Plan Review Details - Permit 06120693
Plan Review Stops For Permit 06120693
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-19 Cont ID  
Sent By rmcdouga Date 2008-02-19 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2008-02-19 Time 07:25 Sent To  
Notes
2008-02-19 09:47:102004 FBC
 NEW SINGLE FAMILY DWELLING
  
 DENIED BY BUILDING
  
 1) A RECORDED NOTICE OF COMMENCEMENT WILL BE REQUIRED.
  
 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY
 IMPACT FEES.
  
 3) TWO COPIES OF A SIGNED AND SEALED GEOTECHNICAL
 REPORT VERIFYING THE SAFE BEARING CAPACITY OF THE SOIL
 WILL BE REQUIRED TO BE SUBMITTED AFTER THE DEMOLITION
 AND PRIOR TO ANY CONSTRUCTION. SEE R 401.4 (PROVISO)
  
 4) THERE ARE CASEMENT WINDOWS SPECIFIED ON SHEET A.8
 WITH HEIGHTS OF 80" AND 99-1/8" (D&G). THESE HEIGHTS
 EXCEED THE MAXIMUM HEIGHTS LISTED ON THE PRODUCT
 APPROVALS FOR THE CASEMENT WINDOWS. PLEASE CORRECT.
  
 5) SUBMIT THE ORIGINAL PERMIT APPLICATION OR COMPLETE A
 DUPLICATE APPLICATION.
  
 6) FEES OF $577.06 ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-20 Cont ID  
Sent By rmcdouga Date 2007-09-20 Time 11:35 Rev Time 0.00
Received By rmcdouga Date 2007-09-18 Time 17:08 Sent To  
Notes
2007-09-20 09:32:262004 FBC
 NEW SINGLE FAMILY DWELLING
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) PROVIDE TWO COPIES OF A SIGNED AND SEALED
 GEOTECHNICAL REPORT TO VERIFY THE SAFE BEARING CAPACITY
 OF THE SOIL. SEE R401.4. (CAN BE PROVISO TO SUBMIT
 AFTER DEMO)
  
 4) THE DOORS FROM THE GARAGE TO THE RESIDENCE ARE
 REQUIRED TO COMPLY WITH R309.1 OPENING PROTECTION.
 OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM
 USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED.
 OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL
 BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1- 3 /
 8 INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB CORE
 STEEL DOORS NOT LESS THAN 1- 3 / 8 INCHES (35 MM)
 THICK, OR 20-MINUTE FIRE-RATED DOORS.
  
 5) THE STORAGE AREA UNDER THE STAIRS ARE REQUIRED TO
 COMPLY WITH R311.2.2 UNDER STAIR PROTECTION. ENCLOSED
 ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE WALLS, UNDER
 STAIR SURFACE AND ANY SOFFITS PROTECTED ON THE ENCLOSED
 SIDE WITH 1/2 -INCH (12.7 MM) GYPSUM BOARD.
  
  
 6) SPECIFY THE LOCATION OF THE DRAFTSTOPPING REQUIRED
 BY R502.1.2 ON THE FLOOR FRAMING PLAN. SEE ITEM #18 ON
 PREVIOUS REVIEW.
  
 7) SPECIFY THE SIZE, NUMBER AND SPACING OF THE VERTICAL
 REINFORCEMENT OF THE CONCRETE BLOCK WALLS AT THE FIRST
 AND SECOND FLOORS AND THE MASONRY CHIMNEY. FBC* 106.1.2
 SEE ITEM #22 ON PREVIOUS REVIEW.
  
 8) SPECIFY THE CONNECTORS AND HANGERS FOR THE WOOD
 GIRDER TRUSSES AT THE SECOND FLOOR BALCONY. FBC*
 106.1.2
  
 9) SHEET A.0 SPECIFIES R-19 ICYNENE INSULATION AND THE
 ENERGY CALCULATIONS SPECIFY R-30. PLEASE CORRECT. SEE
 #32 FROM PREVIOUS REVIEW.
  
 10) THE PLANS SPECIFY ISONYNE (ICYNENE) ATTIC
 INSULATION THE MANUFACTURER'S SPECIFICATIONS THAT WERE
 SUBMITTED ARE FOR ANOTHER SPRAY FOAM INSULATION. PLEASE
 REVISE SHEET A.0. RATHER THAN SPECIFY A PARTICULAR
 BRAND, JUST SPECIFY SPRAY FOAM INSULATION.
  
