Plan Review Details - Permit 06120650
Plan Review Stops For Permit 06120650
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-04-26 Cont ID  
Sent By shill Date 2007-04-26 Time 17:33 Rev Time 0.00
Received By shill Date 2007-04-26 Time 17:33 Sent To  
Notes
2007-04-26 17:34:06REVISED1.0A DATED 4/18/07

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-22 Cont ID  
Sent By shill Date 2007-03-22 Time 10:40 Rev Time 0.00
Received By shill Date 2007-03-22 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-05 Cont ID  
Sent By shill Date 2007-02-05 Time 08:49 Rev Time 0.00
Received By shill Date 2007-02-05 Time 08:49 Sent To  
Notes
2007-02-05 08:52:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PLEASE SIGN OWNER/AGENT LINE OF ENERGY CALC.THIS
 MAY BE DONE BY MAKING AN APPOINTMENT, ESPECIALLY IF THE
 PLAN PASSES ALL REVIEWS OTHERWISE.
  
 PROVISO ITEM, NO PRODUCT APPROVALS SUBMITTED; WILL
 REQUIRE SEPARATE PERMITS:
  
 5.)PROVIDE PRODUCT APPROVALS FOR THE NEW WINDOWS.
 FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 FAC9B72.
  
 6.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-09 Cont ID  
Sent By shill Date 2007-01-09 Time 14:18 Rev Time 0.00
Received By shill Date 2007-01-09 Time 14:18 Sent To  
Notes
2007-01-09 14:55:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)SHEET 1.0A NEW INTERIOR PARTITION, TEXT STATES
 FIRESTOP BUT NOTHING SHOWN GRAPHICALLY.
  
 3.)THE FLOOR PLAN SHOWS A TABLE BLOCKING THE FRONT
 DOOR.
  
 4.)DECLARE WIND DESIGN CRITERIA, FBC 1603.1.4.
  
 5.)PROVIDE PRODUCT APPROVALS FOR THE NEW WINDOWS.
 FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 FAC9B72.
  
 6.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 7.)INCLUDE FBC EB IN GOVERNING CODE.DECLARE LEVEL
 OF ALTERATION, FBC EB 3.
  
 8.)SEE FBC 11-4.1.6(2).SHOW COMPLIANCE ON THE PLAN.
 IF NECESSARY, PROVIDE COST INFORMATION.
  
 9.)IS THIS A CHANGE OF OCCUPANCY?WHAT IS THE
 OCCUPANCY OF THE ADJACENT TENANT?
  
 10.)SHEETS 3.1M AND 3.2M REFER TO THE WRONG BUILDING
 CODE (FBC2001).
  
 11.)ADDRESS ADDITTIONAL LOAD ON THE ROOF (MECHANICAL
 EQUIPMENT).
  
 12.)PROVIDE INFORMATION IN REGARDS TO HOW YOU
 DETERMINED OCCUPANT LOAD.SEE FBC 1004, CANNOT BE LESS
 THAN TABLE 1004.1.2.USING SQUARE FOOT AREA AND THE
 TABLE, M OCCUPANCY WOULD BE AN OCCUPANT LOAD OF 59. M
 IS FOR LESS THAN 50, OTHERWISE IS A AND NEEDS TWO MEANS
 OF EGRESS.PLEASE ADDRESS.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 1.30
Received By jleahy Date 2007-04-16 Time 15:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-03-23 Cont ID  
Sent By dpalmer Date 2007-03-23 Time 09:44 Rev Time 0.00
Received By dpalmer Date 2007-03-23 Time 08:28 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-08 Cont ID  
Sent By dpalmer Date 2007-03-08 Time 07:54 Rev Time 0.00
Received By dpalmer Date 2007-03-08 Time 07:05 Sent To  
Notes
2007-03-08 07:55:18*** UNSAT 3RD REVIEW ***
  
 1) NOTE: PLEASE SEE THE FIRST REVIEW WHICH REQUESTED
 NEW CODES TO BE PLACED ON PLANS.THIS WAS DONE AND
 CORRECTED ON PREVIOUS REVIEW HOWEVER PLEASE SEE NEW
 ELECTRICAL NOTES NOW ADDED TO SHEET 2.0E CONTAINS THE
 WRONG CODES FOR THE NEC AND THE YEARS FOR THE LS 101
 AND NFPA-72 ARE NOT SHOWN.
 PLEASE LIST AS STATED ON FIRST REVIEW NOTES
 2005 NFPA-70 (NEC)
 2003 NFPA-101( LIFE SAFETY CODE)
 2002 NFPA-72
 * THE CORRECT CODE FOR THE FBC 2004 W/ 2006 REVISIONS
 WAS ADDED.
  
