003 NFPA-101 LIFE SAFETY CODE
 2002 NFPA-72
 2004 FBC W/2006 REVISIONS.
 PLEASE STATE THESE CODE ON E COVER SHEETS OR ANY OTHER
 E-SHEET(S) WHERE NOTES ARE PRESENT REFLECTING THE CODE
  
  
 2) NOTE: PLEASE SEE THE PREVIOUS TWO REVIEWS REQUESTED
 COMPLIANCE TO FBC CHAPTER 13. THERE WERE SUBSTANTIAL
 CHANGES WHICH WENT INTO EFFECT ON OCTOBER 1ST, 2005.
 PLEASE SEE NOT SYSTEM IS PROPOSED, ONLY PLANS NOW
 INDICATE A SYMBOL IN AREAS FOR *MOTION DETECTORS*
 PLEASE SEE NO TIMES OR INFORMATION WAS PROVIDED FOR
 THESE NEW DEVICES AS NOTED PREVIOUSLY. NO DETAIL ON
 WIRING OF THESE DEVICES AS LIGHTING IS STILL SHOWN
 CIRCUITED BACK TO THE MAIN PANEL.
 PLEASE SEE NOT ALL AREAS SHOW MOTION DETECTORS OR
 OCCUPANCY DEVICES. PLEASE SPECIFY THESE DEVICES. PLEASE
 KNOW RANGES ON MOTION DEVICES ONLY ARE DIFFERENT AND
 MAY OR MAY NOT PROVIDE THE NEEDED COVERAGE. PLEASE SEE
 OTHER COMMENT WITH RESPECT TO STAIRS ON MOTION
 DETECTORS.
 PLEASE SEE SEPARATE SPACES WHICH REQUIRE DEVICES YET
 PLANS DO NOT INDICATE ANY DEVICES FOR THESE AREAS.
 PLEASE SEE THERE ARE MAXIMUM TIMES STATED IN THE FBC
 DEPENDING ON THE TYPES OF DEVICES CHOSEN. (OS TYPES
 30MINS)(TIMER TYPES 4HRS) THIS ALL DEPENDS ON DESIGN OF
 DEVICES ETC.
 PLEASE SEE THE SAME ENERGY CALCULATIONS WERE SUBMITTED
 BACK. PLEASE SEE THE RESPONSE MENTIONS HAVE BEEN
 PROPERLY SUBMITTED, HOWEVER PLEASE SEE NO INFORMATION
 PER 13-415.2 COULD BE FOUND ON PLANS AND OTHER
 DOCUMENTS SUBMITTED. PLEASE SEE THE FIXTURES AS SHOWN
 ON PLANS DO NOT ALL CORRELATE WITH THE FIXTURE LEGEND
 AND NO PERFORMANCE CALCULATIONS WERE LOCATED BASED ON
 THE FIXTURES ON PLANS AND SQ FT OF PROJECT ON HOW THE
 NUMBER OF 1.0 W/SF IS MET.
 THE DESIGN TOTAL COMPARED TO THE DESIGN ALLOWANCE BASED
 ON THE SECTION 13-415.2.C.1, 13-415.2.C.
 13-415.2.ABC.1.3
 PLEASE SEE AS THE SAME ENERGY CALCULATIONS FOR METHOD C
 WAS SUBMITTED BACK; PLEASE SEE THESE ARE STILL NOT
 SEALED AS REQUIRED AND PREVIOUSLY REQUESTED. PLEASE SEE
 13-415.1.ABC.1.1, 13-415.1.ABC.1.2, AND
 13-415.1.ABC.1.3 (WHERE APPLICABLE ON .1.3).PLEASE SEE
 13-103.1.1.1 WHICH REQUIRES THESE TO BE *SIGNED, DATED
 AND SEALED* BY THE DESIGN PROFESSIONAL OF RECORD AND
 RESPONSIBLE FOR THE DOCUMENTS.
 3) NOTE: PLEASE SEE PREVIOUS REVIEWS REQUESTED
 PHOTO-METRICS AND ANY CONTROLS TO MEET BOTH THE FBC AND
 NFPA-101 FOR DEVICES CHOSEN.
 PLEASE SEE THE PLANS NOW INDICATE ONLY ONE DEVICE ON
 EACH LEVEL FOR CONTROL OF EGRESS LIGHTING. PLEASE SEE
 7.9.2.2 OF THE LIFE SAFETY CODE WHICH WAS GIVEN ON BOTH
 OF THE PREVIOUS REVIEWS.
 FBC 1006.1.2, LS101 7.8.1.2.2
 PLEASE ADJUST.
  
 4) NOTE: PLEASE SEE FIRST REVIEW COMMENTS WHICH GAVE
 NOTES FOR REQUIRED DEDICATED CIRCUITS FOR ELEVATOR
 ROOMS, EQUIPMENT ETC. THE RESPONSE WAS THE EQUIPMENT
 ROOM WAS TO HAVE DEDICATED CIRCUITS ETC AND THIS WAS
 DONE. PLEASE SEE 620.24 HOWEVER AS THIS REQUIRES
 DEDICATE BRANCH CIRCUIT FOR PIT LIGHTS AND RECEPTACLES.
 PLEASE SEE THE LIGHTING IS STILL SHOWN ON THE SAME
 CIRCUIT AS THE LIGHTING ON FIRST FLOOR.
  
 5) NOTE: PLEASE SEE THAT SOME LOAD CALCULATIONS FOR
 SERVICE ARE NOW BEING SUBMITTED FOR THE FIRST TIME FOR
 REVIEW. PLEASE SEE NO LOAD SUMMARY ON HOW LOADS WERE
 DERIVED WAS SUBMITTED.
 PLEASE SEE CONTINUOUS LOADS AS REQUIRED ARE STILL NOT
 SHOWN AT 125%.
 PLEASE SUBMIT LOAD CALCULATIONS BASED ON FUTURE LOADS
 AND CURRENT KNOWN
 PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12,
 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS
 PREVIOUSLY NOTED.
 PLEASE CLARIFY WHERE THE *85%* AS SHOWN AS A DE-RATING
 FOR * EQUIPMENT* COMES FROM BASED ON THE NEC. PLEASE
 SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE AND EACH
 OF THE PANELS AS BEING SHOWN EVEN THOSE BEING SET ASIDE
 FOR FUTURE USE. PLEASE SEE THE ONLY PANEL SHOWN WHICH
 IS THE NHP AND THIS DOES NOT INCLUDE A LOAD SUMMARY OR
 HOW THE SERVICE WAS SIZED OR CORRECT LOAD CALCULATIONS
 FOR THIS PANEL OR SERVICE.
 PLEASE SEE NOTE #9 ABOVE AS THE SERVICE SIZE OR
 CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN
 NOT BE DETERMINED AT THIS TIME.
 PLEASE SEE ALL OF 220.
 PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
  