 11) THE SPRAY FOAM ATTIC INSULATION IS REQUIRED TO BE
 BE PROTECTED BY AN IGNITION BARRIER IN COMPLIANCE WITH
 R314.5.3 ATTICS.
 WHERE ATTIC ACCESS IS REQUIRED BY SECTION R807.1 AND
 WHERE ENTRY IS MADE ONLY FOR SERVICE OF UTILITIES, FOAM
 PLASTICS SHALL BE PROTECTED AGAINST IGNITION BY
 1.5-INCH-THICK (38 MM) MINERAL FIBER INSULATION, 1 / 4
 -INCH-THICK (6.4 MM) WOOD STRUCTURAL PANELS, 3 / 8
 -INCH (9.5 MM) PARTICLEBOARD, 1/4-INCH (6.4 MM)
 HARDBOARD, 3 / 8 -INCH (9.5 MM) GYPSUM BOARD, OR
 CORROSION-RESISTANT STEEL HAVING A BASE METAL THICKNESS
 OF 0.016 INCH (0.406 MM) AND THE THERMAL BARRIER
 SPECIFIED IN SECTION R314.4 IS NOT REQUIRED. THE
 IGNITION BARRIER IS NOT REQUIRED WHERE THE FOAM PLASTIC
 INSULATION HAS BEEN TESTED IN ACCORDANCE WITH SECTION
 R314.6 .
 THE IGNITION BARRIER IS NOT REQUIRED WHEN THE FOAM HAS
 BEEN TESTED IN ACCORDANCE WITH R314.6 SPECIFIC
 APPROVAL.
 PLASTIC FOAM NOT MEETING THE REQUIREMENTS OF SECTIONS
 R314.3 THROUGH R314.5 SHALL BE SPECIFICALLY APPROVED ON
 THE BASIS OF ONE OF THE FOLLOWING APPROVED TESTS:
 FM4880, UL 1040, NFPA 286, OR UL 1715, OR FIRE TESTS
 RELATED TO ACTUAL END-USE CONFIGURATIONS. THE SPECIFIC
 APPROVAL SHALL BE BASED ON THE ACTUAL END USE
 CONFIGURATION AND SHALL BE PERFORMED ON THE FINISHED
 FOAM PLASTIC ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED
 FOR USE. ASSEMBLIES TESTED SHALL INCLUDED SEAMS, JOINTS
 AND OTHER TYPICAL DETAILS USED IN THE INSTALLATION OF
 THE ASSEMBLY AND SHALL BE TESTED IN THE MANNER INTENDED
 FOR USE. SPECIFY HOW THE FOAM WILL BE PROTECTED FROM
 IGNITION ON THE PLANS OR PROVIDE ACCEPTABLE EVIDENCE OF
 THE REQUIRED TESTING.
  
 12) PLEASE REMOVE THE OLD OR EXPIRED PRODUCT APPROVALS
 FROM THE SUBMITTAL. ONLY SUBMIT PRODUCT APPROVALS THAT
 WILL BE USED. REMOVE ANY DUPLICATE PRODUCT APPROVALS.
 INDICATE WHICH PRODUCT APPROVALS ARE FOR WHICH
 OPENINGS.
  
 13) THE COMPONENT AND CLADDING PRESSURES ON S.1 FOR A
 TWO STORY BUILDING ARE WORST CASE AND DO NOT ACCOUNT
 FOR OPENING SIZE OR GARAGE DOORS. BECAUSE SEE FBC TABLE
 R301.2(2) AND TABLE R301.2(4). BECAUSE THESE PRESSURES
 ARE SPECIFIED SOME OF THE PRODUCT APPROVALS MAY HAVE
 PRESSURES THAT ARE NOT ADEQUATE. THE OVERHEAD GARAGE
 DOORS FOR EXAMPLE. PLEASE SPECIFY THE REQUIRED
 COMPONENT AND CLADDING PRESSURES AT THE OPENINGS ON THE
 PLANS.
  
 14) THE PRODUCT APPROVAL FOR THE THERMA-TRU FIBERGLASS
 DOOR REQUIRES HURRICANE PANELS FOR THE NON-IMPACT RATED
 SIDELITES. SUBMIT PRODUCT APPROVALS FOR THE STORM
 PANELS.
  
 15) SUBMIT THE NEW NOA #06-0807.07 FOR THE PGT FD 101
 FRENCH DOORS. SEE ITEM #42 FROM PREVIOUS REVIEW.
  
 16) SUBMIT THE NEW NOA #05-1129.11 FOR THE PGT CASEMENT
 WINDOWS. SEE ITEM #43 FROM PREVIOUS REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-20 Cont ID  
Sent By rmcdouga Date 2007-02-20 Time 14:23 Rev Time 0.00
Received By rmcdouga Date 2007-02-20 Time 08:45 Sent To  
Notes
2007-02-20 12:04:59DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) ON SHEET A.0 THERE IS A TYPO UNDER JURISDICTION.
 OALM SHOULD BE PALM.
  
 4) ON A.0 THE EXPOSURE CATEGORY SHOULD BE "B" NOT NEAR
 COASTAL.
  
 5) ON A.0 THE BUILDING CATEGORY IS II.
  
 6) THE ROOF DEAD LOAD ON A.O DOES NOT CONCUR WITH THE
 LOADS SPECIFIED ON S.1.
  
 7) SPECIFY THE ORIENTATION OF THE SITE PLAN ON A.0 AND
 SHOW THE LOCATION OF ALPINE RD.
  
 8) THE INSULATION NOTES ON A.0 DO NOT LIST THE EXTERIOR
 WOOD FRAME WALLS AT THE MASTER BEDROOM OR ADJACENT WOOD
 FRAME WALLS, FLOOR ABOVE COVERED PORCH AND FLOOR AT THE
 GARAGE.
  
 9) SHOW COMPLIANCE WITH FBC R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL.
 EXCEPTION : DETACHED GARAGES ACCESSORY TO A DWELLING
 LOCATED WITHIN 2 FEET (610 MM) OF A LOT LINE SHALL BE
 PERMITTED TO HAVE ROOF EAVE PROJECTIONS NOT EXCEEDING 4
 INCHES (102 MM).
 PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM)
 SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR
 FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE
 PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 EXCEPTION: TOOL AND STORAGE SHEDS, PLAYHOUSES AND
 SIMILAR STRUCTURES ARE NOT REQUIRED TO PROVIDE WALL
 PROTECTION BASED ON LOCATION ON THE LOT.
 THE DISTANCE TOO THE PROPERTY LINE IS 5'. SUBMIT A SITE
 PLAN SHOWING THE SEPARATION DISTANCE TO STRUCTURES ON
 THE ADJACENT PROPERTY WHERE DISTANCE TO PROPERTY LINE
 IS LESS THAN 6'.
  
