Plan Review Details - Permit 06120663
Plan Review Stops For Permit 06120663
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-31 Cont ID  
Sent By mjacobs Date 2007-01-31 Time 12:15 Rev Time 0.00
Received By mjacobs Date 2007-01-31 Time 05:53 Sent To PC
Notes
2007-01-31 06:44:21BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. SUBMIT PRODUCT APPROVAL
 FOR NEW ROLL-UP DOOR.
  
 4)SHOW THE STRUCTURAL SUPPORT IN DETAIL WHERE THE
 WALL WILL BE REMOVED AND THE ROLL-UP DOOR WILL BE
 INSTALLED.
  
 5)THE ARCHITECT SEAL SHALL BE CLEAR AND LEGIBLE ON
 ALL SHEETS. SEE THE SEAL OF JOBY L. BALINT. HIS NAME IS
 NOT LEGIBLE ON THE SEAL,F.S. 481.221(2).
  
 6)THE DRAWINGS SHOWS TENANT 101 AND TENANT 103. WILL
 THERE BE ONE TENANT OR TWO? INDICATE THE SQUARE FOOTAGE
 OF EACH TENANT SPACE. THE DRAWINGS SHALL ALSO SHOW THE
 SQUARE FOOTAGE OF THE STORAGE AND BUSINESS AREA.
  
 7)THE MATERIALS AND PRODUCTS WHICH WILL BE STORED IN
 THE STORAGE AREA SHALL BE INDICATED ON THE DRAWINGS SO
 THAT THE CORRECT WALL AND FLOOR SEPERATIONS ARE
 INSTALLED PER FBC. TABLE 302.3.2 AND FBC 708.
  
  
 8) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R.
  
 9)11-4.1.3 (12) STORAGE, SHELVING AND DISPLAY UNITS.
  
 (A) IF FIXED OR BUILT-IN STORAGE FACILITIES SUCH AS
 CABINETS, SHELVES, CLOSETS, AND DRAWERS ARE PROVIDED IN
 ACCESSIBLE SPACES, AT LEAST ONE OF EACH TYPE PROVIDED
 SHALL CONTAIN STORAGE SPACE COMPLYING WITH SECTION
 11-4.25 . ADDITIONAL STORAGE MAY BE PROVIDED OUTSIDE OF
 THE DIMENSIONS REQUIRED BY SECTION 11-4.25 .
 (B)SHELVES OR DISPLAY UNITS ALLOWING SELF-SERVICE
 BY CUSTOMERS IN MERCANTILE OCCUPANCIES SHALL BE LOCATED
 ON AN ACCESSIBLE ROUTE COMPLYING WITH SECTION 11-4.3 .
 REQUIREMENTS FOR ACCESSIBLE REACH RANGE DO NOT APPLY.
  
 10)WHERE IS THE SECONDARY MEANS OF EGRESS? ONE SHOWS
 SOME STAIRS, SO, HOW WILL THIS MEET THE ACCESSIBILITY
 REQUIREMENTS.SEE SHEET AO.O2
  
 11)SHOW THE ELEVATION DRAWINGS OF THE DELIVERY AREA.
 ARE THERE ANY ACCESSIBILE RAMPS? IF SO, INDICATE THE
 SLOPE.
  
  
 ) 106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES. THE DRAWINGS SHALL BE DIMENTIONED. SHOW ALL
 THE DIMENTIONS OF ROOMS, CORRIDORS AND DOORS ETC.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-14 Cont ID  
Sent By dpalmer Date 2007-01-14 Time 18:04 Rev Time 0.00
Received By dpalmer Date 2007-01-14 Time 17:17 Sent To  
Notes
2007-01-14 18:04:29** UNSAT **
  
 1) NOTE: PLEASE SEE THE PLANS SHALL STATE THE INTENDED
 OCCUPANCY AND TENANT MATERIALS.
 PLEASE SEE THE DELIVERY AREA STATES A CHAINS LINK FENCE
 FOR WHAT SEEMS LIKE IT SHOULD BE A TENANT SEPARATION?
 PLEASE KNOW THIS INFORMATION IN QUESTION HAS BEEN
 FORWARDED TO THE PLAN REVIEW STAFF WHICH WAS PART OF
 THE PREVIOUS PROJECT FOR THE ADJACENT BUILD OUT.
 TENANT SEPARATION?
 PLEASE KNOW THAT DUE TO THIS INFORMATION NOT STATED ON
 PLANS, SOME ITEMS FOR CODE COMPLIANCE REVIEW CAN NOT BE
 DONE AT THIS TIME.
 NEC 500.
  