 6) NOTE: PLEASE SEE THE RISER AS SUBMITTED IS STILL NOT
 COMPLETE.
 PLEASE SEE NO INFORMATION FOR ANY OF THE PROPOSED MAINS
 IS SHOWN. ONLY ONE OF THE MAINS INDICATES IT WILL BE
 800AMPS.
 PLEASE SEE NO AIC RATINGS FOR EACH OF THE SERVICE
 EQUIPMENT AND MAIN WAS SUBMITTED. SOME AIC CALCULATIONS
 THESE WAS SUBMITTED. 110.9
 PLEASE SEE NO MAINS AS REQUIRED PER 230.70, 230.71,
 230.72, 230.76 AND 230.79 ETC WAS SHOWN.
 IN FACT PLEASE SEE THE RESPONSE LETTER NOW MENTIONS
 SPECIFICALLY THAT A NEW SHUNT TRIP AND SHUNT TRIP
 BREAKERS WAS ADDED. THE RISER NOW SHOWS THIS AND AS
 PREVIOUSLY STATED IN BOTH PREVIOUS REVIEWS MAIN MUST
 MEET 230.76 AND 230.79. SHUNT TRIP BREAKERS AND SHUNT
 TRIPS DO NOT MEET CODE. PLEASE KNOW THAT ALL MAINS AND
 MEANS OF DISCONNECT MUST CONTAIN A MANUAL MEANS OF
 DISCONNECT RATED FOR THE LOAD SERVED.
 PLEASE SEE THE LOCATION OF THESE MAINS SHALL BE LOCATED
 AT THE NEAREST POINT OF ENTRANCE INTO THE BUILDING.
 THIS IS A LIFE SAFETY HAZARD AND PROPERTY HAZARD. IF
 THERE IS A STRUCTURE FIRE FOR EXAMPLE AND THE ONLY WAY
 TO SHUT OFF THE POWER TO THE BUILDING IS LOCATED CLOSE
 TO THE CENTER OF THE BUILDING THIS WOULD NOT ONLY CAUSE
 A DELAY IT WOULD ALSO CREATE A HAZARD TO FIRE
 DEPARTMENT PERSONNEL IN AN EFFORT TO TURN OFF POWER.
 PLEASE SEE THERE ARE NUMEROUS ITEMS NOT COMPLETED ON
 RISER AT THIS TIME.
  
 ** AS A NOTE PANEL NHP IS GOING TO BE 800AMPS?
  
 7) NOTE: PLEASE SEE THE RISER STILL DOES NOT INDICATE
 THE GROUNDING ELECTRODE SYSTEM AS REQUIRED PER 250.50.
 PLEASE SEE THE RISER MENTIONS AND SHOWS ALL AS EXISTING
 HOWEVER THIS IS NOT POSSIBLE AS THE RISER JUST ABOVE
 WHICH SHOWS EXISTING CONDITIONS AND THIS DOES NOT
 CORRELATE WITH THE NEW PROPOSED RISER.
 HOW CAN THE GROUNDING ELECTRODE SYSTEM AS SHOWN BE
 EXISTING WHEN THE RISER AS SHOWN IS NEW?
 PLEASE ALSO SEE THAT 250.50 WHICH REQUIRES ALL FOOTER
 STEEL ETC TO BE PART OF THE GROUNDING ELECTRODE SYSTEM.
 PLEASE SEE THE ADDITION AND NEW FOOTER STEEL OR
 BUILDING STEEL ETC IS REQUIRED TO BE PART OF THE
 SYSTEM.
 PLEASE SHOW NEW SYSTEM.
 250.50,250.54, 250.56 ETC.
 PLEASE ALSO SEE AS PREVIOUSLY NOTED IN REVIEWS: THE
 RISER IS STILL SHOWING *EQUIPMENT GROUNDING CONDUCTORS*
 AHEAD OF THE FIRST MEANS OF DISCONNECT(S) WHICH IS NOT
 PERMITTED. THIS CONDITION AS SHOWN WOULD CREATE
 OBJECTIONABLE CURRENTS AS STATED IN 250.6.
 PLEASE SEE 250.24 AS THIS REQUIRES BONDING AT THE FIRST
 MEANS OF DISCONNECT. WHEN THE BONDING IS DONE AT THE
 FIRST MEANS OF DISCONNECT AS REQUIRED PER 250.24 AND IF
 AN *EQUIPMENT GROUNDING CONDUCTOR IS INSTALLED BEFORE
 THE FIRST MEANS OF DISCONNECT THEN THIS WOULD BE
 PARALLELING THE NEUTRAL. (OBJECTIONABLE CURRENTS)
 PLEASE ADJUST RISER.
  
 8) NOTE: PLEASE SEE ONLY ONE SET OF PLANS CONTAIN
 SHEETS FOR A LIGHTNING PROTECTION SYSTEM.
 PLEASE SUBMIT TWO COMPLETED SET OF PLANS ALONG WITH NEW
 SHEETS FOR REVISED COMMENTS AS WELL AS LIGHTNING
 PROTECTION SHEETS.
  
 9) NOTE: PLEASE SEE PREVIOUS REVIEWS STATED A NOTE
 WHICH SAID *PLEASE BE SURE TO CALL IF THERE ARE ANY
 QUESTIONS OR COMMENTS WITH RESPECT TO THE TYPED
 COMMENTS*. IT ALSO STATED * IF THERE ARE ANY COMMENT
 WHICH ARE NOT CLEAR IN ANY WAY, NOT UNDERSTOOD OR NOT
 TYPED IN A CLEAR MANOR, PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER*.
 PLEASE KNOW TO DATE NO CONTACT FROM THE DESIGNER OF
 RECORD HAS BEEN MADE.
 **PLEASE SEE PREVIOUS NOTES GAVE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 PLEASE SEE SEVERAL OF THE CODE SECTIONS GIVEN ON ALL
 PREVIOUS REVIEWS STILL REMAIN. PLEASE SEE AS REQUIRED
 PER THE FLORIDA STATUTES 553.80(2)(B), A FEE HAS NOW
 BEEN ASSESSED AS REQUIRED FOR SAID REPEAT COMMENTS.
 THIS STATUTE APPLIES TO ANY OF THE SAME CODE COMPLIANT
 COMMENTS REPEATED.
 PLEASE SEE THE AMOUNT DUE BEFORE PLANS MAY BE
 RESUBMITTED IS 4X TIMES THE PORTION OF THE BASE PERMIT
 FEE ATTRIBUTED TO PLAN REVIEW. THE BASE PERMIT FEE WAS
 $12,500 AT 30% IS $3,750 TIME FOUR.THIS FEE IS
 $15,000.00.
 THIS FEE IS REQUIRED BEFORE PLANS MAY BE SUBMITTED. **
 IT IS STRONGLY RECOMMENDED THAT A MEETING BE HELD
 BETWEEN THE DESIGN TEAM AND THIS OFFICE ONCE ALL OF THE
 REVIEWS HAVE BEEN COMPLETED AS THE STATUTE REQUIRES THE
 FINE EACH TIME THEREAFTER AS WELL.
 PLEASE KNOW THAT PLANS ARE BEING RETAINED BY THIS
 OFFICE AND WILL BE PLACED WITH PLANS WHICH WERE
 RETAINED FROM PREVIOUS REVIEWS.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ARE
 ALSO BEING RETAINED.
 PLEASE KNOW IF THERE IS A CONFLICT BETWEEN THE DESIGN
 TEAM OR DESIGNER WHICH IS NOT SETTLED ON A LOCAL LEVEL
 THE PLANS WILL BE FORWARD TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS AND STATES LEGAL COUNSEL TO THE
 BOARD FOR REVIEW.
 THIS INFORMATION WILL BE FORWARDED TO THE ASSISTANT
 BUILDING OFFICIAL MR. ROBERT BROWN.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-07 15:50:242007-07-07 15:50:24
 PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW
 IS COMPLETED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-15 Cont ID  
Sent By dpalmer Date 2007-04-15 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2007-04-15 Time 12:52 Sent To  
Notes
2007-04-15 14:53:31********* UNSAT2NDREVIEW ***********
  
 ** PLEASE SEE SOME ITEMS FROM THE THREE PREVIOUS
 REVIEWS ARE STILL IN NEED OF ADDRESSING. PLEASE SEE NEW
 COMMENTS DUE TO CHANGES IN PLANS OR BASED ON PAPERWORK
 AND DOCUMENTATION SUBMITTED NOT DONE BY ANY DESIGN
 PROFESSIONAL
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT
 CORRECT.
 PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN
 OCT 1ST OF 2005. PLEASE SEE THERE ARE SEVERAL CODES
 WHICH ARE STILL BEING REFLECTED FROM THE *2001 FBC* ,
 THE 2000 FLORIDA ACCESSIBILITY CODE ETC?
 PLEASE ALSO SEE THAT AS OF DECEMBER 8TH, 2006 THE
 CODES CHANGED TO THE 2006 REVISIONS TO THE 2004 FBC.
 PLEASE SEE THIS INCLUDES ALL MECHANICAL, PLUMBING
 BUILDING ETC.
 PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO
 ADOPTED THE NEW 2005 NFPA-70 (NEC).
 PLEASE SEE THE INCORRECT NFPA-101, 1 AND 72 ARE
 REFLECTED ALONG WITH THE INCORRECT NFPA-70 WHICH IS
 SHOWN AS THE 2002.
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL
 COVER SHEET AND ELECTRICAL PLANS AT A MINIMUM. 2005
 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 NFPA-1.
  
 ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY
 ALSO BE STATED TO BE DONE. THIS IS FOR ELECTRICAL
 REVIEW ONLY HOWEVER ALL CORRECTED CODES MUST BE STATED
 FOR DESIGN WHETHER OR NOT COMMENTS ARE MADE BY ANY OF
 THE OTHER TRADES.
  
 2) NOTE: PLEASE SEE THE END OF THE PREVIOUS REVIEW
 REQUESTED FOR ALL OLD/VOIDED SHEETS WHICH WERE BEING
 REPLACED TO BE REMOVED AND TO SUBMIT *ONE COPY* OF THE
 OLD/VOIDED SHEETS BACK WITH PLANS FOR REFERENCE. THE
 SHEETS WERE REMOVED HOWEVER NO OLD/VOIDED SHEETS WERE
 SUBMITTED BACK WITH PLANS?
 PLEASE SUBMIT ALL FOR THE NEXT REVIEW AS SHEETS WILL BE
 REQUIRED TO BE REMOVED AND REPLACED ON AGAIN.
  
 3) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2.
 THIS INFORMATION WHICH WAS SUBMITTED ON SEPARATE SHEETS
 SHALL BE PART OF THE PLANS, SIGNED, DATED AND SEALED BY
 THE RESPONSIBLE DESIGN PROFESSIONAL ALONG WITH TITLE
 BLOCK INFORMATION ON PLANS AND SHEETS. THESE WOULD BE
 INCORPORATED IN PLAN SETS NOT SUBMITTED AS LOOSE
 SHEETS.
 PLEASE ALSO THE INFORMATION ON SHEETS DOES NOT INDICATE
 WHAT THESE ARE FOR? PLEASE SEE THAT ONLY A WORST CASE
 IS BEING REQUESTED FOR BRANCH CIRCUITS AND FEEDERS.
 PLEASE KNOW THIS WOULD INCLUDE SITE WIRING. THE
 NUMERICAL DESIGNATIONS ON THESE SEPARATE SHEETS DO NOT
 INDICATE WHAT THEY ARE FOR?
 FBC 106.1.2, 106.3.5.1.2
 FS 471.025
  
 4) NOTE: PLEASE SUBMIT MINIMUM ENERGY CALCULATIONS AND
 PERFORMANCE CALCULATIONS BASED ON THE AREA BEING DONE
 AS A SHELL. PLEASE SEE 13-415.1.AB.1 AND 13-415.2.
 PLEASE SEE 13-101.1.6 FOR MINIMUM REQUIRED FOR SHELL AS
 METHOD *B* AND *C*. PLEASE SEE THE SINGLE SHEET
 SUBMITTED DOES NOT COORDINATE WITH ALL REQUIREMENTS
 FROM THE 2004 FBC W/ 2006 REVISION AND FLA-COM UPDATED
 FORM NUMBERS/METHODS.
 PLEASE SEE THE ENERGY CALCULATIONS SHALL CORRELATE WITH
 ALL FIXTURES AS SHOWN ON PLANS FOR DESIGN WATTAGE, TYPE
 OF CONTROLS ETC.
 PLEASE SEE 13-103.1.1.1 AS THE DESIGNER OF RECORD
 RESPONSIBLE FOR PLANS/DESIGNS/ENERGY CALCULATIONS MUST
 BE SIGNED, DATED AND SEALED AS STATED ON PREVIOUS
 REVIEW.
 * PLEASE KNOW THESE SHALL BE SIGNED, DATED AND SEALED,
 BY THE ENGINEER OF RECORD. 13-103.1.1.1
  
 5) NOTE: PLEASE SEE THAT THE REQUIRED DEVICES FOR ALL
 LIGHTING AND DETAIL FOR SYSTEM OR DEVICES WHICH ARE
 GOING TO BE INSTALLED AND LOCATIONS ARE NOT SHOWN ON
 PLANS FOR COMPLIANCE WITH CHAPTER 13 OF THE 2004 FBC W/
 2006 REVISIONS.
 PLEASE SEE THAT A SINGLE TC IS NOT THE ONLY ITEM
 NEEDED. PLEASE SEE THAT OVER-RIDE DEVICES ARE REQUIRED
 AT THE POINT OF ENTRANCE INTO SPACES AND THESE DEVICES
 A LIMITED TO TIME OF OVER-RIDE DEPENDING ON THE DEVICE
 WHICH IS SELECTED. PLEASE SEE ALL ROOMS AND SEPARATE
 SPACES SHALL ALSO CONTAIN DEVICES WHICH ARE NOT SHOWN
 AND MAXIMUM OVER RIDE TIMES.
 PLEASE SEE THE SAME SECTIONS AS NOTED ON PREVIOUS
 REVIEW.
 PLEASE SEE THAT LIGHTING CONTROLS ARE REQUIRED FOR
 AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE SEE FBC
 2004 (2006 REVISIONS) 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE ALSO SEE THE STAIR AREAS WHICH ARE STATED AS
 BEING LEFT IN THE *ON* POSITION WHICH DOES NOT MEET THE
 INTEND OF THE FLORIDAENERGY CODE OR REQUIRED MANDATES
 NATIONWIDE.
 PLEASE SEE THERE ARE SECTIONS ON THE FBC AND NFPA WHICH
 ADDRESS EGRESS PATHS AND STAIRS. PLEASE SEEFBC
 1006.1.2
  
 6) NOTE: PLEASE SEE THAT THE PLANS ARE MISSING THE
 REQUIRED EGRESS PHOTO-METRICS AS PREVIOUSLY REQUESTED
 AND REQUIRED PER NFPA-101 7.8.1.3, 7.9.2.2
 THE LOOSE SHEETS WHICH CONTAIN PHOTO-METRICS ARE DONE
 PART OF THE PLANS; THEY DO NOT INDICATE THE STAIR
 LIGHTING UNDER NORMAL OR EMERGENCY IN ANY FASHION WHICH
 IS THE MOST IMPORTANT AREAS. THEY ARE NOT SIGNED, DATED
 OR SEALED BY THE RESPONSIBLE DESIGNER OF RECORD AS
 REQUIRED PER FS 471.025
 THEY DO NOT INDICATE THE OTHER EGRESS PATHS UNDER
 NORMAL AND EMERGENCY CONDITIONS.
  