 10)THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE. THE
 FIRST FLOOR ELEVATION IS REQUIRED TO BE A MINIMUM OF
 7'-6". AN ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR
 TO C.O.
  
 11) R401.4 SOIL TESTS.
 IN AREAS LIKELY TO HAVE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER UNKNOWN SOIL CHARACTERISTICS, THE
 BUILDING OFFICIAL SHALL DETERMINE WHETHER TO REQUIRE A
 SOIL TEST TO DETERMINE THE SOIL?S CHARACTERISTICS AT A
 PARTICULAR LOCATION. THIS TEST SHALL BE MADE BY AN
 APPROVED AGENCY USING AN APPROVED METHOD.
 SUBMIT A GEOTECHNICAL REPORT TO VERIFY THE SAFE BEARING
 CAPACITY OF THE SOIL.
  
 12) SUBMIT A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 13) SHOW COMPLIANCE WITH R322.1.1
 ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES, TRIPLEXES,
 CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT LEAST ONE
 BATHROOM, LOCATED WITH MAXIMUM POSSIBLE PRIVACY, WHERE
 BATHROOMS ARE PROVIDED ON HABITABLE GRADE LEVELS, WITH
 A DOOR THAT HAS A 29-INCH (737 MM) CLEAR OPENING.
 HOWEVER, IF ONLY A TOILET ROOM IS PROVIDED AT GRADE
 LEVEL, SUCH TOILET ROOMS SHALL HAVE A CLEAR OPENING OF
 NOT LESS THAN 29 INCHES (737 MM).
  
 14) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS .
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 15) SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED.
 THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND
 ITS ATTIC AREA BY NOT LESS THAN 1/2 -INCH (12.7 MM)
 GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES
 BENEATH HABITABLE ROOMS SHALL BE SEPARATED FROM ALL
 HABITABLE ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH
 (15.9 MM) TYPE X GYPSUM BOARD OR EQUIVALENT. WHERE THE
 SEPARATION IS A FLOOR-CEILING ASSEMBLY, THE STRUCTURE
 SUPPORTING THE SEPARATION SHALL ALSO BE PROTECTED BY
 NOT LESS THAN 1/2 -INCH (12.7 MM) GYPSUM BOARD OR
 EQUIVALENT.
  
 16)SPECIFY THE WINDOW TYPES ON THE PLANS ( SHINGLE
 HUNG, ETC.).
  
 17)THE WINDOW IN BEDROOM #4 IS REQUIRED TO COMPLY
 WITH R310.1. EMERGENCY ESCAPE AND RESCUE REQUIRED.
  
 18)SHOW COMPLIANCE WITH R502.1.2 DRAFTSTOPPING
 REQUIRED.
 WHEN THERE IS USABLE SPACE ABOVE AND BELOW THE
 CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS
 SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED
 SPACE DOES NOT EXCEED 1,000 SQUARE FEET. DRAFTSTOPPING
 SHALL DIVIDE THE CONCEALED SPACE INTO APPROXIMATELY
 EQUAL AREAS.
  
 19) ON S.1 UPDATE THE MASONRY STANDARDS SPECIFIED TO
 THE 2002 EDITIONS AS LISTED IN THE REFERENCED STANDARDS
 IN CHAPTER 35 OF THE 2004 FBC.
  
 20) SPECIFY THE DIMENSIONS ON THE FOUNDATION PLAN ON
 S.2.
  
 21) SPECIFY THE FASTENER TYPES FOR THE WINDOW/DOOR BUCK
 ATTACHMENT DETAILS ON S.3.
  
 22) PROVIDE A COLUMN SCHEDULE ON THE STRUCTURAL PAGES
 WHICH SPECIFIES REINFORCEMENT.
  
 23) PROVIDE A STRUCTURAL DETAIL FOR THE ARCHED
 OPENINGS.
  
 24) SPECIFY ALL OF THE CONNECTORS FOR THE PORCH ROOF ON
 DETAIL 5/A.5. SEE MARKINGS ON PLANS.
  
 25) DETAIL 5/A5 SPECIFIES A TILE ROOF AND THE
 ELEVATIONS SHOW METAL ROOFS. PLEASE CLARIFY.
  
 26)UPLIFT CONNECTORS ARE REQUIRED FOR THE TRUSSES AT
 THE COVERED PORCH. PLEASE SPECIFY.
  
 27)THE 2ND FLOOR FRAMING PLAN ON S.3 SPECIFIES A
 DOUBLE LEDGER AT THE OUTER WALL OF THE COVERED PORCH
 AND SECTION 2/A.5 SHOWS THE TRUSSES ON TOP OF THE WALL.
 PLEASE CLARIFY.
  
 28) PROVIDE A DETAIL OF THE BAY WINDOW ROOF WITH
 CONNECTORS SPECIFIED. SPECIFY THE FRAMING AT WINDOWS,
 HEADERS, STRAPPING, ETC.
  
 29) PROVIDE DETAILS FOR THE BEAMS AND LINTELS INCLUDING
 REINFORCEMENT AT THE FIREPLACE. SEE SECTION 2/A.2.
  
 30)SPECIFY THE CONNECTORS AT THE SECOND FLOOR JOISTS
 THAT WILL BE USED TO RESIST LATERAL FORCES AT THE FLOOR
 DIAPHRAM.
  