 2) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON
 PLANS FOR THE DESIGNS WHICH THEY ARE UNDER.
 PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER
 DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE
 RELEVANT.
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70
 (NEC).
 PLEASE SEE THE OTHER CODES WHICH ARE STATED ON PLANS
 FOR ELECTRICAL SHEETS WHICH ARE ALREADY STATED ARE:
 2002 NFPA-72 AND 2003 NFPA-101.
  
 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER
 13-415.1.AB.1, PERFORMANCE CALCULATIONS PER 13-415.2.
 THESE ARE REQUIRED TO BE SIGNED DATED AND SEALED BY THE
 DESIGNER OF RECORD.
 PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES
 TO BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION
 ON PLANS. PLEASE BE SURE TO CORRELATE WITH THE
 PERFORMANCE CALCULATIONS AND ENERGY CALCULATIONS.
 PLEASE SEE THE METHOD B SUBMITTED DOES NOT INDICATE
 AUTOMATED CONTROLS ETC.
 PLEASE SEE LIGHTING DENSITIES.
 PLEASE CLARIFY HOW FINE STORAGE IS DETERMINED. THIS
 SHALL BE REVIEWED BY THIS OFFICE FOR FINAL
 DETERMINATION FOR LIGHTING ALLOWANCE.
 PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR LIGHTING
 ALLOWANCE AND SHOW COMPLIANCE.
 NOT ENOUGH INFORMATION ON LIGHTING ALLOWANCES IS
 PROVIDED.
  
 4) NOTE: PLEASE SEE THE 2006 REVISIONS TO THE 2004 FBC
 CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SUBMIT AUTOMATED LIGHTING CONTROL METHODS,
 SCHEDULING, DEVICES AND TYPES OF DEVICES.
 PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE
 DEVICES. (30 MINS FOR OCCUPANCY TYPE AND 4HRS MAX FOR
 TIMER TYPE.
 PLEASE PROVIDE A DETAIL FOR THE CIRCUITING THE
 EMERGENCY AND EXIT LIGHTS. (THERE IS A NOTE ON PLANS,
 HOWEVER SUBMIT DETAIL AS NUMEROUS SITUATIONS IN THE
 JURISDICTION HAS HAD THESE FIXTURES BEING WIRED ON THE
 LOAD SIDE OF THESE DEVICES.
 PLEASE KNOW AS NO INFORMATION WAS SUBMITTED FOR REVIEW,
 A COMPLETE REVIEW FOR COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
  
 5) NOTE: PLEASE PROVIDE PHOTO-METRICS FOR THE EGRESS
 AREAS TO THE PUBLIC RIGHT OF WAY INCLUDING STAIRS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2
  
 6) NOTE: PLEASE COMPLETE SERVICE RISER DIAGRAM WITH THE
 FOLLOWING INFORMATION NOT SHOWN.
 PLEASE SEE MISSING CONDUCTORS FROM GUTTER TO METER AND
 TO MAIN.
 PLEASE SEE MISSING SIZE AND OVER CURRENT PROTECTION OF
 MAIN.
 PLEASE SE MISSING AIC RATING FOR NEW MAIN. (EVEN THOUGH
 NOTE IS ON 801 FOR OTHER EQUIPMENT).
 PLEASE INDICATE A "FOATING NEUTRAL"AT THE NEW METER.
 PLEASE REMOVE ALL REFERENCES TO "BUILDING #4"MAIN/
 SERVICE AS THERE IS ONLY ONE SERVICE ON THIS BUILDING.
 PLEASE SEE NOTES ON RISER.
 PLEASE PROVIDE THE COMPLETE RISER AND LOADS ON THE
 EXISTING RISER WITH NEW LOADS BEING ADDED.
  
 215.5, 215.3, 220.12, 220.14, 220.42, 220.42 ETC
 110.9, 250.6, 250.24B, ETC
 FBC 106.1.2 , 106.3.5.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR HORN,
 STROBES AND/OR HORN STROBE DEVICES PER FBC 11-4.28.1,
 .2 AND .3(4).
 THE INSTALLATION OF ANY ADDITIONAL DEVICES TO THE
 EXISTING FIRE ALARM SYSTEM WILL BE REQUIRED UNDER
 SEPARATE PLANS, PERMIT, HOWEVER THESE REQUIRED LEVELS
 ARE TO BE SHOWN ON BASE PLANS.
  
