| 2006-12-28 16:56:26 | BUILDING PLAN REVIEW |
| | PERMIT:06120710 |
| | ADD:2808 AUSTRALIAN AVE. |
| | CONT: SEALCOAT SYSTEMS. |
| | TEL: (941)423-2216 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | REVIEW : 1ST |
| | ACTION: DENIED |
| | |
| | |
| | 1) FBC 1609.6.2.2. THE SYSTEM SELECTED |
| | FROM THE SUBMITTED FLAT ROOF PRODUCT |
| | APPROVAL NOA HAS A MAXIMUM DESIGN |
| | PRESSURE OF LESS THAN -89 PSF AND CITES |
| | GENERAL LIMITATION #9 (SEE PAGE 11_ TO |
| | _30_).GENERAL LIMITATION #9 PROHIBITS |
| | RATIONAL ANALYSIS OR EXTRAPOLATION TO |
| | ENHANCE THE UPLIFT PRESSURE AT PERIMETER |
| | AND CORNER AREAS BY REDUCING THE |
| | FASTENER SPACING IN THESE AREAS.EITHER |
| | SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT |
| | APPROVAL) THAT DOES NOT CITE GENERAL |
| | LIMITATION #9.ALTERNATIVELY IF THE |
| | SELECTED SYSTEM DOES CITE GENERAL |
| | LIMITATION #9, IT MUST HAVE A MAXIMUM |
| | DESIGN PRESSURE THAT EXCEEDS THE |
| | PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 |
| | PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR |
| | LESS). |
| | |
| | 2)IN THE PACKAGE IS THE ROOFING POLICY AND PROCEDURE |
| | OF OUR DEPARTMENT. PROVICE ALL THE INFORMATION |
| | REQUESTED IN THE POLICY. NOTE: SOME OF THE PRODUCT |
| | APPROVALS REQUIRE CALCULATIONS SIGNED AND SEAL FROM A |
| | REGISTERED ENGINEER,ARCHITECT OR ROOF CONSULTANT. READ |
| | THE GENERAL LIMITATIONS CAREFULLYTO SEE IF THIS |
| | INFORMATION SHALL BE SUBMITTED ALONG WITH THE PRODUCT |
| | APPROVALS. HI-LIGHT OR CIRCLE THE SYSTEM WHICH WILL BE |
| | USED. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |
| | |
| | |