Plan Review Details - Permit 07010426
Plan Review Stops For Permit 07010426
Review Stop AD ADDRESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-01-05 Cont ID  
Sent By lursu Date 2007-01-05 Time 13:13 Rev Time 0.00
Received By jleech Date 2007-01-17 Time 15:03 Sent To  
Notes
2007-01-05 13:14:38PERMIT HAS BEEN ATTACHED TO THE CORRECT SITE ADDRESS (
 4619 GEORGIA AVE ) AND PCN ( 74 43 44 04 13 000 1070).
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-13 Cont ID  
Sent By mjacobs Date 2007-06-13 Time 17:51 Rev Time 0.00
Received By mjacobs Date 2007-06-13 Time 16:09 Sent To  
Notes
2007-06-13 17:51:11BUILDING PLAN REVIEW
 PERMIT: 07010426
 ADD: 4619 GEORGIA AVE.
 CONT: STONE IMAGE INC.
 TEL: (561)547-1177
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)NOTE: THE DRAWINGS STATE THE 2006 FBC WITH REV. TO
 2004. THIS IS INCORRECT. WE AREUSING THE 2004 FBC
 WITH 2006 FBC REV. REVISE SHEET A-1 TO SHOW THE CORRECT
 INFORMATION.
  
 3) REPEAT: 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE PRODUCT APPROVALS FOR
 THE ROOFING MATERIALS/EXTERIOR DOOR / PRECAST LINTEL
 AND WINDOWS ETC.
 FLORIDA STATUTES 489.113(3)A CONTRACTOR SHALL
 BUBVONTRACT ALL ELECTRICAL, MECHANICAL, PLUMBING,
 ROOFING, SHEET METAL, SWIMMING POOL, AND
 AIR-CONDITIONING WORK, UNLESS SUCH CONTRACTOR HOLDS A
 STATE CERTIFICATE OR REGISTRATION IN THE RESPECTIVE
 TRADE CATEGORY,
  
 4)11-4.15.1DRINKING FOUNTAINS OR WATER COOLERS
 REQUIRE TO BE ACCESSIBLE SHALL COMPLY WITH THIS
 SECTION. SHOW ALL REQUIRE DIMENTIONS FOR THE DRINKING
 FOUNTAIN PROVIDED.
  
 5)FBC. 1203.4.2.1ROOMS CONTAINING BATHTUBS,
 SHOWERS, SPAS AND SIMILAR BATHING FIXTURES SHALL BE
 MECHANICALLY VENTILATED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL.
  
 6)INDICATE CLEARLY WHICH TYPE OF HURRICANE STRAP WILL
 BE USED FOR THE RAFTERS AND CAST CRETE TABLES. BE
 SPECIFIC WITH EACH TABLE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-24 Cont ID  
Sent By mjacobs Date 2007-01-18 Time 17:13 Rev Time 0.00
Received By mjacobs Date 2007-01-18 Time 17:09 Sent To  
Notes
2007-01-18 17:10:38BUILDING PLAN REVIEW
 PERMIT:07010426
 ADD: 4619GEORGIA AVE
 CONT: STONE IMAGE
 TEL: (561)547-1177
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION.
  
 2) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R.
  
 3) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE PRODUCT APPROVALS FOR
 THE ROOFING MATERIALS/ EXTERIOR DOORS/ WINDOWS ETC.
  
 4)ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 _XX___1.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED
 POLICY:MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE /
 AREA OF EACH ROOF TYPE
  
 _XX___2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX___3.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 _XX___4.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 _XX___ 5.)ON THE TILE PRODUCT APPROVAL, INDICATE
 WHICH METHOD OF ATTACHMENT YOU ARE USING.
  
 _XX___ 6.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
 5)WHAT IS THE USE OF THE MAIN STRUCTURE AROUND THE
 PROPOSED BATHROOM/STORAGE.
  