 PLEASE SHOW AND INDICATE THE MINIMUM LEVELS FOR
 SECTIONS BELOW, PLEASE SEE THE COMMENTS WITH RESPECT TO
 EGRESS LIGHTING AND CONTROLS FOR CHAPTER 13. PLEASE SEE
 SECTION 1006.1.2 OF THEFBC 2004 PLEASE SEE THE
 FOLLOWING TEXT WHICH WAS EXTRACTED DIRECTLY FROM
 NFPA-101.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTER 11
 THROUGH CHAPTER 42. FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND
 PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF
 THIS REQUIREMENT, EXIT DISCHARGE SHALL INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT PASSAGEWAYS LEADING TO A
 PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2.
 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 LOCATIONS AND FOR SUCH PERIODS OF TIME AS ARE NECESSARY
 TO MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA
 VALUES HEREIN SPECIFIED.
 7.8.1.2.2 AUTOMATIC, MOTION SENSOR, TYPE LIGHTING
 SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS,
 PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR
 FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET
 FOR A MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR
 IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA
 SERVED BY THE LIGHTING UNITS.
 7.8.1.3* THE FLOORS AND OTHER WALKING SURFACES WITHIN
 AN EXIT AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND
 EXIT DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE
 ILLUMINATED AS FOLLOWS:
 (1)DURING CONDITIONS OF STAIR USE, THE MINIMUM
 ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST 108 LUX
 (10 FT-CANDLE), MEASURED AT THE WALKING SURFACES. (2)
 THE MINIMUM ILLUMINATION FOR FLOORS AND WALKING
 SURFACES, OTHER THAN NEW STAIRS, SHALL BE TO VALUES OF
 AT LEAST 10.8 LUX (1 FT-CANDLE), MEASURED AT THE
 FLOOR.
 ***PLEASE ALSO SEE SECTION 7.9.2.2. WHERE THE FAILURE
 OF ANY SINGLE DEVICE OR LIGHTINGSHALL NOT LEAVE ANY
 ONE EGRESS AREA IN TOTAL DARKNESS. PLEASE PLACE DEVICES
 WHICH ARE TO CONTROL STAIRWAY LIGHTING FOR COVERAGE AND
 THAT A MINIMUM OF TWO DEVICES CONTROL ANY ONE AREA.
  
 7) NOTE: PLEASE SEE THE ELECTRICAL EQUIPMENT ROOM. THE
 LIGHT SWITCH IS LOCATED IN THE MIDDLE OF THE WALL WHERE
 THE ELECTRICAL EQUIPMENT IS LOCATED.
 PLEASE COORDINATE.
 FBC 106.1.2
  
 8) NOTE: PLEASE CORRELATE RISER AND PLANS FOR THE MAIN
 ELECTRICAL ROOM EQUIPMENT. PLEASE SEE THE PLANS
 INDICATE A 400A METER AND MAIN AND THE RISER INDICATES
 800AMP?
 PLEASE SEE THE LOCATION WILL REQUIRE FURTHER
 CONSULTATION WITH THE FIRE MARSHAL'S OFFICE AS THE
 LOCATION OF THE MAIN IS LOCATED INSIDE THE BUILDING
 THROUGH A MINIMUM OF THREE LOCKED DOORS WHICH AT THIS
 TIME IS TOO FAR INTO THE BUILDING FOR LIFE SAFETY AND
 READY ACCESS TO MAIN IN THE EVENT OF AN EMERGENCY OR TO
 SHUT OFF POWER DURING A FIRE.
 PLEASE SEE NEC 230.70, 90.4
 FBC 104.6
  
 9) NOTE: PLEASE SEE THAT THE RISER IS ONLY NOW BEING
 SUBMITTEDWITH MORE COMPLETEDINFORMATION FOR
 CONDUCTORS, CONDUITS ETC, HOWEVER THERE ARE STILL SOME
 ITEMS WHICH NEED TO BE INCLUDED FOR CODE COMPLIANCE AS
 PREVIOUSLY NOTED.
 PLEASE SEE THE RISER AS SUBMITTED IS STILL NOT COMPLETE
 AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT
 BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH
 ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING,
 SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC
 RATINGS FOR ALL SERVICE EQUIPMENT ETC.
 ** PLEASE SEE SOME OF THE ITEMS WHICH ARE STILL
 MISSING.
 A) NO GROUNDING ELECTRODE SYSTEM.
 B) NO AIC RATINGS FOR ALL SERVICE EQUIPMENT.
 C) AN EQUIPMENT GROUNDING CONDUCTOR MAY NOT BE
 INSTALLED BEFORE THE FIRST MEANS OF DISCONNECT AS NOW
 SHOWN ON RISER. (250.6, 250.24)
 D) LOADS CAN NOT BE VERIFIED FOR SERVICE RISER AS SHOWN
 WHICH WILL BE NOTED BELOW TO VERIFY IF THE CONDUCTORS
 ETC SHOWN ARE OF ADEQUATE SIZE ETC.
 SECTIONS AS GIVEN IN PREVIOUS REVIEW.
 ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70,
 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24,
 110.26 ETC.
 PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC.
  
 10) NOTE: PLEASE SEE PLANS MENTION A LOCK OFF/ON DEVICE
 IS TO BE INSTALLED HOWEVER NO NOTES COULD BE LOCATED
 FOR TYPE OF DEVICE WHICH IS REQUIRED TO BE INSTALLED AS
 NOTED ON PREVIOUS REVIEW.
 ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE
 SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL
 PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS
 NOT ACCEPTABLE TO THIS AHJ.
 110.3, 90.4.
  
 11) NOTE:PLEASE SEE THE SEPARATE SHEETS SUBMITTED FOR
 PANEL NHP DOES NOT PROVIDE THE REQUIRED AND REQUESTED
 INFORMATION FOR COMPLETE LOAD CALCULATIONS FOR SERVICE
 AND ALL EQUIPMENT BY THE DESIGNER OF RECORD.ALL
 INFORMATION SHALL BE INCLUDED IN RECORD SETS OF PLANS
 AND NOT SUBMITTED ON LOOSE SHEETS WHICH DO NOT CONTAIN
 THE COMPLETED INFORMATION OR DONE BY THE DESIGNER OR
 RECORD.
 PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12,
 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS
 PREVIOUSLY NOTED.
 PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE
 AND EACH OF THE PANELS AS BEING SHOWN EVEN THOSE BEING
 SET ASIDE FOR FUTURE USE. PLEASE SEE THE ONLY PANEL
 SHOWN WHICH IS THE NHP AND THIS DOES NOT INCLUDE A LOAD
 SUMMARY OR HOW THE SERVICE WAS SIZED OR CORRECT LOAD
 CALCULATIONS FOR THIS PANEL OR SERVICE.
 PLEASE SEE NOTE #9 ABOVE AS THE SERVICE SIZE OR
 CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN
 NOT BE DETERMINED AT THIS TIME.
 PLEASE SEE ALL OF 220.
 PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 12) NOTE: PLEASE SEE THIS SAME COMMENT FROM PREVIOUS
 REVIEW WHICH REMAINS AS NOT INFORMATION WAS SUBMITTED.
 PLEASE SEE NOTE ABOVE (#13) WHICH REQUEST THE AIC
 RATINGS FOR ALL EQUIPMENT. PLEASE BE SURE THESE
 CORRELATE WITH THE DIVISION SPEC SUBMITTED. 106.1.2.
 NEC 110.9
  
 13) NOTE: PLEASE CLARIFY PANEL NHP WHICH INDICATE MORE
 THAN 42 SPACES WHICH IS NOT PERMITTED PER 408.35.
 PLEASE PROVIDE MORE INFORMATION ON THIS PANEL AS THIS
 IS ONLY SHOWN AS WHAT APPEARS TO BE A TWO SECTION PANEL
 ON RISER AND RESPONSE MENTIONS THIS, HOWEVER PLANS,
 RISER AND PANEL SCHEDULE DOES NOT SHOW IF THIS FIRST
 SECTION CONTAINS FEED-THRU LUGS, FEEDERS, OCP ETC.
 PLEASE PROVIDE INFORMATION.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
  
 14) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) WHICH IS
 BEING ATTACHED WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 PLEASE SEE THIS IS GIVEN ONLY AS A NOTICE AT THIS
 TIME.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-30 Cont ID  
Sent By dpalmer Date 2007-01-30 Time 08:01 Rev Time 0.00
Received By dpalmer Date 2007-01-29 Time 12:49 Sent To  
Notes
2007-01-30 08:01:56*** UNSAT ****
  
 *** IMPORTANT***
 * PLEASE KNOW THAT BASED ON THE COMMENTS BELOW AND
 PLANS NOT BEING COMPLETE AT THIS TIME, WHEN PLANS ARE
 RESUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS MADE
 WHICH WERE NOT MADE ON THIS REVIEW.
  