 2) NOTE: PLEASE SEE FIRST REVIEW NOTES WHICH MENTIONED
 THAT THE RISER SHOWS A PANEL *H* AND BOTH PANEL
 SCHEDULES SUBMITTED WERE A AND B. THIS WOULD HAVE BEEN
 REDLINED, HOWEVER AS PLANS ARE COMING BACK FOR OTHER
 CORRECTIONS PLEASE CORRECT AT THIS TIME.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AND THE
 PLANS DO NOT CORRELATE.
 PLEASE SEE THE FIXTURE LEGEND WHICH THE 2X4 FLUORESCENT
 FIXTURES ARE SHOWING A #=# FOR THE LAMPS??
 PLEASE SEE MANY OF THE FIXTURES INDICATE SOME SORT OF
 1-L, 2-L, 3-L AND 4-L ON THEM, HOWEVER NOT ALL.
 PLEASE SEE OF THIS IS FOR THE NUMBER OF LAMPS IN EACH
 FIXTURE THIS DOES NOT CORRELATE WITH THE CALCULATIONS.
 PLEASE KNOW EVEN IF THIS IS NOT THE NUMBER OF LAMPS AND
 THE NUMBER OF LAMPS ON EACH IS DIVIDED BY THE TOTAL
 FIXTURE WATTAGE ON CALCULATIONS MAKING THESE ALL FOUR
 LAMPS FIXTURES AT 32W EACH, THIS WOULD STILL NOT
 CORRELATE WITH ALL FIXTURES ON PLANS AND ENERGY
 CALCULATIONS.
 PLEASE SEE MEN'S AND WOMEN'S BATHROOMS. HOW DOES EACH
 OF THESE SHOW 64 WATTS ON LOAD CALCULATIONS IF THESE
 FIXTURES ARE 4-LAMP? PLEASE SEE THE FIXTURE LEGEND DOES
 NOT LEND ANY INFORMATION ON TWO TYPES OF 2X4 FIXTURES?
 PLEASE SEE THE SCONE AS SHOWN ON PLANS COULD NOT FOUND
 FIGURED INTO CALCULATIONS.
 PLEASE SEE THE ONE BATHROOM SHOWS 2-2X2 FIXTURES AND AS
 FIXTURE LEGEND STATES THESE ARE 2-32W LAMPS IN EACH,
 YET THE CALCULATIONS ONLY SEEM TO INDICATE ONE FIXTURE
 AT 64W'S??
 * PLEASE SEE THE ENERGY CALCULATIONS *INPUT DATA* FOR
 ELECTRICAL IS THE SAME SHEETS IN WHICH THIS REVIEWER
 HAD REDLINED AS THE SAME CIRCLES PREVIOUSLY PLACED ON
 THEM DURING REVIEW ARE NOW BACK ON SHEETS.
  
 4) NOTE: NOTICE TO THE ENGINEER. IT IS THE
 RESPONSIBILITY OF THE ENGINEER OF RECORD TO REVIEW ALL
 PLANS AND DOCUMENTS UNDER HIS DIRECT SUPERVISION BEFORE
 SIGNING, DATING AND SEALING SAID PLANS OR DOCUMENTS.
 SEE FLORIDA STATUTES 471.025(2).
 PLEASE KNOW ONE SET OF ELECTRICAL PLANS AND ENERGY
 CALCULATIONS ARE BEING RETAINED AND PLACED WITH
 PREVIOUS RETAINED PLANS FOR POSSIBLE REVIEW FROM THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
 PLEASE ALSO SEE THE EXACT TEXT EXTRACTED FROM PART
 (3).
 ************************************************
 (3)NO LICENSEE SHALL AFFIX OR PERMIT TO BE AFFIXED
 HIS OR HER SEAL, NAME, OR DIGITAL SIGNATURE TO ANY
 PLAN, SPECIFICATION, DRAWING, FINAL BID DOCUMENT, OR
 OTHER DOCUMENT THAT DEPICTS WORK WHICH HE OR SHE IS NOT
 LICENSED TO PERFORM OR WHICH IS BEYOND HIS OR HER
 PROFESSION OR SPECIALTY THEREIN. *
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-05 Cont ID  
Sent By dpalmer Date 2007-02-05 Time 16:00 Rev Time 0.00
Received By dpalmer Date 2007-02-05 Time 13:12 Sent To  
Notes
2007-02-05 16:00:56******* UNSAT 2ND REVIEW ******
  
 *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
  
 **** IMPORTANT****
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*.
  
 A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY
 THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE
 PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE
 #1**
  
 B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND LABELED **
 NEW NOTES **
  
  
  
 1) NOTE: OK.
  
 2) NOTE: NO.
 PLEASE SEE THERE WERE NO TIMES SUBMITTED.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH THE FIXTURES, WATTAGES, THE NUMBER OF
 FIXTURES, AND THE TYPE OF FIXTURES ETC WHICH ARE ON
 PLANS.
 PLEASE SEE THE CALCULATIONS SUBMITTED AND COORDINATE
 WITH PLANS.
  
