Plan Review Details - Permit 07010435
Plan Review Stops For Permit 07010435
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-07-20 Cont ID  
Sent By jwitmer Date 2007-03-29 Time 10:51 Rev Time 0.00
Received By jwitmer Date 2007-07-20 Time 09:44 Sent To PC
Notes
2007-01-09 11:20:13PAPA SHOWS DIFFERENT ADDRESS, PER LMARTINEZ-COPY OF
 APPL SENT TO LILI

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-07-20 Cont ID  
Sent By jwitmer Date 2007-07-20 Time 10:28 Rev Time 1.22
Received By jwitmer Date 2007-07-20 Time 09:44 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-05-02 Cont ID  
Sent By jwitmer Date 2007-05-02 Time 11:20 Rev Time 1.22
Received By jwitmer Date 2007-05-02 Time 11:20 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-29 Cont ID  
Sent By jwitmer Date 2007-03-29 Time 10:52 Rev Time 1.11
Received By jwitmer Date 2007-03-29 Time 10:52 Sent To  
Notes
2007-03-29 10:59:40PERMIT: 07010435
 ADD: 4920 LORING DR
 CONT: DYNAMIC SOUTH, INC
 TEL: (239)283-3338
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3A) 2ND REQUEST,SHEET A-3A PLANS INDICATE A ENLARGED
 EQUIPMENT PLANS, PLANS DO NOT INDICATE WHERE THE
 BATTERY CABINETS ARE LOCATED? STRUCTURAL PLAN ALSO
 INDICATES
 2900 LBS EACH, HOW MANY BATTERY CABINETS ARE THERE?
  
 3B) 2ND REQUEST,PLEASE PROVIDE WHAT OCCUPANCY
 CLASSIFICATION THIS PENTHOUSE IS CLASSIFIED AS?
 TABLE302.1.1
 307.9 EXCEPTIONS (11)
 STATIONARY BATTERIES UTILIZED FOR FACILITY EMERGENCY
 POWER, UNINTERRUPTED POWER SUPPLY OR TELECOMMUNICATION
 FACILITIES PROVIDED THAT THE BATTERIES ARE PROVIDED
 WITH SAFETY VENTING CAPS AND VENTILATION IS PROVIDED IN
 ACCORDANCE WITH THE F LORIDA BUILDING CODE, MECHANICAL
 .
  
 4) 2ND REQUEST,WHAT TYPE OCCUPANCY IS BELOW THIS
 LEVEL PROVIDE THE RATED ASSEMBLY FOR THE FLOOR CEILING
 ASSEMBLY.
  
 5A)2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5B) 2ND REQUEST,WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 C) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 LOUVERED DOOR
 WALL LOUVER - PROVIDE THE FLORIDA COVERSHEET AND
 ASSOCIATED NOA.
  
 6) 2ND REQUEST, PLEASE PROVIDE THE POSITIVE AND
 NEGATIVE PRESSURES FOR THE NEW OPENINGS
 NOTE > 60'-0" ABOVE GRADE NEEDS TO REFLECT DESIGNED TO
 ASCE 7-02,
 1609.1.1
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-05 Cont ID  
Sent By jwitmer Date 2007-02-05 Time 13:46 Rev Time 2.22
Received By jwitmer Date 2007-02-05 Time 13:46 Sent To  
Notes
2007-02-05 14:20:23BUILDING PLAN REVIEW
 PERMIT: 07010435
 ADD: 4920 LORING DR
 CONT: DYNAMIC SOUTH, INC
 TEL: (239)283-3338
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3A)SHEET A-3A PLANS INDICATE A ENLARGED EQUIPMENT
 PLANS, PLANS DO NOT INDICATE WHERE THE BATTERY CABINETS
 ARE LOCATED? STRUCTURAL PLAN ALSO INDICATES
 2900 LBS EACH, HOW MANY BATTERY CABINETS ARE THERE?
  