 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT
 CORRECT.
 PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN
 OCT 1ST OF 2005. PLEASE ALSO SEE THAT AS OF DECEMBER
 8TH, 2006 THE CODES CHANGED TO THE 2006 REVISIONS TO
 THE 2004 FBC. PLEASE SEE THIS INCLUDES ALL MECHANICAL,
 PLUMBING BUILDING ETC.
 PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO
 ADOPTED THE NEW 2005 NFPA-70 (NEC).
 PLEASE SEE THE INCORRECT NFPA-101, 1 AND 72 ARE
 REFLECTED.
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL
 COVE SHEET AND ELECTRICAL PLANS AT A MINIMUM.
 2005 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003
 NFPA-1.
  
 ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY
 ALSO BE STATED TO BE DONE, THIS IS FOR ELECTRICAL
 REVIEW ONLY.
  
 2) NOTE: PLEASE SEE THAT THE BASE ELECTRICAL PLANS
 SHALL INDICATE THE MINIMUM LEVELS FOR ALL HORNS,
 STROBES, OR HORN/STROBE DEVICES AS REQUIRED UNDER FBC
 2004 11-4.28.1,.2 AND .3(4). THE PLANS NEED TO INDICATE
 THESE DEVICES ON THE SYMBOL LEGENDS AND CORRELATE WITH
 PLANS.
 PLEASE BE SURE ALL MINIMUM LEVELS AS REQUIRED ARE
 INDICATED.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 3) NOTE: PLEASE KNOW THAT THE LIGHTNING PROTECTION
 SYSTEM SHALL BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT.
  
 4) NOTE: PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION
 FOR ANY SITE LIGHTING POLES. PLEASE ALSO BE SURE THE
 INFORMATION PROVIDED SHALL INCLUDE THE EFFECTIVE
 PROJECTED AREA (EPA) OF THE FIXTURE. PLEASE KNOW THAT
 THE MINIMUM WIND LOAD FOR POLES SHALL BE STATED ON
 PLANS AND IF THE INFORMATION FOR THE POLE CALCULATIONS
 IS NOT KNOWN AT THIS TIME BASED ON WHETHER OR NOT THE
 MANUFACTURE HAS BEEN CHOSEN, THIS MAY BE SET UP AS A
 *PROVISO*, HOWEVER THE MINIMUM WIND SPEEDS SHALL BE ON
 PLANS.
 ** PLEASE SEE FBC 2004.
 FBC ADMIN SECTION 106.1.2
  
 5) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2.
  
 6) NOTE: PLEASE SUBMIT MINIMUM ENERGY CALCULATIONS AND
 PERFORMANCE CALCULATIONS BASED ON THE AREA BEING DONE
 AS A SHELL. PLEASE SEE 13-415.1.AB.1 AND 13-415.2. *
 PLEASE KNOW THESE SHALL BE SIGNED, DATED AND SEALED, BY
 THE ENGINEER OF RECORD. 13-103.1.1.1
  
 7) NOTE: PLEASE SEE THAT LIGHTING CONTROLS ARE REQUIRED
 FOR AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE SEE FBC
 2004 (2006 REVISIONS) 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 8) NOTE: PLEASE SEE MISSING DEDICATED EQUIPMENT ROOM
 FOR THE ELEVATOR. PLEASE SEE THE NEC 620. 620.22,
 620.23, 620.24 AND 620.51.
 PLEASE SEE MISSING THE DEDICATED CIRCUITS FOR THIS ROOM
 AND OTHER ELEVATOR RELATED LIGHTING ETC WHICH MAY NOT
 FEED ANY OTHER AREAS. PLEASE SEE PLANS INDICATE THESE
 CIRCUITS FEEDING OTHER LIGHTING OUTSIDE OF THESE
 AREAS.
 PLEASE ALSO SEE THE STATE ELEVATOR CODE.
 PLEASE ALSO PROVIDE MORE INFORMATION FOR THE ELEVATOR
 MOTOR ITSELF. PLEASE VERIFY THE CONDUCTORS ETC. 620.11,
 620.12 ETC.
  
 9) NOTE:PLEASE VERIFY THE LOCATION OF THE ROOF TOP
 GFI REQUIRED FOR A/ C EQUIPMENT PER 210.63 AND
 210.8(B)(3).
  
 10) NOTE: PLEASE PLACE ALL FIXTURE DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE SUBMITTED FIXTURE LEGEND.
 PLEASE KNOW THAT MANY AREAS CAN NOT BE VERIFIED AT THIS
 TIME.
 FBC 106.1.2.
  
 11) NOTE: PLEASE SEE MISSING EMERGENCY BATTERY BACK UP
 LIGHTS REQUIRED IN STAIRS, ELEVATOR EQUIPMENT ROOM,
 ELECTRICAL EQUIPMENT ROOM.
 NFPA-101 7.8, 7.9
 NFPA-70 700.16, AND 700.12E.
  
 12) NOTE: PLEASE SUBMIT AND PROVIDE PHOTO-METRICS FOR
 ALL EGRESS PATHS. PLEASE SEE NFPA-101 7.8.1.3,
 7.9.2.2.
  
 13) NOTE: PLEASE SEE RISER AS SUBMITTED IS NOT COMPLETE
 AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT
 BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH
 ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING,
 SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC
 RATINGS FOR ALL SERVICE EQUIPMENT ETC.
 ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70,
 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24,
 110.26 ETC.
 PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC.
  
 14) NOTE: PLEASE SEE NFPA-72 4.4.1 MORE SPECIFICALLY
 4.4.1.4.1, 4.4.1.4.2.1 AND .2.2.
 PLEASE INDICATE HOW THIS PROTECTION WILL BE PROVIDED
 FOR THE DEDICATE BRANCH CIRCUIT FOR THE FIRE ALARM
 CONTROL PANEL.
 ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE
 SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL
 PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS
 NOT ACCEPTABLE TO THIS AHJ.
 110.3, 90.4.
  
 16) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 SERVICE AND EACH OF THE PANELS AS BEING SHOWN EVEN
 THOSE BEING SET ASIDE FOR FUTURE USE. PLEASE SEE THE
 ONLY PANEL SHOWN WHICH IS THE NHP DOES NOT INCLUDE A
 LOAD SUMMARY OR HOW THE SERVICE WAS SIZED.
 PLEASE SEE NOTE #13 ABOVE AS THE SERVICE SIZE OR
 CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN
 NOT BE DETERMINED AT THIS TIME.
 PLEASE SEE ALL OF 220.
 PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 17) NOTE: PLEASE SEE NOTE ABOVE (#13) WHICH REQUEST THE
 AIC RATINGS FOR ALL EQUIPMENT. PLEASE BE SURE THESE
 CORRELATE WITH THE DIVISION SPEC SUBMITTED. 106.1.2.
 NEC 110.9
  