 NOTE: ONE SET OF THE DRAWINGS ARE NOT SIGNED AND
 SEALED. IF THE THIRD SET OF DRAWINGS ARE TO BE
 REVIEWED, THEN, THEY SHALL BE SIGNED AND SEALED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-08 Cont ID  
Sent By dpalmer Date 2007-06-08 Time 11:50 Rev Time 0.00
Received By dpalmer Date 2007-06-08 Time 10:04 Sent To  
Notes
2007-06-08 11:52:15 
 ** UNSAT **
  
 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON
 PLANS FOR THE DESIGNS WHICH THEY ARE UNDER.
 PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER
 DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE
 RELEVANT.
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70
 (NEC).
  
 2) NOTE: PLEASE SEE RISER NOW INDICATES 2/0 CONDUCTORS
 BEING FED TO A 60A BREAKER. PLEASE KNOW THIS IS NOT
 POSSIBLE AS THIS SIZE CONDUCTOR WILL NOT FIT INTO THE
 LUGS.225.31-225.39 FOR DISCONNECTING MEANS FOR THE
 CIRCUIT(S) TO THIS DETACHED STRUCTURE. PLEASE INDICATE
 WHERE THE FEED IS COMING FROM AND HOW IT IS GETTING TO
 THIS NEW LOCATION.
 PLEASE INDICATE THE SIZE OF THE CIRCUITS, CONDUCTORS
 ETC.
 240.4, 310.16, 408.4, 300.5 ETC
  
 3) NOTE: PLEASE SEE NO PANEL SCHEDULE FOR CIRCUITS AT
 THE DETACHED BUILDING WAS SUBMITTED.
 PLEASE SEE 408.4.
  
 4) NOTE: PLEASE ALSO THE MISSING GROUNDING ELECTRODE
 CONNECTION. PLEASE SEE 250.32 AND 250.50
  
 5) NOTE: PLEASE SEE RISER DOES NOT INDICATE ANY OCP AT
 THE MAIN EXISTING PANEL AS SHOWN TO FEED NEW PANEL.
 PLEASE ALSO CLARIFY WHAT IS BEING SHOWN AS TWO CONDUITS
 FROM THE MAIN EXISTING PANEL TO NEW PANEL.
 FBC 106.1.2, 106.3.5.1.2
 PLEASE SEE 408.4, 240.4, 310.16.
  
 6) NOTE: PLEASE SEE THE ADDRESS FOR SAID PROJECT HAS
 NOW CHANGED, PLEASE BE SURE TO REVISED PERMIT
 APPLICATION AND PLAN TITLE BLOCKS TO NEW ADDRESS.
 FAC 61G1-16.004
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-14 Cont ID  
Sent By dpalmer Date 2007-01-14 Time 17:11 Rev Time 0.00
Received By dpalmer Date 2007-01-14 Time 16:54 Sent To  
Notes
2007-01-14 17:11:29 
 ** UNSAT **
  
 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON
 PLANS FOR THE DESIGNS WHICH THEY ARE UNDER.
 PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER
 DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE
 RELEVANT.
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70
 (NEC).
  
 2) NOTE: PLEASE SEE 225.31-225.39 FOR DISCONNECTING
 MEANS FOR THE CIRCUIT(S) TO THIS DETACHED STRUCTURE.
 PLEASE INDICATE WHERE THE FEED IS COMING FROM AND HOW
 IT IS GETTING TO THIS NEW LOCATION.
 PLEASE INDICATE THE SIZE OF THE CIRCUITS, CONDUCTORS
 ETC.
 240.4, 310.16, 408.4, 300.5 ETC
  
 3) NOTE: PLEASE SEE RECEPTACLE AT THIS BUILDING IS
 REQUIRED TO BE GFI PROTECTED.
 210.8(B)(1) & (4).
  
 4) NOTE: PLEASE ALSO THE MISSING GROUNDING ELECTRODE
 CONNECTION. PLEASE SEE 250.32
  
 5) NOTE: PLEASE SEE EVEN THOUGH NOT REQUIRED THE THIRD
 SET OF PLANS SUBMITTED WERE NOT SIGNED, DATED OR
 SEALED. IF THE THIRD SET WAS SUBMITTED TO HAVE AN EXTRA
 COPY STAMPED, PLEASE BE SURE THE DESIGNER OF RECORD
 SIGNS, DATES AND SEALS LIKE THE OTHER SETS.
 *THIS IS ONLY NOTED AS THE TWO REQUIRED ARE OK.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-06-12 Cont ID  
Sent By mawillia Date 2007-06-12 Time 17:08 Rev Time 0.00
Received By mawillia Date 2007-06-12 Time 16:24 Sent To  
Notes
2007-06-12 16:33:11*****DENIED*****
  
  
 1.NFPA 101, THE LIFE SAFETY CODE, 2003 EDITION SHALL
 BE REFERENCED.
  