 31)PROVIDE A DETAIL OF THE EXTERIOR WOOD FRAME LOAD
 BEARING WALL AT THE SECOND FLOOR MASTER BEDROOM.
  
 32) SHEET A.0 SPECIFIES R-19 ICYNENE INSULATION AND THE
 ENERGY CALCULATIONS LIST R-30. PLEASE CORRECT.
  
 33) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY CALC. FORM. SEE FBC CHAPTER 13.
  
 34) ICYNENE IS TYPICALLY USED IN UNVENTED ATTICS. THE
 SECTION ON A.2 SOWS THE INSULATION AT THE CEILING
 RATHER THAN AT THE ROOF, WHICH WILL REQUIRE ROOF
 VENTILATION PER R806.1.PLEASE CLARIFY.
  
 35) SUBMIT MANUFACTURER'S SPECS. AND INSTALLATION
 INSTRUCTIONS FOR THE ICYNENE INSULATION.
  
 36) SUBMIT MANUFACTURER'S SPECS. AND INSTALLATION
 INSTRUCTIONS FOR THE ISOKERN FIREPLACES AND FLUE
 ASSEMBLIES.
  
 37) SUBMIT TRUSS DRAWINGS AND LAYOUTS THAT HAVE BEEN
 SIGNED AND SEALED BY THE TRUSS ENGINEER AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD OF THE STRUCTURE.
  
 38) SUBMIT SHOP DRAWINGS FOR THE BALCONY GUARD RAILS
 FOR APPROVAL PRIOR TO INSTALLATION.
  
 39)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 40) SUBMIT PRODUCT APPROVALS FOR THE FOLLOWING:
 - METAL ROOF
  
 41) THE PRODUCT APPROVAL NOA FOR THE THERMA-TRU
 FIBERGLASS DOOR IS EXPIRED. SUBMIT CURRENT PRODUCT
 APPROVAL.
  
 42) THE NOA FOR THE PGT FD101 FRENCH DOORS HAS BEEN
 REVISED BY NOA #06-0807.07. SUBMIT NEW NOA.
  
 43) THE NOA FOR THE PGT CASEMENT WINDOWS HAS BEEN
 REVISED BY NOA # 05-1129.11. SUBMIT NEW NOA. PLEASE
 SPECIFY THE APPROPRIATE WINDOW INFORMATION SUCH AS
 SIZE, GLASS TYPE AND DESIGN PRESSURE BY CIRCLING THEM
 ON THE TABLES IN THE NOA.
  
 45) THE NOA FOR THE PGT 2" MULLINS IS EXPIRED. SUBMIT
 CURRENT NOA.
  
 46) SPECIFY WHICH WINDOWS WILL BE MULLED TOGETHER.
  
 47) SPECIFY WHICH ATTACHMENT METHOD WILL BE USED TO
 INSTALL THE CONCRETE ROOF TILE. CIRCLE THE APPROPRIATE
 ITEM IN THE PRODUCT APPROVAL.
  
 48) THE INSTALLATION DRAWING FOR THE GARAGE DOOR IS
 ONLY PARTIALLY LEGIBLE. SUBMIT CLEAR COPIES. THE DESIGN
 PRESSURES OF -40 PSF IS TOO LOW BASED ON THE REQUIRED
 PRESSURES THAT ARE SPECIFIED ON S1.
  
 IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE INSERT THE NEW
 SHEETS INTO THE PLANS MAKING TWO COMPLETE SETS AND
 SUBMIT ONE SET OF THE OLD PLAN SHEETS FOR REFERENCE
 PURPOSES. A RESPONSE LETTER STATING HOW THE COMMENTS
 HAVE BEEN ADDRESSED WILL ALSO BE HELPFUL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-02-12 Cont ID  
Sent By dpalmer Date 2008-02-12 Time 12:08 Rev Time 0.00
Received By dpalmer Date 2008-02-12 Time 12:08 Sent To M
Notes
2008-02-12 12:08:57 
  
  
 ** DENIED 3RD REVIEW **
  
 1) NOTE: PLEASE SEE THERE ARE SEVERAL PLAN SHEETS
 SUBMITTED WHICH CONTAIN A SIGNATURE AND DATE YET THE
 PLANS ARE NOT SEALED.
 PLEASE SEE THE TITLE BLOCKS FOR ADDRESSING OF FIRM DOES
 NOT CORRESPOND TO THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. PLEASE SEE THE PLANS ARE STILL
 SHOWING 550 S QUADRILLE. PLEASE ALSO SEE SEVERAL SHEETS
 INDICATE THE FIRM LICENSE NUMBER HOWEVER THIS SEEMS TO
 BE GETTING CUT OFF IN THE PRINTING.
 MANY OF THESE ITEMS AS NOTED CAN BE CHANGED BY HAND.
 FAC 61G1-16.004, FS 481.221
 FBC 106.5, 106.1.2
  
 2) NOTE: PLEASE SEE THE RISER NOW INCLUDES AN
 *EQUIPMENT GROUNDING CONDUCTOR* FROM METER TO THE FIRST
 MEANS OF DISCONNECT WHICH IS PANEL *H* WHICH IS NOT
 PERMITTED PER 250.6, 250.24.
 ** THIS COULD BE REDLINED**
  