 8) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS EMERGENCY
 LIGHTS AND EXIT LIGHTS ON THEIR OWN CIRCUIT?
 PLEASE SEE 700.12E.
  
 9) NOTE: PLEASE BE SURE TO INDICATE ALL CIRCUITS ON
 PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE.
 106.1.2, 106.3.5.1.2
 NEC 408.4, 310.16, 240.4 FOR VERIFICATION.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT SUBMITTED A
 ND CHANGES IN PLANS WILL BE REQUIRED, THERE MAY BE
 COMMENTS ON THE NEXT REVIEW DUE TO ANY POSSIBLE
 CHANGES.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-30 Cont ID  
Sent By mwennerg Date 2007-01-30 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2007-01-30 Time 11:06 Sent To  
Notes
2007-01-30 11:16:40***DENIED***
  
 1) NFPA 101, AND NFPA 1, 2003 EDITION SHALL BE
 REFERENCED. PLEASE CORRECT ON SHEET A0.02.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY
 WITH NFPA 241.
  
 3) ALL NEW FIRE DAMPER INSTALLATIONS TO BE TESTED FOR
 CLOSURE IN ACCORDANCE WITH UL REQUIREMENTS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 5) ADDRESS SUITE NUMBER TO BE DISPLAYED AT FRONT DOOR
 ENTRANCE, AND BACK ENTRANCE WHERE APPLICABLE. SUITE
 NUMBERS SHALL BE AT LEAST 3" IN HEIGHT AND CONTRASTNG
 TO THE BACKGROUND.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-01-31 Time   Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 11:02 Sent To  
Notes
2007-01-09 14:23:13TO "BOB"#18
2006-12-27 11:03:52WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-16 Cont ID  
Sent By tgordon Date 2007-01-16 Time 12:04 Rev Time 1.00
Received By tgordon Date 2007-01-16 Time 12:04 Sent To  
Notes
2007-01-16 12:24:21*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) SEE PAGE M101 EF-1, SEE HIGH LIGHTED 4_ M701 AND
 HIGH LIGHTED EXISTING O/A, PLEASE REMOVE THESE
 NOTATIONS AS THIS IS AN EXHAUST FAN.
  
 3) SEE PAGE M101, ALL RETURN AIR GRILLS NOTEDAA/-,
 CAN NOT DETERMINE SIZE, PLEASE CORRECT.
  
 4) SEE PAGE M801 EQUIPMENT SCHEDULE, CONDENSER UNIT,
 RATING EER, DO YOU MEAN SEER, IF SO PLEASE CORRECT.
  
 5) SHOW MODEL NUMBERS FOR ALL AHU'S AND CONDENSER UNITS
 IN EQUIPMENT SCHEDULE.
  
 6) A FIRE DAMPER IS REQUIRED AT 8" SUPPLY DUCT
 PENETRATING FIRE RATED WALL IN CORRIDOR, PER 2004 FBC/M
 607.5.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-20 Cont ID  
Sent By jleech Date 2007-01-20 Time 07:30 Rev Time 0.00
Received By jleech Date 2007-01-20 Time 07:30 Sent To  
Notes
2007-01-20 07:49:37DENIED;
 1.FBC-2004 PLUMBING TABLE 403.1 (8S) ONE SEVICE SINK IS
 REQUIRED. LOCATION OF DRINKING FOUNTAIN IS NOT SHOWN.
 ALSO SHOW DRINKING FOUNTAIN ELEVATION ON PAGE A3.01 AND
 FIXTURE SCHEDULE PAGE P001.
 2. LIST MATERIAL TO BE STORED TO DETERMINE IF A
 EMERGENCY SHOWER AND EYEWASH STATION IS REQUIRED.
 3.PAGE P001 PLUMBING FIXTURE SCHEDULE LISTS BATHROOM #
 106 NOT SHOWN ON PLANS, SHOW LOCATION.
 4. CONDENSATE PIPE TO BE SUPPORTED EVERY 4' IF PVC OR
 EVERY 10' IF COPPER, PER TABLE 308.5 ADD NOTE TO PLAN
 AND SPEC OUT MATERIAL TO BE USED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695