 3B)PLEASE PROVIDE WHAT OCCUPANCY CLASSIFICATION THIS
 PENTHOUSE IS CLASSIFIED AS? TABLE302.1.1
 307.9 EXCEPTIONS (11)
 STATIONARY BATTERIES UTILIZED FOR FACILITY EMERGENCY
 POWER, UNINTERRUPTED POWER SUPPLY OR TELECOMMUNICATION
 FACILITIES PROVIDED THAT THE BATTERIES ARE PROVIDED
 WITH SAFETY VENTING CAPS AND VENTILATION IS PROVIDED IN
 ACCORDANCE WITH THE F LORIDA BUILDING CODE, MECHANICAL
 .
  
 4) WHAT YPE OCCUPANCY IS BELOW THIS LEVEL PROVIDE THE
 RATED ASSEMBLY FOR THE FLOOR CEILING ASSEMBLY.
  
 5A)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5B)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 C) FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 LOUVERED DOOR
 WALL LOUVER
  
 6) PLEASE PROVIDE THE POSITIVE AND NEGATIVE PRESSURES
 FOR THE NEW OPENINGS
 NOTE > 60'-0" ABOVE GRADE NEEDS TO REFLECT DESIGNED TO
 ASCE 7-02,
 1609.1.1
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-06-23 Cont ID  
Sent By dpalmer Date 2007-06-23 Time 21:01 Rev Time 0.00
Received By dpalmer Date 2007-06-23 Time 20:48 Sent To  
Notes
2007-06-23 21:03:35**NOTES REDLINED ON PLANS.
 SIGNS WILL BE REQUIRED NOT ONLY AS NOTED ON PLANS,
 HOWEVER WILL BE REQUIRED IN MAIN ELECTRICAL ROOM, FIRE
 COMMAND ROOM ( IF APPLICABLE) FIRE ALARM/PANEL
 LOCATIONS.
 230.2E, 702.8

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-08 Cont ID  
Sent By dpalmer Date 2007-04-08 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2007-04-08 Time 11:32 Sent To  
Notes
2007-04-08 11:32:55 
 ** UNSAT **
  
 1) NOTE: PLEASE SEE THE VALUE FOR SCOPE OF WORK HAS
 BEEN INCREASED AND THE BALANCE OF FEES WILL BE REQUIRED
 TO BE PAID BEFORE ISSUANCE. THIS WILL NOT PREVENT PLANS
 FROM BEING STAMPED.
  
 2) NOTE: PLEASE SEE THESE PLANS ARE NOW SHOWING FOR THE
 FIRST TIME THE DISTANCE OF THE EXISTING MAIN ELECTRICAL
 ROOM AND NEW LOCATION FOR THE GENERATOR CONNECTION.
 PLEASE KNOW AS PER THIS AHJ AND THE FIRE MARSHAL'S
 OFFICE, IN THE INTEREST OF LIFE SAFETY FOR TIME AND
 SAFETY, THE DISTANCE OF TRAVEL IS FURTHER THAN WHAT IS
 ACCEPTABLE.
 PLEASE PROVIDE A CLOSER LOCATION FOR THIS.
 FBC 104.6
 225.31-225.39
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-04 Cont ID  
Sent By dpalmer Date 2007-03-04 Time 07:55 Rev Time 0.00
Received By dpalmer Date 2007-03-02 Time 19:16 Sent To  
Notes
2007-03-04 07:55:53*** UNSAT 2ND REVIEW**
  
 * PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL NEED
 TO BE ADDRESSED.
  
 1) NOTE: OK.
  