 3) NOTE: PLEASE SEE THERE ARE LOADS ON PANEL SCHEDULE
 WHICH DO NOT CORRELATE WITH LOADS ON LOAD
 CALCULATIONS.
 PLEASE SEE FOR EXAMPLE: NO MICROWAVE ON PANEL SCHEDULE
 YET SHOWN ON CALCS, PLEASE SEE LOAD ON FRIG IS HIGHER
 ON PANEL THAN ON CALCS, PLEASE SEE DISPOSAL AND
 DISHWASHER LOADS ALSO.
 NEC 220
 FBC 106.3.5.4
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-24 Cont ID  
Sent By dpalmer Date 2007-08-24 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2007-08-24 Time 18:15 Sent To M
Notes
2007-08-24 19:11:31 
 *** DENIED2ND REVIEW ***
  
 *** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS
 BASED ON SOME INFORMATION ON REVISED PLANS.
  
 ** SEVERAL OF THE ITEMS BELOW WOULD HAVE BEEN REDLINED
 HOWEVER A COUPLE OF COMMENTS ARE NEEDED AT THIS TIME
 AND PLANS ARE COMING BACK FOR OTHER COMMENTS. PLEASE
 ADDRESS ALL AT THIS TIME EVEN AS MANY OF THESE WERE
 ITEMS WHICH WOULD HAVE BEEN REDLINED.
  
 1) NOTE: PLEASE SEE THE CODE REFERENCES *2005
 NFPA-2005*. THIS APPEARS TO BE A MISPRINT AND WOULD
 HAVE BEEN REDLINED. SEE PLANS.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 RECESSED LIGHTING FIXTURES WHICH ARE REQUIRED TO MEET
 FBC 13-606.1.ABC.1.2.4. THE INCORRECT CODE SECTION WAS
 GIVEN BY THIS REVIEWER ON PREVIOUS REVIEW, HOWEVER THE
 TYPE OF FIXTURES ARE STILL REQUIRED.
 RESPONSE MENTIONS TO SEE REVISED LEGEND HOWEVER COULD
 NOT LOCATE ANY REFERENCE TO THE TYPE OF FIXTURES.
  
 3) NOTE: PLEASE SEE THE PANEL/SERVICE LOAD CALCULATIONS
 ARE BLANK AND NOT COMPLETE AT THIS TIME.
 PLEASE SEE NEC 220 FOR CALCULATIONS.
 PLEASE CLARIFY RECESSED LIGHTING FIXTURES IN LOAD
 CALCULATIONS AS THESE WITH THE AMOUNT SHOWN ON PLANS
 MAY NOT BE FIGURED IN THE GENERAL LIGHTING LOADS.220.14
  
 MAY CALL TO GO OVER THIS.
  
 4) NOTE: PLEASE SEE 210.52 FOR A MISSING RECEPTACLE
 UPSTAIRS BEDROOM.
 THIS WOULD HAVE BEEN REDLINED ALSO.
  
 5) NOTE: PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS. THIS IS TO COORDINATE WITH THE PANEL SCHEDULE
 AS ALREADY SUBMITTED. 408.4
  
 6) NOTE: PLEASE SEE 220.53, 210.52B1, 210.11C AS THE
 DINING ROOM RECEPTACLES ARE TO BE ON ONE OR *MORE* OF
 THE SMALL APPLIANCE CIRCUITS. THE LOAD FOR EACH SMALL
 APPLIANCE CIRCUIT IS REQUIRED TO BE FIGURED AT 1.5KW.
 PLEASE KNOW THE TWO MINIMUM ARE ALREADY SHOWN AT 1.5,
 HOWEVER THE DINING ROOM IS SHOWN AT .85 WHICH NEEDS TO
 BE 1.5.
 PLEASE ADJUST
  
 7) NOTE: PLEASE SEE THE SMOKE DETECTION DEVICES WERE
 REVISED ON PLANS TO BE LABELED AS *SMOKE ALARMS* YET
 THE PANEL SCHEDULE STILL INDICATES *SMOKE DETECTORS*.
 THIS SEEMS LIKE IT WAS MEANT TO BE CHANGED HOWEVER IF
 INDEED SD PLEASE CLARIFY AND ADJUST PLANS.
 NFPA-72 DEFINITIONS.
  
 8) NOTE: PLEASE SEE AHU #2 AS THIS INDICATES A 50AMP
 OVER CURRENT PROTECTION ON ONE PHASE AND 60AMP ON THE
 OTHER PHASE.
 (MISPRINT HOWEVER PLEASE CORRECT AT THIS TIME).
 424.3B.
 FBC 106.1.2
  
 AS STATED ON THE PREVIOUS REVIEW:
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-28 Cont ID  
Sent By dpalmer Date 2006-12-28 Time 08:41 Rev Time 0.00
Received By dpalmer Date 2006-12-28 Time 07:07 Sent To Z
Notes
2006-12-28 08:46:03 
 ** UNSAT **
  
  
 ** PLEASE KNOW ANY REFERENCES TO THE FBC CHAPTER 1 IN
 THE FOLLOWING NOTES THE ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE ONLY ONE SET OF PLANS ARE SIGNED,
 DATED AND SEALED BY THE ARCHITECT OF RECORD. PLEASE BE
 SURE BOTH SETS ARE SIGNED AND SEALED.
 FS 481.221
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS AS THIS PERMIT APPLICATION HAS BEEN MADE UNDER
 THE NEW 2005 NEC.
 THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON
 ELECTRICAL SHEETS.
 2005 NFPA-2005
 2002 NFPA-72
 PLANS MAY NOT REFERENCE LATEST EDITION AS THE STATE OF
 FLORIDA ONLY JUST ADOPTED THE NEW REVISIONS TO THE 2004
 FBC AND THE 2005 NEC.
  
