Plan Review Details - Permit 06120699
Plan Review Stops For Permit 06120699
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-02-12 Cont ID  
Sent By mawillia Date 2007-02-12 Time 12:52 Rev Time 0.00
Received By mawillia Date 2007-02-12 Time 12:52 Sent To  
Notes
2007-02-12 12:56:07******APPROVED******
  
  
 COMMENTS FROM PREVIOUS FIRE PLAN REVIEW HAVE BEEN
 ADDRESSED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-24 Cont ID  
Sent By mwennerg Date 2007-01-24 Time 14:22 Rev Time 0.00
Received By mwennerg Date 2007-01-24 Time 14:22 Sent To  
Notes
2007-01-24 14:46:19***DENIED***
  
 1) STANDPIPE CONNECTIONS ARE LOCATED AT ALTERNATE STAIR
 LEVELS WHICH WILL NOT BE AN ACCEPTABLE ARRANGEMENT.
 CONNECTIONS SHALL BE LOCATED AT EACH LEVEL OF FLOOR
 ENTRANCE.
  
 2) STANDPIPE CONNECTIONS TO BE 2 1/2"- 1 1/2" REDUCER
 WITH CHAIN.
  
 3) STANDPIPE CONNECTIONS SHALL BE LOCATED SO AS NOT TO
 INTERFERE WITH MEANS OF EGRESS.
  
 4) IT WOULD APPEAR THAT THE GROUND LEVEL CONNECTION IS
 LOCATED IN A MANNER THAT NEGATIVELY IMPACTS REQUIRED
 HEADROOM DISTANCE.
  
 5) STANDPIPE CONNECTIONS SHALL BE LOCATED NOT TO EXCEED
 130'.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-09 Cont ID  
Sent By adarroug Date 2007-02-09 Time 12:09 Rev Time 0.00
Received By adarroug Date 2007-02-09 Time 12:09 Sent To FIRE
Notes
2007-02-09 12:10:22TO "MAW" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-24 Cont ID  
Sent By mwennerg Date 2007-01-24 Time 14:47 Rev Time 0.00
Received By mwennerg Date 2006-12-27 Time 16:12 Sent To  
Notes
2006-12-27 16:12:41TO "F" BOX