 18) NOTE: PLEASE CLARIFY PANEL NHP WHICH INDICATE MORE
 THAN 42 SPACES WHICH IS NOT PERMITTED PER 408.35.
 PLEASE PROVIDE MORE INFORMATION ON THIS PANEL AS THIS
 DOES NOT SHOW BEING A TWO SECTION OR CONTAINING
 FEED-THRU LUGS ETC.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-29 12:49:58IN ELEC FOR REVIEW (ONE ROLL) AND PERMIT APPLICATION.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status N Date 2007-11-29 Cont ID  
Sent By rchokshi Date 2007-11-29 Time 10:12 Rev Time 0.00
Received By rchokshi Date 2007-11-29 Time 10:12 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2007-09-14 Cont ID  
Sent By rchokshi Date 2007-09-14 Time 16:02 Rev Time 0.00
Received By rchokshi Date 2007-09-14 Time 16:01 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-07-24 Cont ID  
Sent By rchokshi Date 2007-07-24 Time 10:31 Rev Time 0.00
Received By rchokshi Date 2007-07-24 Time 10:05 Sent To  
Notes
2007-07-24 10:31:06***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA OF YOUR
 SITE, & 5,10, 25, 100 YEAR FLOOD CRITERIATO DETERMINE
 THE FIRST FLOOR ELEVATION, HOW DID YOU COME UP THE
 FIRST FLOOR ELEVATION,PLEASE SHOW THATIN YOUR STORM
 WATER CALCULATION.WE COULD NOT FIND WATER QUALITY
 CALS THAT YOU SAID YOU HAVE SUBMITTED. WE NEED A
 SEPARATE COPY OF WATER QUALITY CALS FOR THIS PROJECT TO
 KEEP IN THIS FILE.
 3. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST
 MATCH WITH AREAS USED IN STORM WATER QUALITY
 CALCULATIONS.
 4.WE COULD NOT FIND A COPY OF SFWMD PERMIT & A WATER
 QUALITY CALS THAT YOU SAID YOU SUBMITTED THIS TIME. WE
 SAW YOUR GEO TECH REPORT BUT WE COULD NOT FIND SOIL
 CONDUCTIVITY USED IN EXFILTRATION TRENCH. PLEASE
 RESUBMIT REVISED GEO TECH REPORT.
 5. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 6. PLEASE PROVIDE LATEST COPY OF SET OF CIVIL DRAWINGS
 WHEN YOU RESUBMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-02-15 Cont ID  
Sent By rchokshi Date 2007-02-15 Time 13:39 Rev Time 0.00
Received By rchokshi Date 2007-02-15 Time 13:24 Sent To  
Notes
2007-02-15 13:36:11PLEASE PROVIDE FOLLOWING INFO:
  
 1. PLEASE SHOW ON DRAWINGS, STANDARDS NOTES OF CITY OF
 WPB FOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY, APPROACH,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES
 ETC.,,MUST MEET ADA ETC.,ALL STANDARD NOTES OF CITY OF
 WPB CAN BE OBTAINED FROM 1000 45TH STREET, ENG DEPT.
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT, & GEOTECH
 REPORT
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL.PL.PROVIDE TOTAL PERVIOUS/IMPERVIOUS AREA.
 7. HOW DIDYOU CONNECT TO THE STORM WATER PIPES IN
 YOUR SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER
 PIPES AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE, NEED
 MORE THAN 2.5 FT HIGH SILT FENCE
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVE
 10. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status N Date 2008-03-03 Cont ID  
Sent By mawillia Date 2008-03-03 Time 14:57 Rev Time 0.00
Received By mawillia Date 2008-03-03 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-27 Cont ID  
Sent By mawillia Date 2007-07-27 Time 00:19 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 23:46 Sent To  
Notes
2007-07-27 00:18:48*****PROVISO*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN SATISFIED;HOWEVER THE APPROPIATE PLAN SHEETS
 WILL BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-08 Cont ID  
Sent By mawillia Date 2007-05-08 Time 15:56 Rev Time 0.00
Received By mawillia Date 2007-05-08 Time 15:21 Sent To  
Notes
2007-05-08 15:55:55*****UNSAT*****
  
  
 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH
 ACCESS TO THE FIRE HYDRANT, FIRE DEPARTMENT CONNECTION,
 OR ANY OTHER FIRE PROTECTION EQUIPMENT.COMMENT NOT
 FOUND ON SHEET LP-101 AS PER YOUR RESPONSE
  
 08.FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80.
 ADD COMMENT TO AN APPROPIATE PLAN SHEET
  
 12.KNOX LOCKING CAPS WILL BE REQUIRED FOR THE NEW
 FIRE DEPARTMENT CONNECTION (FDC).CONTACT WEST PALM
 BEACH FIRE PREVENTION (561-804-4724) FOR APPLICATIONS.
 ADD COMMENT TO AN APPROPIATE PLAN SHEET
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-21 Cont ID  
Sent By mawillia Date 2007-02-21 Time 10:47 Rev Time 0.00
Received By mawillia Date 2007-02-21 Time 10:47 Sent To Z
Notes
2007-02-21 16:01:57*****DENIED*****
  
  
 01.THE 2003 EDITION OF NFPA 101 AND THE FLORIDA FIRE
 PREVENTION CODE 2004 SHALL BE REFERENCED.SEE SHEET
 GV-101
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.FIRE DEPARTMENT ACCESS ROADS SHALL BE MAINTAINED
 THROUGHOUT CONSTRUCTION.
  
 04.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUNTLY AS NECESSARY FOR SAFE OPERATION.
  
 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH
 ACCESS TO THE FIRE HYDRANT, FIRE DEPARTMENT CONNECTION,
 OR ANY OTHER FIRE PROTECTION EQUIPMENT.
  
 06.WHEN/IF IT IS NECESSARY TO SHUT DOWN FIRE
 PROTECTION SYSTEMS, THE FIRE DEPARTMENT SHALL BE
 NOTIFIED WHEN IT IS SHUT DOWN AND WHEN IT IS RETURNED
 TO SERVICE.
  
 07.PROVIDE THE INTERIOR FINISH FOR THE NEW
 CONSTRUCTION.INTERIOR WALL AND CEILING FINISH
 MATERIAL SHALL BE CLASS A OR CLASS B FOR THE EXITS AND
 IN EXIT ACCESS CORRIDORS, AND SHALL BE CLASS A, CLASS
 B, OR CLASS C IN ALL OTHER AREAS.
  
 08.FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80.
  
 09.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW THE
 NUMERICAL ADDRESS ON THE BUILDING TO BE VISIBLE FROM
 GREENWOOD AVENUE.AS PER WEST PALM BEACH CODE, THOSE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.IF THE BUILDING IS SET-BACK FROM THE
 STREET OR ROADSIDE AND ARE NOT PLAINLY VISIBLE, A
 MONUMENT SIGN OR MARQUEE WITH THE ADDRESS WILL BE
 REQUIRED IN ADDITION TO THE BUILDING NUMBER.
  
 10.IF THE BUILDING IS EQUIPPED WITH A KNOX-BOX
 (KEY-ENTRY BOX), WILL THE DEVICE NEED TO BE RELOCATED
 AS PER THE SCOPE OF THE NEW CONSTRUCTION?IF SO,
 INDICATE LOCATION ON THE PLANS.
  
 11.THE EXISTING FIRE DEPARTMENT CONNECTION (FDC)
 SHALL NOT BE REMOVED AND CAPPED UNTIL SUCH TIME THAT
 THE NEW PIV AND FDC IS INSTALLED AND IN SERVICE.
  
 12.KNOX LOCKING CAPS WILL BE REQUIRED FOR THE NEW
 FIRE DEPARTMENT CONNECTION (FDC).CONTACT WEST PALM
 BEACH FIRE PREVENTION (561-804-4724) FOR APPLICATIONS.
  