 3) NOTE: PLEASE SEENFPA-72 11-5.1.1, 11.8.3. PLEASE
 SEE NFPA-72 DEFINITIONS AS PLANS CALL FOR SD FOR SMOKE
 DETECTORS THIS IS OK, HOWEVER PLEASE KNOW IF THESE ARE
 INDEED SMOKE DETECTORS AS DEFINED IN NFPA72, THESE
 WOULD BE DEVICES WHICH ONLY DETECT AND WOULD SIGNAL TO
 OTHER ALARM/HORN DEVICES. NO ALARM HORN DEVICES ARE
 SHOWN. PLEASE INDICATE IF PART OF A FUTURE LV FA
 SYSTEM.
 PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED
 DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY
 WOULD BE LABELED AS SA FOR SMOKE ALARMS.
 PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT
 THE SOUTHERN SECTION MEETING FROM NFPA THAT IF UNITS
 ARE INDEED DEVICES WHICH DETECT AND SOUND AN ALARM,
 PLANS SHOULD SHOW THEM AS SA AND THIS IS NOT NEW IN THE
 CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST TO
 SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06 SHOULD
 BE CHANGING IF WHERE APPLICABLE.
 PLEASE SEE MISSING SA/SD AT THE BOTTOM OF THE STAIRS
 LEADING TO THE FLOOR ABOVE AND MISSING ONE INSIDE AND
 OUTSIDE DEN AS THIS IS CONSIDERED AN ADAPTABLE SLEEPING
 ROOM.
 ANY DEVICES LOCATED O WITHIN 20FT OF COOKING APPLIANCES
 SHALL BE PHOTO-ELECTRIC OR RESETTING TYPE.11.8.3 PLEASE
 ADJUST PLANS AND NOTES.
  
 4) NOTE: PLEASE SEE FBC 2004 13-103.1.1.1 WHICH
 REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED.
 PLEASE NOTE ON PLANS ACCORDINGLY.
  
 5) NOTE: PLEASE CLARIFY RISER AS THIS SHOW 350MCM BEING
 INSTALLED TO FPL YET THE RISER ONLY INDICATES A 200A
 SERVICE BEING INSTALLED?
 FBC ADMIN SECTION 106.1.2
  
 6) NOTE: PLEASE ALSO VERIFY SERVICE AS SHOWN AND
 CORRELATE. PLEASE SEE RISER SHOWS THE PANEL H AS
 CONTAINING A MAIN BACK TO BACK WITH THE METER; HOWEVER
 PANEL SCHEDULE FOR H ONLY INDICATES THIS AS BEING A MLO
 PANEL. PLEASE SEE NOTE #8 AS AN EQUIPMENT GROUND IS
 SHOWN TO THE MAIN PANEL.
 IF THIS IS A METER/MAIN COMBO, PLEASE ADJUST PLANS AND
 RISER ACCORDINGLY.
 IF THIS IS INDEED THE CASE PLEASE SEE THE FOLLOWING
 TWO COMMENTS.
 PLEASE CLARIFY. 230.70,
 FBC 106.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE PROVIDE THE NEW MAIN AIC RATING AS
 REQUIRED PER 110.9
 FBC ADMIN SECTION 106.1.2, 106.3.5.4
  
 8) NOTE: PLEASE SEE IF A MAIN IS NOT LOCATED OUTSIDE
 THEN PLEASE SEE 250.6 AND 250.24B AS AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOT INSTALLED FROM THE METER TO
 THE FIRST MEANS OF DISCONNECT.
  
 9) NOTE: PLEASE SEE PANEL SCHEDULE AS SHOWN, PLEASE SEE
 KITCHEN GFI CIRCUITS SHOULD BE NOTED AS THE KITCHEN
 SMALL APPLIANCE CIRCUITS IF INDEED THESE WILL
 BE.(CLARIFICATION AS IT IS BEING ASSUMED THAT THESE
 ARE)
 408.4
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE THAT ALL ITEMS WHICH SEEM TO BE
 GAS APPLIANCES SHALL BE SHOWN ON PANEL SCHEDULE AS
 SUCH. WILL ELECTRICAL BE INSTALLED TO ANY OF THESE
 LOCATION FOR ANY OF THESE APPLIANCE TO BE ELECTRIC? IF
 SO, PLEASE ALSO INCLUDE ON PANEL SCHEDULE AND LOAD
 CALCULATIONS.
 PLEASE KNOW THAT THIS IS SOMETIMES DONE AND ONLY BEING
 NOTED FOR THE ELECTRICAL PART OF THIS COMMENT. PLEASE
 HOWEVER LIST AS GAS WHERE APPLICABLE.
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE THE CONDUCTORS SHOWN TO THE TWO
 A/C DISCONNECTS INDICATE THESE AS BEING THREE PHASE.
 PLEASE ADJUST SERVICE, CONDUCTORS, OR EXPLAIN THE 3RD
 CONDUCTOR AS SHOWN.
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE DEN AREA WHICH SEEMS TO SHOW A
 RECEPT LOCATED IN THE FLOOR JUST ON THE OUTSIDE OF A
 WALL WHICH ALREADY CONTAINS A RECEPT. PLEASE SEE IF
 INDEED A FLOOR RECEPT PLEASE ADJUST NOTE AND SYMBOL FOR
 SUCH.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE 210.52 FOR SEVERAL MISSING
 REQUIRED RECEPTACLE FOR WALL SPACES 2FT OR MORE. PLEASE
 SEE ONE SET OF PLANS ARE REDLINED FOR MOST LOCATIONS.
  
 13) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.52A FOR
 MISSING DINING AND OTHER SIMILAR AREAS AND CIRCUITING,
 LOADS AS REQUIRED.
  