 2) NOTE: NO,
 PLEASE SEE THAT THE SCOPE OF WORK SHALL INCLUDE ALL
 LABOR AND MATERIALS EVEN IF EQUIPMENT IS OWNER
 SUPPLIED. THE SCOPE OF WORK AND MATERIALS/EQUIPMENT AS
 SHOWN WILL BE ASSESSED VALUES PER TABLES IN EVALUATION
 BOOKS ADOPTED BY THE FBC. PLEASE SEE THE SCOPE SEEMS
 LOW. PLEASE ADJUST.
 FBC 108.3
  
 3) NOTE: NO,THE NOTES ADDED ON PLANS FOR ONE OF THE
 SUB ELECTRICAL ROOMS TO ADD SIGNAGE IS NOT ALL THAT IS
 REQUIRED TO BE SHOWN ON PLANS. TRAVEL DISTANCE AND
 LOCATION OF ALL DISCONNECTING MEANS FOR POWER TO THIS
 STRUCTURE WILL BE DETERMINED BY THIS OFFICE FOR THE
 LIFE SAFETY ASPECT OF TRAVEL DISTANCE, TIME ETC.
 PLEASE CLARIFY THE LOCATION OF EXISTING MAIN ELECTRICAL
 ROOM. PLEASE SEE THE REQUIRED MEANS OF DISCONNECT FOR
 THE FEED FROM THE GENERATOR COULD NOT BE LOCATED.
 PLEASE SEE SIGNAGE ETC.
 225.31-225.39, 701OR 702
  
 4) NOTE: NO, A RESPONSE LETTER OR INFORMATION WAS NOT
 PROVIDED TO SHOW OTHER WISE.
 PLEASE SUBMIT INFORMATION AS PREVIOUSLY REQUESTED.
 PLEASE CLARIFY THE REQUIREMENTS UNDER FLORIDA STATUES
 WHICH NOW REQUIRES BACK UP POWER FOR THESE SYSTEMS AS
 LEGALLY REQUIRED. IF THIS IS THE CASE AS STATED, WOULD
 NOT THE LEGALLY REQUIRED BACK UP BE PERMANENT?
 PLEASE SEE NFPA-110,NFPA-70 701
  
 5) NOTE: NO, PLEASE SEE THE PLANS STILL CONTAIN THE
 SAME NOTE AND THE INFORMATION AS REQUIRED AND REQUESTED
 IS NOT ON PLANS. THIS LOAD INFORMATION IS REQUIRED AT
 THIS TIME AND TO BE ON PLANS AND THE RESPONSIBILITY OF
 THE DESIGNER OF RECORD.
 PLEASE SUBMIT THE LOADS ON THE EXISTING EQUIPMENT
 WHICH THE NEW LOADS ARE BEING ADDED. THE NOTE WHICH
 MENTIONS THAT THE CONTRACTOR SHALL PROVIDE READINGS,
 LOAD TESTING ETC IS NOT PERMITTED. THIS MUST BE DONE AT
 THIS TIME BEFORE ISSUANCE PERMIT AND THIS INFORMATION
 MUST BE PART OF THE DESIGN AND STATED ON PLANS.
 220.87.
 FBC 106.1.2, 106.3.5.1.2
  
 NOTES 6-9 ARE OK OR NOT APPLICABLE FOR THIS REVIEWER AT
 THIS TIME.
  
 ** PLEASE KNOW THAT A TYPED WRITTEN RESPONSE EXPLAINING
 ANY OF THE COMMENTS OR HOW THE COMMENT WAS ADDRESSED
 WOULD HELP IN THE REVIEW PROCESS.
 PLEASE KNOW THAT ALL DOCUMENTATION SHALL BEAR THE NAME,
 SIGNATURE AND SEAL FROM THE DESIGNER OF RECORD.
 FS 471.023, FAC 61G15-23.002
  
 **PLEASE CLARIFY AND SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS, OR IF THERE ANY
 COMMENTS ON THE NOTES TYPE ON REVIEW, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-21 Cont ID  
Sent By dpalmer Date 2007-01-21 Time 11:47 Rev Time 0.00
Received By dpalmer Date 2007-01-21 Time 10:00 Sent To  
Notes
2007-01-21 11:50:22** UNSAT **
  