 ** PREVIOUS REVIEW NOTE REVIEW#1**
 PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND
 .1.3
 PLEASE INDICATE SCHEDULING, OVER RIDE DEVICES AT
 INGRESS/EGRESS, SEPARATE SPACES, TIMES ON ALL OVER RIDE
 DEVICES.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, AND 13-415.2.ABC.1
 ENERGY CALCULATIONS ARE SUBMITTED HOWEVER THEY ARE NOT
 SIGNED, DATED OR SEALED BY THE ENGINEER OF RECORD.
 PLEASE CLARIFY PERFORMANCE CALCULATIONS AND HOW METHOD
 A CAN BE USED ON AN EXISTING SPACE OR IS THIS AN
 EXISTING SHELL WITH NEW EXTERIOR WALL BEING BUILD OUT
 FOR INTERIOR USE.
  
 3) NOTE: OK.
  
 4) NOTE: NO, PLEASE SEE COMMENTS FROM FIRE REVIEW WHERE
 COOKING WITH GREASE LADEN VAPORS WHICH WILL REQUIRE A
 HOOD OF SORTS, AND AS THIS APPEARS TO BE THE CASE,
 ELECTRICAL FOR HOOD NEEDS TO BE SHOWN. THERE IS NOTHING
 LOCATED ON PLANS FOR SUCH AND ANY SHUT OFF OF ANY
 ELECTRICAL UNDER HOOD (WHERE ELECTRIC IS INSTALLED).
 PLEASE SEE COMMENT #7 WITH RESPECT TO MISSING
 CIRCUITING ON PLANS.
  
 **PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE NFPA-96 AND CLARIFY ANY LIGHTING AND
 ELECTRICAL WHICH MAY BE PART OF ANY HOOD SYSTEM WHICH
 IS REQUIRED TO CONTAIN SHUNT TRIP DEVICES/BREAKERS.
  
 5) NOTE: NO? NO NOTES, RESPONSE OR NOTES COULD BE FOUND
 AND PANELS SCHEDULE DOES NOT SEEM TO INDICATE ANY
 ELECTRICAL FOR THIS, NEW OR EXISTING.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE CLARIFY NEW OR EXISTING ROOF TOP GFI FOR THE RTU
 A/C SYSTEM.
 210.63, 210.8
  
 6) NOTE: OK.
  
 7) NOTE: NO.
 PLEASE SEE THERE ARE SEVERAL ITEMS ON PLANS WHICH DO
 NOT CORRELATE WITH THE PANEL SCHEDULES.
 PLEASE SEE THERE ARE ITEMS ON PANEL SCHEDULES NOT ON
 PLANS.
 PLEASE SEE THERE ARE ELECTRICAL ITEMS ON PLANS (LIGHTS)
 WHICH DO NOT INDICATE ANY CIRCUITING.
 PLEASE SEE PANEL SCHEDULE WHICH DOES NOT INCLUDE ALL
 CIRCUITS ON PLANS.
 PLEASE SEE ITEMS ON PANEL SCHEDULE SHOWN AS 220V , YET
 ON 1-POLE BREAKERS.
 ETC.
 ONE SET OF PLANS HAS MANY OF THESE ITEMS REDLINED,
 HOWEVER NOT ALL.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE PROVIDE ALL CIRCUITING ON PLANS AND CORRELATE
 WITH THE SUBMITTED PANEL SCHEDULE(S). PLEASE SEE SOME
 MISSING FOR LIGHTING, RECEPTS ETC.
 FBC 106.1.2, 106.3.5.1.2, NEC 408.4, 310.16 ETC
  
 8) NOTE: NO, PLEASE SEE AS NOTE #7 ABOVE MENTIONS,
 PLEASE SEE FIXTURE(S) WHICH CIRCUITING IS MISSING.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE 700.12 FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE:
  
 13) NOTE: OK.
  
 14) NOTE: OK, VALUE INCREASED.
  
 15) NOTE: OK.
  
 16) NOTE: NO, SAME NOTE. PLEASE SEE THE FOLLOWING IS
 TEXT EXTRACTED FROM THE CODE TO HELP EXPLAIN THE
 PREVIOUS NOTE AS NO CHANGES WERE MADE TO THIS COMMENT.
 *SECTION 210.8(B)(2), WHICH WAS NEW FOR THE 2002 CODE,
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT RECEPTACLES IN
 NON-DWELLING-TYPE KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO ALL 15- AND 20-AMPERE, 125-VOLT
 KITCHEN RECEPTACLES, WHETHER OR NOT THE RECEPTACLE
 SERVES COUNTERTOP AREAS.*
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE 210.8B3 FOR GFP PROTECTION FOR ALL 15/20A
 120V RECEPTS IN KITCHEN/ KITCHEN AREAS.
  