 13.PROVIDE A LAYOUT OF THE EXISTINGFIRE ALARM SYTEM
 IN CONJUNCTION WITH THE NEW CONSTRUCTION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-07-24 Cont ID  
Sent By adarroug Date 2008-07-24 Time 10:06 Rev Time 0.00
Received By adarroug Date 2008-07-24 Time 10:06 Sent To B
Notes
2008-07-24 10:06:48TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-03-13 Cont ID  
Sent By adarroug Date 2008-03-13 Time 14:55 Rev Time 0.00
Received By adarroug Date 2008-03-13 Time 14:55 Sent To B
Notes
2008-03-13 14:56:05TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-02-12 Cont ID  
Sent By adarroug Date 2008-02-12 Time 14:29 Rev Time 0.00
Received By adarroug Date 2008-02-12 Time 14:29 Sent To  
Notes
2008-02-12 14:30:50TO "COMM" BD#8

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-09 Cont ID  
Sent By adarroug Date 2007-11-09 Time 10:58 Rev Time 0.00
Received By adarroug Date 2007-11-09 Time 10:58 Sent To  
Notes
2007-11-27 14:28:50TO "COMM" BD#33
2007-11-09 11:02:50WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-04 Cont ID  
Sent By adarroug Date 2007-10-04 Time 09:50 Rev Time 0.00
Received By adarroug Date 2007-10-04 Time 09:50 Sent To B
Notes
2007-10-04 09:51:23TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 10:06 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 10:06 Sent To  
Notes
2007-09-14 08:27:389-14-07--TO "RCHOKSHI" DESK/ PER "RBROWN"
2007-09-06 10:08:09WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 10:12 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 10:12 Sent To  
Notes
2007-07-12 14:40:50TO "COMM" BD#59
2007-07-03 10:13:10WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-28 Cont ID  
Sent By spalmer Date 2007-03-28 Time 18:29 Rev Time 0.00
Received By spalmer Date 2007-03-28 Time 18:29 Sent To  
Notes
2007-03-30 18:02:38TO COMM BOARD # 39
2007-03-28 18:30:13WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-21 Cont ID  
Sent By lfranco Date 2007-02-23 Time 18:31 Rev Time 0.00
Received By mawillia Date 2007-01-09 Time 09:25 Sent To  
Notes
2007-01-22 08:19:37TO "COMM" BD#62
2007-01-09 13:26:19WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-02-21 Cont ID  
Sent By rkussner Date 2008-02-21 Time 08:56 Rev Time 0.00
Received By rkussner Date 2008-02-21 Time 08:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-31 Cont ID  
Sent By rregueir Date 2007-07-31 Time 10:07 Rev Time 0.00
Received By rregueir Date 2007-07-31 Time 09:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-04-25 Cont ID  
Sent By rregueir Date 2007-04-25 Time 18:59 Rev Time 0.00
Received By rregueir Date 2007-04-25 Time 18:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-14 Cont ID  
Sent By rregueir Date 2007-02-14 Time 13:53 Rev Time 0.00
Received By rregueir Date 2007-02-13 Time 14:17 Sent To  
Notes
2007-02-14 13:57:53-----------------DENIED--------------------
  
 1. PG MM-501, DETAIL 1: PLEASE PROVIDE FLORIDA PRODUCT
 APPROVAL SHEETS FOR MANUFACTURED CONDENSING UNIT
 STANDS. ALSO PLEASE SHOW COMPLIANCE WITH CLEARANCE
 REQUIREMENTS OF FBC TABLE 1509.7.
  
 2. PLEASE PROVIDE A PLAN SHOWING FRESH AIR AND EXHAUST
 DUCT SIZES, ROUTING AND LOCATION OF 2ND FLOOR SLAB
 PENETRATIONS. IS THIS FLOOR RATED? ARE FIRE DAMPERS OR
 SHAFTS NEEDED AT THESE LOCATIONS? FBC 106.1.1
  
 3. PG MM-602 ELEVATOR MACHINE ROOM ACU SCHEDULE SHOWS 3
 SEPERATE SPLIT SYSTEMS BUT ONLY ONE IS SHOWN ON PLANS.
 PLEASE CLARIFY PER FBC 106.1.1
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-05-06 Cont ID  
Sent By mperson Date 2008-05-06 Time 11:07 Rev Time 0.00
Received By mperson Date 2008-05-06 Time 11:07 Sent To PC
Notes
2008-05-06 11:08:34RESTAMP SHEET PL-104: "OK"

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-03-03 Cont ID  
Sent By kstevens Date 2008-03-03 Time 16:11 Rev Time 0.00
Received By kstevens Date 2008-03-03 Time 16:11 Sent To  
Notes
2008-03-03 16:14:55REVISION DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. SHT L1-101 REVISION SUBMITTED INDICATES REVISION
 NUMBER ONE. REVISION SIGNED, SEALED & DATED 11-07-07
 ALSO INDICATES REVISION NUMBER ONE. EACH REVISION SHALL
 HAVE ITS OWN REVISION DESIGNATION NUMBER IN ORDER TO
 KEEP TRACK OF ALL REVISIONS. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-03-03 Cont ID  
Sent By kstevens Date 2008-03-03 Time 16:10 Rev Time 0.00
Received By kstevens Date 2008-03-03 Time 16:10 Sent To  
Notes
2008-03-03 16:10:59REVISION OK (NEW SHEET)--PL-104 PLUMBING PLAN
 RAINWATER HARVESTER

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-12-13 Cont ID  
Sent By kstevens Date 2007-12-13 Time 12:44 Rev Time 0.00
Received By kstevens Date 2007-12-13 Time 12:44 Sent To  
Notes
2007-12-13 12:45:04REVISIONS OK--SHTS LI-101 & PL-104 (NEW SHEET)

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-08-11 Cont ID  
Sent By kstevens Date 2007-08-11 Time 09:34 Rev Time 0.00
Received By kstevens Date 2007-08-10 Time 18:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-05-09 Cont ID  
Sent By kstevens Date 2007-05-09 Time 16:49 Rev Time 0.00
Received By kstevens Date 2007-05-09 Time 16:49 Sent To  
Notes
2007-05-09 17:16:08DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
  
 CORE/SHELL ONLY
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT GV-101 CODE REFERENCES ARE INCORRECT. THE CODE
 ADOPTED IS THE FBC-2004 WITH 2005, & 2006 REVISIONS.
 PLEASE INDICATE THE CORRECT CODE REFERENCE FOR DESIGN &
 CONSTRUCTION. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THERE ARE STILL SOME CODES
 DATED 2001, & 2000. ALL CODES SHALL REFLECT THE CODE IN
 EFFECT AT THIS TIME.
  
 2. OK
 3. OK
 4. OK
  
 5. SHT AF-103 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. INDICATE THE SQUARE FOOTAGE OF EACH AREA,
 PLUS 1/2 THE AREA OF ALL VERTICAL WALLS, INCLUDING
 PARAPETS, PLUS ANY ROOF AREA THAT DRAINS ONTO THE ROOF
 AREAS FROM ABOVE. IF SCUPPERS ARE USED, SUBMIT A DETAIL
 SHOWING THE LENGTH, WIDTH, AND THE MEASUREMENT FROM THE
 ROOF TO THE FLOW LINE OF THE SCUPPER. SECTION
 1503.4.2.
 ****RESPONSE NOTED, BUT SHT AF-103 SEEM TO INDICATE
 THAT THE CENTER OF THE ROOF IS EITHER THE HIGH POINT OR
 THE LOW POINT OF THE ROOF. PLEASE INDICATE THE SLOPE OF
 THE ROOF AND INDICATE HIGH & LOW POINTS OF THE ROOF.
 SECTION 106.2.1 (MORE INFORMATION REQUIRED).--THE
 SECONDARY ROOF DRAINS ARE NOT SHOWN ON THE MAIN ROOF
 PLAN. PLEASE INDICATE THE LOCATION OF THE SECONDARY
 ROOF DRAINS. IF THE SECONDARY ROOF DRAINS FOR THE MAIN
 ROOF ARE TO BE SCUPPERS, SUBMIT A DETAIL SHOWING THE
 HEIGHT, WIDTH, AND INDICATE THE HEIGHT OFF THE ROOF TO
 THE FLOW LINE. TABLE 1106.3 AND SECTIONS 1107.1 &
 1107.2 AND BUILDING CODE SECTION 1503.4.3
  