 1) NOTE: PLEASE STATE ALL OF THE FOLLOWING RELEVANT
 CODES ON PLANS. PLEASE SEE AS OF DECEMBER 8TH, 2006 THE
 STATE OF FLORIDA ADOPTED THE 2005 NFPA-70. PLEASE SEE
 THE PLANS NOTES A 2003 NEC. PLEASE KNOW THERE WAS THE
 2002.
 PLEASE ALSO LIST THE 2002 NFPA-72 AND THE 2003
 NFPA-101.
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL BE SHOWN FOR ALL LABOR AND MATERIALS EVEN IF
 EQUIPMENT IS OWNER SUPPLIED..
 FBC 108.3
  
 3) NOTE: PLEASE CLARIFY THE LOCATION OF EXISTING MAIN
 ELECTRICAL ROOM. PLEASE SEE THE REQUIRED MEANS OF
 DISCONNECT FOR THE FEED FROM THE GENERATOR COULD NOT BE
 LOCATED.
 PLEASE SEE SIGNAGE ETC.
 225.31-225.39, 701OR 702
  
 4) NOTE: PLEASE CLARIFY THE REQUIREMENTS UNDER FLORIDA
 STATUES WHICH NOW REQUIRES BACK UP POWER FOR THESE
 SYSTEMS AS LEGALLY REQUIRED. IF THIS IS THE CASE AS
 STATED, WOULD NOT THE LEGALLY REQUIRED BACK UP BE
 PERMANENT?
 PLEASE SEE NFPA-110,NFPA-70 701
  
 5) NOTE: PLEASE SUBMIT THE LOADS ON THE EXISTING
 EQUIPMENT WHICH THE NEW LOADS ARE BEING ADDED. THE NOTE
 WHICH MENTIONS THAT THE CONTRACTOR SHALL PROVIDE
 READINGS, LOAD TESTING ETC IS NOT PERMITTED. THIS MUST
 BE DONE AT THIS TIME BEFORE ISSUANCE PERMIT AND THIS
 INFORMATION MUST BE PART OF THE DESIGN AND STATED ON
 PLANS.
 220.87.
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE BUILDING REVIEW NOTES PERTAINING TO
 PRODUCT DATA SUBMITTALS WHICH WERE NOT SUBMITTED WITH
 PLANS.
 ONLY NOTED.
  
 7) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PANEL/TRANSFER SWITCH. PLEASE BE SURE
 THIS CONTAINS A LISTING FROM A NRTL.
 110.3, 90.7, 701.7
  
 8) NOTE: PLEASE CLARIFY AN EQUIPMENT GROUND FROM THE
 *6SDL* TO THE EMON METER AND DISCONNECT. PLEASE CLARIFY
 AS THE CONDUITS ON SHEETS CONTAINING SOME OF THESE WITH
 EQUIPMENT GROUNDING AND SOME DO NOT?
 250.110, 250.24, 250.122
  
 9) NOTE: PLEASE SEE THE ADDRESS DOES NOT CORRELATE WITH
 THE APPLIED LOCATION, PLANS AND THE PALM BEACH COUNTY
 PROPERTY APPRIASERS. THIS HAS BEEN ROUTED TO THE
 ADDRESSING PERSON AND ONCE THE FINAL ADDRESS IS
 DETERMINED, PLEASE BE SURE THE PLANS CONTAIN THE ACTAUL
 ADDRESS IN THE TITLE BLOCKS.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
 **PLEASE CLARIFY AND SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS, OR IF THERE ANY
 COMMENTS ON THE NOTES TYPE ON REVIEW, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-12 Cont ID  
Sent By mawillia Date 2007-07-12 Time 11:41 Rev Time 0.00
Received By mawillia Date 2007-07-12 Time 11:11 Sent To  
Notes
2007-07-12 11:22:55*****PROVISO*****
  
  
  
 THERE SHALL BE NO PENETRATIONS INTO, AND OPENINGS
 THROUGH, AN EXIT ENCLOSURE ASSEMBLY EXCEPT AS PER NFPA
 101 (2003 EDITION) 7.1.3.2.1(6).
  