 14) NOTE:PLEASE CLARIFY IF THE LOAD ON THE POOL PUMP
 IS SHOWN AT THE CONTINUOUS DUTY AS ON LOAD CALCULATIONS
 OR PLEASE SHOW AT 125%.
 215.3, 230.42
  
 15) NOTE: PLEASE SEE 210.70 AND LS 101 7.8, PLEASE SEE
 THE DEN SHALL BE REQUIRED TO CONTAIN A LIGHT FIXTURE OF
 SOME KIND BEFORE FINAL OR OTHER EXCEPTION FOR SWITCHED
 RECEPT ETC.
 PLEASE ADJUST PLANS AS NEEDED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-06 Cont ID  
Sent By adarroug Date 2008-02-06 Time 11:58 Rev Time 0.00
Received By adarroug Date 2008-02-06 Time 11:58 Sent To Z
Notes
2008-02-06 11:58:58TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-22 Cont ID  
Sent By adarroug Date 2007-08-22 Time 09:02 Rev Time 0.00
Received By adarroug Date 2007-08-22 Time 09:02 Sent To Z
Notes
2007-08-22 09:02:46TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-20 Cont ID  
Sent By rmcdouga Date 2007-02-20 Time 14:23 Rev Time 0.00
Received By rmcdouga Date 2006-12-27 Time 15:29 Sent To  
Notes
2006-12-27 15:30:18TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-12 Cont ID  
Sent By tgordon Date 2008-02-12 Time 14:37 Rev Time 0.30
Received By tgordon Date 2008-02-12 Time 14:37 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-28 Cont ID  
Sent By tgordon Date 2007-08-28 Time 16:32 Rev Time 0.45
Received By tgordon Date 2007-08-28 Time 16:32 Sent To P
Notes
2007-08-28 16:34:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 1-2-07 NOTE #4, MANUAL J
 CALCULATION DO NOT SHOW THE BUILDINGS NEEDED SENSIBLE
 BTU'S ON THEM, (THE HIGH LIGHTED SENSIBLE BTU'S ARE FOR
 THE A/C SYSTEM NOT THE BUILDING) YOU MAY NEED THE LONG
 FORM TO GET THIS, PLEASE CORRECT
  
 2) THE GAS CLOTHES DRYER APPEARS TO BE GETTING IT'S
 COMBUSTION AIR FROM THE SECOND FLOOR BATHROOM, PER RES.
 M1701.4 PROHIBITED SOURCES.
 COMBUSTION AIR DUCTS AND OPENINGS SHALL NOT CONNECT
 APPLIANCE ENCLOSURES WITH SPACE IN WHICH THE OPERATION
 OF A FAN MAY ADVERSELY AFFECT THE FLOW OF COMBUSTION
 AIR. COMBUSTION AIR SHALL NOT BE OBTAINED FROM AN AREA
 IN WHICH FLAMMABLE VAPORS PRESENT A HAZARD. FUEL-FIRED
 APPLIANCES SHALL NOT OBTAIN COMBUSTION AIR FROM ANY OF
 THE FOLLOWING ROOMS OR SPACES:
 1.SLEEPING ROOMS.
 2.BATHROOMS.
 3.TOILET ROOMS.
 PLEASE SHOW THE COMBUSTION AIR CALCULATIONS FOR THE GAS
 CLOTHES DRYER AND PROVIDE COMBUSTION AIR IN COMPLIANCE
 WITH M1701.1, M1701.2, AND M1701.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-02 Cont ID  
Sent By tgordon Date 2007-01-02 Time 08:01 Rev Time 1.15
Received By tgordon Date 2007-01-02 Time 08:01 Sent To B
Notes
2007-01-02 08:19:11*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR A 19 AND A 17.30
 SEER A/C SYSTEM, MECHANICAL PLANS ARE CALLING FOR TWO
 13 SEER A/C SYSTEMS, THE TWO MUST COINCIDE, PLEASE
 CORRECT.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) ENERGY CALCULATIONS NEED THE JURISDICTION NUMBER ON
 THEM.
  
 4) MANUAL J CALCULATION DO NOT SHOW THE BUILDINGS
 NEEDED SENSIBLE BTU'S ON THEM, YOU MAY NEED THE LONG
 FORM TO GET THIS, PLEASE CORRECT.
  
 5) SEE PLANS PAGE M.1 SUPPLY AIR DUCT TO THE BATHROOM
 IN THE DEN NEEDS TO BE SIZED.
  
 6) SEE PLANS PAGE M.2 SUPPLY AIR DUCT TO BEDROOM #4
 NEEDS TO BE SIZED.
  
 7) SEE MECHANICAL PLANS A/C EQUIPMENT LISTING, AIR
 HANDLER #2 MODEL NUMBER, ARI DIRECTORY DOES NOT LIST
 THIS AIR HANDLER WITH THAT CONDENSER UNIT, PLEASE
 CORRECT.
  
 8) IF ANY APPLIANCES ARE GAS PLEASE NOTE SO ON
 MECHANICAL PLANS.
  
