Plan Review Details - Permit 06120710
Plan Review Stops For Permit 06120710
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2007-01-11 Cont ID  
Sent By mjacobs Date 2007-01-11 Time 17:45 Rev Time 0.00
Received By mjacobs Date 2007-01-11 Time 17:45 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-11 Cont ID  
Sent By mjacobs Date 2007-01-11 Time 17:45 Rev Time 0.00
Received By mjacobs Date 2007-01-11 Time 15:57 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-28 Cont ID  
Sent By mjacobs Date 2006-12-28 Time 16:56 Rev Time 0.00
Received By mjacobs Date 2006-12-28 Time 14:59 Sent To PC
Notes
2006-12-28 16:56:26BUILDING PLAN REVIEW
 PERMIT:06120710
 ADD:2808 AUSTRALIAN AVE.
 CONT: SEALCOAT SYSTEMS.
 TEL: (941)423-2216
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 F.S.= FLORIDA (STATE) STATUTE
  
 REVIEW : 1ST
 ACTION: DENIED
  
  
 1) FBC 1609.6.2.2. THE SYSTEM SELECTED
 FROM THE SUBMITTED FLAT ROOF PRODUCT
 APPROVAL NOA HAS A MAXIMUM DESIGN
 PRESSURE OF LESS THAN -89 PSF AND CITES
 GENERAL LIMITATION #9 (SEE PAGE 11_ TO
 _30_).GENERAL LIMITATION #9 PROHIBITS
 RATIONAL ANALYSIS OR EXTRAPOLATION TO
 ENHANCE THE UPLIFT PRESSURE AT PERIMETER
 AND CORNER AREAS BY REDUCING THE
 FASTENER SPACING IN THESE AREAS.EITHER
 SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT
 APPROVAL) THAT DOES NOT CITE GENERAL
 LIMITATION #9.ALTERNATIVELY IF THE
 SELECTED SYSTEM DOES CITE GENERAL
 LIMITATION #9, IT MUST HAVE A MAXIMUM
 DESIGN PRESSURE THAT EXCEEDS THE
 PRESSURE IN ROOF ZONE 3 (TYPICALLY -89
 PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR
 LESS).
  
 2)IN THE PACKAGE IS THE ROOFING POLICY AND PROCEDURE
 OF OUR DEPARTMENT. PROVICE ALL THE INFORMATION
 REQUESTED IN THE POLICY. NOTE: SOME OF THE PRODUCT
 APPROVALS REQUIRE CALCULATIONS SIGNED AND SEAL FROM A
 REGISTERED ENGINEER,ARCHITECT OR ROOF CONSULTANT. READ
 THE GENERAL LIMITATIONS CAREFULLYTO SEE IF THIS
 INFORMATION SHALL BE SUBMITTED ALONG WITH THE PRODUCT
 APPROVALS. HI-LIGHT OR CIRCLE THE SYSTEM WHICH WILL BE
 USED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-11 Cont ID  
Sent By adarroug Date 2007-01-11 Time 15:22 Rev Time 0.00
Received By adarroug Date 2007-01-11 Time 15:22 Sent To B
Notes
2007-01-11 15:22:46TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-28 Cont ID  
Sent By mjacobs Date 2006-12-28 Time 14:59 Rev Time 0.00
Received By mjacobs Date 2006-12-28 Time 14:59 Sent To  
Notes
***NONE***