 PLAN SHEET A-1, A-2, AND A-3 STAMPED, INITIALED, AND
 DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-03-22 Cont ID  
Sent By mawillia Date 2007-03-22 Time 10:59 Rev Time 0.00
Received By mawillia Date 2007-03-22 Time 10:55 Sent To  
Notes
2007-03-22 10:59:01*****PROVISO*****
  
  
  
 THERE SHALL BE NO PENETRATIONS INTO, AND OPENINGS
 THROUGH, AN EXIT ENCLOSURE ASSEMBLY EXCEPT AS PER NFPA
 101 (2003 EDITION) 7.1.3.2.1(6).
  
 THE APPROPIATE PLAN SHEET(S) WILL BE STAMPED ONCE ALL
 OTHER PLAN REVIEWS HAVE BEEN SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-02-07 Cont ID  
Sent By mawillia Date 2007-02-07 Time 19:37 Rev Time 0.00
Received By mawillia Date 2007-02-07 Time 19:37 Sent To  
Notes
2007-02-07 19:47:36*****PROVISO*****
  
  
  
 THERE SHALL BE NO PENETRATIONS INTO, AND OPENINGS
 THROUGH, AN EXIT ENCLOSURE ASSEMBLY EXCEPT AS PER NFPA
 101 (2003 EDITION) 7.1.3.2.1(6).
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 09:58 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 09:58 Sent To  
Notes
2007-06-26 13:30:00TO "COMM" BD#28
2007-06-07 09:58:59WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 19:06 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 19:06 Sent To  
Notes
2007-03-30 19:06:34TO COMM BOARD # 8

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 18:41 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 18:41 Sent To  
Notes
2007-03-29 18:41:59WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-20 Cont ID  
Sent By adarroug Date 2007-02-20 Time 10:27 Rev Time 0.00
Received By adarroug Date 2007-02-20 Time 10:27 Sent To  
Notes
2007-02-26 13:24:02TO "COMM" BD#30
2007-02-20 10:27:16WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-07 Cont ID  
Sent By mawillia Date 2007-02-07 Time 19:36 Rev Time 0.00
Received By mawillia Date 2007-01-09 Time 11:20 Sent To  
Notes
2007-01-19 09:41:03TO "COMM" BD#7
2007-01-09 11:20:31WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-06-25 Cont ID  
Sent By tgordon Date 2007-06-25 Time 15:59 Rev Time 0.30
Received By tgordon Date 2007-06-25 Time 15:59 Sent To  
Notes
2007-06-25 16:00:52REVIEWED ON 4-6-07 AND STAMPED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-04-06 Cont ID  
Sent By tgordon Date 2007-04-06 Time 11:22 Rev Time 0.20
Received By tgordon Date 2007-04-06 Time 11:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-07 Cont ID  
Sent By tgordon Date 2007-03-07 Time 10:55 Rev Time 0.25
Received By tgordon Date 2007-03-07 Time 10:55 Sent To  
Notes
2007-03-07 10:59:34*** DENIED ***
 1) MORRISON HERSHFIELD CORP. CERTIFICATE OF
 AUTHORIZATION HAS EXPIRED, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By tgordon Date 2007-01-22 Time 14:10 Rev Time 0.25
Received By tgordon Date 2007-01-22 Time 14:10 Sent To  
Notes
2007-01-22 14:17:51*** DENIED ***
 1) PLEASE SUBMIT A PRODUCT APPROVAL FOR THE LOUVERED
 VENT LV1. PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 EXHAUST FAN EF1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-06-26 Cont ID  
Sent By eschneid Date 2007-06-26 Time 13:36 Rev Time 0.00
Received By eschneid Date 2007-06-26 Time 13:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-01-23 Cont ID  
Sent By eschneid Date 2007-01-23 Time 11:35 Rev Time 0.00
Received By eschneid Date 2007-01-23 Time 11:35 Sent To  
Notes
***NONE***