 9) THE ARCHITECT DID NOT SEAL ALL PAGES OF THE PLANS,
 PLEASE CORRECT PER FAC 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-09-12 Cont ID  
Sent By jleech Date 2007-09-12 Time 10:10 Rev Time 0.00
Received By jleech Date 2007-09-12 Time 10:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-28 Cont ID  
Sent By jleech Date 2006-12-28 Time 14:43 Rev Time 0.00
Received By jleech Date 2006-12-28 Time 14:30 Sent To M
Notes
2006-12-28 14:43:13DENIED;
 1.SANITARY RISER DIAGRAM 2ND FLOOR SOUTH; MISSING
 AUTOMATIC CLOTHES WASHER AND ONE LAVATORY. THE BRANCH
 DRAIN FOR W/M IS REQUIRED TO BE 3" FBC-2004 PLUMBING
 SECTION406.3. THE WET VENT FOR THE MISSING LAV TO BE
 BETWEEN THE W/C AND THE SHOWER. THE W/M MUST DUMP DOWN
 STREAM OF THE BATHROOM GROUPS SECTION 909.1.
 2. THE SHOWERDRAIN MUST BE WITHIN 6' OF THE BREAK TO
 THE VENT SEE TABLE 906.1.
 3. ONE SET OF PLANS NOT SIGNED OR SEALED.
 ONE PAGE P-2 MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-02-12 Cont ID  
Sent By choops Date 2008-02-12 Time 10:58 Rev Time 0.00
Received By choops Date 2008-02-12 Time 10:58 Sent To E
Notes
2008-02-12 11:02:42***APPROVED - RESUB #2***
  
 PROVISOS:
  
 1)CHIMNEY MAY NOT EXCEED 33' MEASURED FROM GRADE
 (30' ALLOWABLE, PLUS 3' FOR ACCESSORIES).
  
 2)OVERHANG DIMENSIONS OF 3' THAT IS ALLOWED TO
 ENCROACH SETBACKS IS MEASURED FROM THE WALL TO THE
 OUTERMOST POINT OF THE ROOF.
  
 3)PALM TREE SUBSTITUTION EXCEEDS THE 35% ALLOWABLE
 LIMIT.TWO (2) SHADE TREES SHALL BE PROVIDED.
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-22 Cont ID  
Sent By choops Date 2007-08-22 Time 15:48 Rev Time 0.00
Received By choops Date 2007-08-22 Time 15:48 Sent To E
Notes
2007-08-22 16:04:07***FAILED***
  
  
 1)EAST SIDE SETBACK DIMENSION SHALL BE SHOWN FROM
 PROPERTY LINE TO THE PROPOSED BUILDING. (REQUIRED 10')
  
 2)CHIMNEY SETBACK DIMENSION SHALL BE SHOWN FROM
 PROPERTY LINE THE THE EDGE OF CHIMNEY.(MAY ENCROACH
 UP 18" INTO 10' REQUIRED SETBACK)
  
 3)PROVIDE A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 THE CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS, SECTION 94-442.
  
 4)WALL TO BE UNDER SEPARATE PERMIT.POOL TO BE
 UNDER SEPARATE PERMIT.PLANS SHALL INDICATE SUCH.
  
 5)ELEVATION DIMENSIONS TO BE MEASURED FROM GRADE.
  
 6)SHEET A.4 SHOWS OVERHANG AT REAR OF BUILDING, THE
 SITE PLAN SHOWS NONE, CLARIFY.SHEET A.5 DETAIL 5
 SHOWS THE ROOF BRACKET AT 3'7"(CAN ONLY ENCROACH A
 MAXIMUM OF 3' INTO A REQUIRED SETBACK)
  
 7)SHEET A.2 SHOWS FRONT PORCH AT A DEPTH OF 3' , THE
 DETAIL ON SHEET A.6 SHOWS IT AT A DEPTH OF 3'6".
 CLARIFY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-28 Cont ID  
Sent By mmclean Date 2006-12-28 Time 09:21 Rev Time 0.00
Received By rmcdouga Date 2007-09-18 Time 17:08 Sent To M
Notes
2006-12-28 10:10:56DENIED,
 1. SITEPLANS SUBMITTED DOES NOT PROVIDE THE ADDRESS OF
 THE PROPERTY
 2. PLEASE SHOW THE PROPOSED DRIVEWAY AND PROVIDE THE
 WIDTH & LENGTH.
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF LANDSCAPE,
 WHICHEVER IS LESS WITHIN THE FIRST 25FT FRONT SETBACK.
  
 3. MUST PULL A SEPARATE PERMIT FOR WALL/GATE/FENCE WITH
 EASEMENT APPROVAL FROM THE CITY OF WEST PALM BEACH
 UTILITY DEPT.
 4. BALCONY SHALL NOT EXTEND FARTHER THAN THREE FEET
 INTO ANY SETBACK (SEC 94-305(2), FLOOR PLANS A.2 SHOWS
 THE BALCONY PROJECTING 3'-6".
 5. THE ROOF OVER THE BALCONY SHALL NOT PROJECT NO
 FARTHER THAN THREE FEET AS THE BALCONY.ROOF CANNOT
 PROJECT FURTHER THAN BALCONY. (SEC 94-305(2)
 6. BAY WINDOW MAY NOT PROJECT MORE THAN 18INCHES INTO
 ANY SIDE SETBACK SEC 94-305(8)
 7. CHIMNEY MAY PROJECT NO MORE THAN 18 INCHES INTO ANY
 SETBACK SEC94-305(10). A.2 SHOWS THE CHIMNEY PROJECTING
 3FT INTO SIDE SETBACK. A.6 PLANS
 8. SHALL SHOW THE APPROACH FOR THE PROPOSED DRIVEWAY.
 9. SITEPLANS SUBMITTED HAS INSUFFICIENT INFORMATION FOR
 A COMPLETE ZONING REVIEW.
  
 NOTE: THE PROPOSED A/C UNIT SHALL NOT BE CLOSER THAN
 1FT FROM SIDE PROPERTY LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720