Plan Review Details - Permit 06120723
Plan Review Stops For Permit 06120723
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-05-10 Cont ID  
Sent By mjacobs Date 2007-05-10 Time 14:09 Rev Time 0.00
Received By mjacobs Date 2007-05-10 Time 13:40 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-14 Cont ID  
Sent By mjacobs Date 2007-02-14 Time 16:31 Rev Time 0.00
Received By mjacobs Date 2007-02-14 Time 12:32 Sent To PC
Notes
2007-02-14 14:44:22 
 BUILDING PLAN REVIEW
 PERMIT: 06120723
 ADD: 307 SUNSET RD.
 CONT: BOYD STUART
 TEL: (561)278-0602
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5)PROVIDE A LEGEND SHOWING WHICH WALLS ARE EXISTING
 AND WHICH ONES ARE NEW. IS THIS AN ADDITION OR PORCH
 ENCLOSURE, WHICH WILL INCREASE THE SQUARE FOOTAGE OF
 THE HOUSE ?SEE SEC.R506 FOR MORE INFORMATION.
 106.1.1CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL (SEE ALSO SEC. 106.3.5)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-05-09 Cont ID  
Sent By btrobaug Date 2007-05-09 Time 14:23 Rev Time 0.50
Received By btrobaug Date 2007-05-09 Time 13:58 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-10 Cont ID  
Sent By btrobaug Date 2007-01-10 Time 08:09 Rev Time 1.00
Received By btrobaug Date 2007-01-09 Time 15:13 Sent To P
Notes
2007-01-10 08:06:26 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), SHOW SAME ON THE PANEL SCHEDULE.
  
 3} 230.70 GENERAL.
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE
 CONDUCTORS.INDICATE COMPLIANCE WITH THIS ARTICLE BY
 STATING THE PANEL COMPLIES (HAS A 200 AMP MAIN
 BREAKER), OR A DISCONNECTING MEANS AT THE METER.
  
 4} GIVE PANEL SPECIFICATIONS, NUMBER OF SPACES, VOLTAGE
 AND AMPERE RATING, MAIN LUG OR MAIN BREAKER.
  
 5} SHEET A-1 NOTES REWIRING THE WHOLE HOUSE W/NEW 200
 AMP PANEL, SHEET A-2 NOTE AN EXISTING PANEL. PLEASE
 CORRELATE.
  
 6} IF THE CUSTOMARY RECEPTACLE SYMBOL, THAT IS LOCATED
 BEHIND THE WATER HEATER AND CONDENSING UNITS, IS
 SUPPOSED TO REPRESENT THE REQUIRED DISCONNECTS FOR
 SAME, THEY ARE IN VIOLATION OF 110.26 FOR CLEAR SPACE.
  
 7} LOCATE THE REQUIRED DISCONNECTING MEANS FOR THE
 WATER HEATER AND THE CONDENSING UNIT. 422.30 & 440.14.
  
 8} SHOW COMPLIANCE WITH THE REQUIRED A/CRECEPTACLE
 PER 210.63.
  
 9} THE RANGE MUST BE CALCULATD @ 8KW MINIMUM PER
 220.55.
  
 10} NOTE THE DOWNSTAIRS BEDROOM RECEPTACLE ADJACENT TO
 THE ENTRY, NEEDS TO BE MOVED OR ANOTHER ADDED TO COMPLY
 WITH 210.52(A)(1).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-07 Cont ID  
Sent By adarroug Date 2007-05-07 Time 16:46 Rev Time 0.00
Received By adarroug Date 2007-05-07 Time 16:46 Sent To E
Notes
2007-05-07 16:47:10TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 11:00 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 11:00 Sent To Z
Notes
2007-05-04 11:00:29TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-16 Cont ID  
Sent By adarroug Date 2007-01-16 Time 17:39 Rev Time 0.00
Received By adarroug Date 2007-01-16 Time 17:39 Sent To B
Notes
2007-01-16 17:40:03TO "BLDG-RES" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-02-14 Time   Rev Time 0.00
Received By adarroug Date 2006-12-28 Time 16:14 Sent To  
Notes
2006-12-28 16:14:38TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-01-10 Cont ID  
Sent By tgordon Date 2007-01-10 Time 16:04 Rev Time 0.15
Received By tgordon Date 2007-01-10 Time 16:04 Sent To Z
Notes
2007-01-10 16:04:55NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-05-10 Cont ID  
Sent By mperson Date 2007-05-10 Time 08:46 Rev Time 0.33
Received By mperson Date 2007-05-10 Time 08:46 Sent To B
Notes
2007-05-10 08:59:30****************PROVISO****************
 FBC-2004 PLUMBING
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 (E) FIXTURES TO BE SIZED PER FBC-2004 PLUMBING SECTIONS
 416.3 LAVATORY WASTE OUTLETS, 417.3 SHOWER WASTE
 OUTLETS AND 420.4 WATER CLOSET CONNECTIONS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-01-10 Cont ID  
Sent By mperson Date 2007-01-10 Time 13:10 Rev Time 0.33
Received By mperson Date 2007-01-10 Time 13:10 Sent To M
Notes
2007-01-10 13:12:15PLUMBING PERMIT REQUIRED

Review Stop Z ZONING
Rev No 2 Status P Date 2007-05-07 Cont ID  
Sent By choops Date 2007-05-07 Time 15:02 Rev Time 0.00
Received By choops Date 2007-05-07 Time 15:02 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-12 Cont ID  
Sent By mmclean Date 2007-01-12 Time 17:38 Rev Time 0.00
Received By mmclean Date 2007-01-12 Time 17:38 Sent To I
Notes
2007-01-12 17:40:01DENIED,
 1. PLEASE PROVIDE A COPY OF CURRENT SURVEYS SHOWING THE
 STRUCTURE THAT IS BEING REPAIRED.
 2. PLEASE CLARIFY IF THE REPAIRS ARE FOR THE MAIN
 STRUCUTRE OR ANY ACCESSORY STRUCTURE.
 3. PLEASE PROVIDE PLANS OF THE EXISTING STRUCTURE
 BEFORE THE INTERIOR REPAIRS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720