 6. INFORMATIONAL. IN PHASE III THE ACCESSIBILITY
 REQUIREMENTS WILL BE REQUIRED PER SECTIONS 11-4.15,
 11-4.16, 11-4.18, 11-4.19, 11-4.21, 11-4.22, AND
 11-4.24. ALSO NO DRINKING FOUNTAINS WERE SEEN.
 ****RESPONSE NOTED, OK
  
 7. IN PHASE III PLEASE SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1004.1.2 & 403.1.
 ****RESPONSE NOTED, OK
  
 **********NEW COMMENT**********
  
 1B. SUBMIT A STORM RISER ISOMETRIC DIAGRAM FOR THE NEW
 ROOFS. SECTION 106.3.5.1.3((7)(13).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-09 Cont ID  
Sent By kstevens Date 2007-02-09 Time 16:29 Rev Time 0.00
Received By kstevens Date 2007-02-09 Time 16:29 Sent To  
Notes
2007-02-09 17:11:24DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
  
 CORE/SHELL ONLY
  
 1. SHT GV-101 CODE REFERENCES ARE INCORRECT. THE CODE
 ADOPTED IS THE FBC-2004 WITH 2005, & 2006 REVISIONS.
 PLEASE INDICATE THE CORRECT CODE REFERENCE FOR DESIGN &
 CONSTRUCTION. SECTION 106.1.1.
  
 2. SHT CX-101 IS NOT SIGNED/SEALED/DATED. THE IS
 REQUIRED BY SECTION 106.1, THE FLORIDA ADMINISTRATIVE
 CODE, AND FLORIDA STATUTES.
  
 3. SHT CU-101 SHOWS A NEW 2-1/2" WATER SERVICE, BUT
 INDICATES ONLY A 2" RPZV BACKFLOW. TABLE 603.1(D)
 REQUIRES THE BACKFLOW TO BE AT LEAST THE SAME SIZE AS
 THE WATER LINE IN WHICH ITS INSTALLED. PLEASE SHOW
 PROPER SIZE BACKFLOW.
  
 4. SHT CU-101 UTILITY CROSSING NOTES. 1(B) & 2(A) NOTES
 STATE "THE MINIMUM HORIZONTAL SEPARATION DISTANCE
 BETWEEN WATERMAINS &GRAVITY SANITARY SEWERS TO BE
 REFUCED TO 3 FEET WHERE THE BOTTOM OF THE PIPE IS LAID
 AT LEAST 6" ABOVE THE TOP OF THE SEWER". SECTION 603.2
 EXCEPTION (1) REQUIRES THE SEPARATION DISTANCE TO BE A
 MINIMUM OF 12" WITHIN 5' OF THE SEWER.
  
 5. SHT AF-103 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. INDICATE THE SQUARE FOOTAGE OF EACH AREA,
 PLUS 1/2 THE AREA OF ALL VERTICAL WALLS, INCLUDING
 PARAPETS, PLUS ANY ROOF AREA THAT DRAINS ONTO THE ROOF
 AREAS FROM ABOVE. IF SCUPPERS ARE USED, SUBMIT A DETAIL
 SHOWING THE LENGTH, WIDTH, AND THE MEASUREMENT FROM THE
 ROOF TO THE FLOW LINE OF THE SCUPPER. SECTION
 1503.4.2.
  
 6. INFORMATIONAL. IN PHASE III THE ACCESSIBILITY
 REQUIREMENTS WILL BE REQUIRED PER SECTIONS 11-4.15,
 11-4.16, 11-4.18, 11-4.19, 11-4.21, 11-4.22, AND
 11-4.24. ALSO NO DRINKING FOUNTAINS WERE SEEN.
  
 7. IN PHASE III PLEASE SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1004.1.2 & 403.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2008-02-20 Cont ID  
Sent By lfranco Date 2008-02-20 Time 15:54 Rev Time 0.00
Received By lfranco Date 2008-02-20 Time 15:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2007-12-11 Cont ID  
Sent By lfranco Date 2007-12-11 Time 11:08 Rev Time 0.00
Received By lfranco Date 2007-12-10 Time 11:08 Sent To  
Notes
2007-12-11 11:18:48PLANNING AND ZONING: **** FAILED****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THE PROJECT IS PART OF THE ST. MARY'S CSPD AND IS
 CURRENTLY BEING REVIEWED FOR A MINOR PD AMENDMENT DUE
 TO RELOCATION OF SOME PARKING SPACES AND THE ADDITION
 OF A PLAYGROUND AREA.THIS PERMIT CANNOT BE APPROVED
 UNTIL FINAL APPROVAL OF THE MINOR AMENDMENT HAS BEEN
 MADE BY THE PLANNING AND ZONING DEPARTMENT DUE TO
 PERTINENT CHANGES THAT WILL NEED TO BE REFLECTED ON
 THIS PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-07-26 Cont ID  
Sent By lfranco Date 2007-07-26 Time 17:28 Rev Time 0.00
Received By lfranco Date 2007-07-26 Time 17:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-04-12 Cont ID  
Sent By lfranco Date 2007-04-12 Time 10:22 Rev Time 0.00
Received By lfranco Date 2007-04-05 Time 19:41 Sent To  
Notes
2007-04-13 10:23:48PLANNING AND ZONING:****** FAILED *******
  
 1PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
 2. THE SITE PLANS/DRAWINGS DO NOT MATCH THE APPROVED
 SITE PLAN/DRAWINGS FROM THE PLANNING AND ZONING
 DEPARTMENT (I.E. ENGINEERING (PARKING DETAILS DO NOT
 COMPLY WITH ZONING CODE). FOR EXAMPLE, SHEET CS-101
 "AREA OF DEVELOPMENT PLAN" SHOWS A 7 FEET-4 INCHES HIGH
 DUMPSTER ENCLOSUREVERSUS THE APPROVED 6 FOOT HIGH
 DUMPSTER ENCLOSURE SHOWN ON SHEET SP-1 OF THE ST.
 MARY'S MINOR AMENDMENT 1068P, APPROVED PLANS FROM THE
 PLANNING AND ZONING DEPARTMENT. IN ADDITION, PROVIDE A
 COPY OF THE PLANNING AND ZONING DEPARTMENT'S APPROVED
 PLANS, WITH EACH PACKET SUBMITTED.ALL DRAWINGS SHALL
 MATCH THESE DRAWINGS.
  
 3.SHEET CS-501 - THE HANDICAP PARKING STALL DETAIL
 DOES NOT COMPLY WITH ZONING CODE, SECTION 94-485, SEE
 ATTACHED DETAILS.FOR EXAMPLE,
  
 A.THERE SHALL BE 2 FEET IN BETWEEN THE BACK OF
 WHEEL STOP TO EDGE OF CURB.
 B.THE PAVEMENT SYMBOL SHALL BE WHITE IN COLOR
 AND 2 FEET FROM THE BOTTOM EDGE OF STALL.
  
 SHOULD YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 OFFICE: (561) 822-1443

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-23 Cont ID  
Sent By lfranco Date 2007-02-23 Time 18:30 Rev Time 0.00
Received By lfranco Date 2007-02-23 Time 18:30 Sent To I
Notes
2007-02-23 18:37:02PLANNING AND ZONING:****** FAILED *******
  
 1PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
 2. THE SITE PLANS/DRAWINGS DO NOT MATCH THE APPROVED
 SITE PLAN/DRAWINGS FROM THE PLANNING AND ZONING
 DEPARTMENT (I.E. THE LANDSCAPE PLAN, ENGINEERING
 (PARKING DETAILS DO NOT COMPLY WITH ZONING CODE),
 ARCHITECTUAL)
  
 SHOULD YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 OFFICE: (561) 822-1443