 2. THE CORRECT NUMERICAL ADDRESS SHOULD BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3.PLANS DO NOT INDICATE IF THE PROPOSED STRUCTURE IS
 ADJOINING OR INDEPENDANT OF AN EXISTING BUILDING.
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS RESPONSE TO THE PROPERTY OR
 VICINITY THEREOF (INCLUDING STREETS AND ROADS).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-24 Cont ID  
Sent By mawillia Date 2007-01-24 Time 13:13 Rev Time 0.00
Received By mawillia Date 2007-01-24 Time 13:06 Sent To  
Notes
2007-01-24 13:24:12*****DENIED*****
  
  
  
 THERE IS NOTSUFFICIENT INFORMATION GIVEN TO CONDUCT A
 FIRE PLAN REVIEW.IN PARTICULAR, BY ADDRESSING BOTH
 THE BUILDING REVIEWANDTHE ZONING REVIEW COMMENTS
 SHOULD SUPPLY THE NEEDED INFORMATION TO CONDUCT AN
 ADEQUATE FIRE PLAN REVIEW.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-29 Cont ID  
Sent By adarroug Date 2007-05-29 Time 13:11 Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 13:11 Sent To  
Notes
2007-06-07 15:59:28TO "BOB"#5
2007-05-29 13:12:05WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-24 Cont ID  
Sent By adavila Date 2007-01-23 Time 10:53 Rev Time 0.00
Received By mawillia Date 2007-01-09 Time 17:39 Sent To  
Notes
2007-01-12 16:38:41TO "BOB"#11
2007-01-09 17:39:19WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-06-12 Cont ID  
Sent By tgordon Date 2007-06-12 Time 08:24 Rev Time 0.15
Received By tgordon Date 2007-06-12 Time 08:24 Sent To  
Notes
2007-06-12 08:24:49NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-01-16 Cont ID  
Sent By tgordon Date 2007-01-16 Time 13:39 Rev Time 0.20
Received By tgordon Date 2007-01-16 Time 13:39 Sent To  
Notes
2007-01-16 13:40:57NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-14 Cont ID  
Sent By jleech Date 2007-06-14 Time 07:44 Rev Time 0.00
Received By jleech Date 2007-06-14 Time 07:35 Sent To  
Notes
2007-06-14 07:52:55DENIED;
 1. PLUMBING NOTE 14 AIR CHAMBERS ARE NOT AN APPROVED
 ENGINEERED PART. WATER HAMMER ARRESTORS TO BE USED, SEE
 FBC-2004 PLUMBING SECTION 604.9 TO FIND OUT WHERE
 REQUIRED.
 2. SANITARY RISER DIAGRAM;MOP SINK NOT VENTED. ((SEE
 ONE SET OF PLANS MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-17 Cont ID  
Sent By jleech Date 2007-01-17 Time 15:08 Rev Time 0.00
Received By jleech Date 2007-01-17 Time 15:08 Sent To  
Notes
2007-01-17 15:29:26DENIED;
 1.FBC-2004 PLUMBING TABLE 403.1 MINIMUM PLUMBING
 FIXTURES REQUIRED.CLASSIFICATION FACTORY A DRINKING
 FOUNTAIN AND A MOP SINK IS REQUIRED.
 2.SHOW WATER RISER DIAGRAM.
 3.MUST STATE ON PLANS OCCUPANCY AND NUMBER OF
 EMPLOYEES. SEE SECTION 106.3.5.1.1(2)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status F Date 2007-06-06 Cont ID  
Sent By adavila Date 2007-06-06 Time 16:44 Rev Time 0.00
Received By adavila Date 2007-06-04 Time 14:09 Sent To  
Notes
2007-06-06 16:45:19PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. REPEAT COMMENT:THE NEW (ACCESSORY) STRUCTURE SHALL
 COMPLY WITH THE LANDSCAPE REQUIREMENTS, ARTICLE XIV, OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 2. A LANDSCAPE PLAN, PREPARED, SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT, SHALL BE SUBMITTED
 MEETING ARTICLE XIV, MORE SPECIFICALLY SECTION
 94-443(B), OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 3. PER SECTION 94-486, ARTICLE XV, OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS, AT LEAST ONE (1) PARKING
 SPACE SHALL BE PROVIDED FOR THE PROPOSED
 STORAGE/BATHROOM.
  
 4. REPEAT COMMENT: THE NEW (ACCESSORY) STRUCTURE SHALL
 COMPLY WITH THE PARKING REQUIREMENTS, ARTICLE XV, OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 5. PROVIDE A LETTER FROM THE ENGINEERING SERVICES
 DEPARTMENT VERIFYING THAT A DUMPSTER IS REQUIRED ON THE
 SITE.
 A. PLEASE NOTE THAT IN THE EVENT THAT A DUMPSTER IS
 NEEDED, DUMPSTER ENCLOSURE MEETING SECTION 94-444(B) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS SHALL BE
 PROVIDED.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-23 Cont ID  
Sent By adavila Date 2007-01-23 Time 11:12 Rev Time 0.00
Received By adavila Date 2007-01-23 Time 10:38 Sent To  
Notes
2007-01-23 10:49:16PLANNING AND ZONING DEPARTMENT
  
 *** FAILED ***
  
 1) PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
  
 2) PLEASE PROVIDE A SURVEY, SIGNED AND SEALED, SHOWING
 ALL IMPROVEMENTS OF THE SUBJECT PROPERTY AND A
 COMPUTATION OF THE TOTAL ACREAGE, TO THE NEAREST
 ONE-HUNDREDTH (1/100) OF AN ACRE.SURVEY MUST BE LESS
 THAN A YEAR OLD.
  
  
 3) PLEASE PROVIDE A SITE PLAN SHOWING WHETHER THE
 PROPOSED BATHROOM/STORAGE WILL BE A FREESTANDING
 ACCESSORY STRUCTURE, AN ADDITION TO THE EXISTING
 STRUCTURE(S), OR COMPLETELY INSIDE AN EXISTING
 BUILDING.
  
 A) SITE PLAN MUST SHOW TOTAL SQUARE FOOTAGE OF THE
 PROPERTY/LOT.
  
 B) SITE PLAN MUST SHOW BUILDING COVERAGE PERCENTAGE.
  
 C) SITE PLAN MUST SHOW SETBACK DIMENSIONS OF THE
 EXISTING AND PROPOSED STRUCTURES FROM THE PROPERTY
 LINES AND ADJACENT BUILDINGS.
  
 D) SITE PLAN MUST SHOW FLOOR AREA RATIO (FAR).
  
  
 4) IN THE CASE OF A NEW (ACCESSORY) STRUCTURE, OR
 ADDITION TO AN EXISTING STRUCTURE:
  
 A) SHALL COMPLY WITH THE INDUSTRIAL ZONING DISTRICT
 REGULATIONS (ARTICLE VIII OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS).
  
 B) SHALL COMPLY WITH THE LANDSCAPE REGULATIONS (ARTICLE
 14, MORE SPECIFICALLY SECTION 94-443(B), OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS).
  
 C) SHALL COMPLY WITH THE PARKING REGULATIONS (ARTICLE
 15 OF THE ZONING AND LAND DEVELOPMENT REGULATIONS).
  
  
 5) THE ZONING AND LAND DEVELOPMENT REGULATIONS MAY BE
 ACCESSED ONLINE AT THE PLANNING DEPARTMENT'S WEBSITE,
 WWW.CITYOFWPB.COM/PLAN.
  
  
 QUESTIONS/COMMENTS, PLEASE CONTACT ANDREINA DAVILA Q.,
 AT 561.822.1435.