  
 *** NEW NOTE **
  
 17) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTE GIVEN AT THIS TIME.
 ONE SET OF ELECTRICAL PLANS AND ENERGY CALCULATIONS ARE
 BEING RETAINED BY THIS OFFICE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-10 Cont ID  
Sent By dpalmer Date 2007-01-10 Time 19:44 Rev Time 0.00
Received By dpalmer Date 2007-01-10 Time 19:44 Sent To  
Notes
2007-01-10 19:42:52** UNSAT **
  
 1) NOTE: PLEASE BE SURE ALL PLANS STATE THE FOLLOWING
 MINIMUM CODES IN WHICH PLANS ARE DESIGNED AND PERMITTED
 UNDER.
 PLEASE KNOW THE FOLLOWING WILL BE REQUIRED FOR
 ELECTRICAL SHEETS.
 2005 NFPA-70 *JUST AS AN FYI AS OF 12/8/06 THE STATE OF
 FLORIDA ADOPTED THE NEW 2005 NEC AND ANY PERMIT
 APPLICATIONS MADE FROM THAT DATE FORWARD WILL BE UNDER
 THE NEW CODE AND THE 2006 REVISIONS TO THE 2004 FBC.
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3
 PLEASE INDICATE SCHEDULING, OVER RIDE DEVICES AT
 INGRESS/EGRESS, SEPARATE SPACES, TIMES ON ALL OVER RIDE
 DEVICES.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, AND 13-415.2.ABC.1
 ENERGY CALCULATIONS ARE SUBMITTED HOWEVER THEY ARE NOT
 SIGNED, DATED OR SEALED BY THE ENGINEER OF RECORD.
 PLEASE CLARIFY PERFORMANCE CALCULATIONS AND HOW METHOD
 A CAN BE USED ON AN EXISTING SPACE OR IS THIS AN
 EXISTING SHELL WITH NEW EXTERIOR WALL BEING BUILD OUT
 FOR INTERIOR USE.
  
 3) NOTE: PLEASE SEE INFORMATION ON TITLE BLOCKS
 REFLECTS METRO DESIGN GROUP WHICH MUST BE LICENSED
 THROUGH THE STATE OF FLORIDA FOR PROVIDING ENGINEERING
 SERVICES.
 PLEASE SEE THAT THIS HAS BEEN NOTED ON PREVIOUS REVIEWS
 ON OTHER PROJECTS AND MAY BE SENT TO THE FLORIDA BOARD
 OF ENGINEERS FOR REVIEW.NO DETERMINATION FROM THE
 STATE HAS BEEN MADE AT THIS POINT IN TIME.
 FS 471.023, 481.229, FAC 61G15-23.002 ETC
 ONE SET OF PLANS WILL BE RETAINED BY THIS OFFICE AT
 THIS TIME.
  
 4) NOTE: PLEASE SEE NFPA-96 AND CLARIFY ANY LIGHTING
 AND ELECTRICAL WHICH MAY BE PART OF ANY HOOD SYSTEM
 WHICH IS REQUIRED TO CONTAIN SHUNT TRIP
 DEVICES/BREAKERS.
  
 5) NOTE: PLEASE CLARIFY NEW OR EXISTING ROOF TOP GFI
 FOR THE RTU A/C SYSTEM.
 210.63, 210.8
  
 6) NOTE: PLEASE SEE 220.12A FOR DETERMINING LOAD
 CALCULATIONS FOR SERVICE FEEDERS ON WINDOWS. PLEASE SEE
 QUOTED COMMENTARY.
 "THE 200-VOLT-AMPERE CALCULATION FOR EACH LINEAR FOOT
 OF A SHOW WINDOW IS REQUIRED TO DETERMINE THE FEEDER
 LOAD. SEE THE COMMENTARY FOLLOWING 220.3(B)(7) FOR LOAD
 CALCULATIONS FOR BRANCH CIRCUITS IN SHOW WINDOWS."
  
 7) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULE(S). PLEASE
 SEE SOME MISSING FOR LIGHTING, RECEPTS ETC.
 FBC 106.1.2, 106.3.5.1.2, NEC 408.4, 310.16 ETC
  
 8) NOTE: PLEASE SEE 700.12 FOR CIRCUITING OF EMERGENCY
 AND EXIT LIGHTS.
  
 9) NOTE: PLEASE SEE KITCHEN/KITCHEN PREP AND EAT IN
 AREAS SHALL CONTAIN A MINIMUM OF 1FT CANDLE FOR MEANS
 OF EGRESS TO THE PUBLIC RIGHT OF WAY. BASED ON THE TWO
 FIXTURES SHOWN THIS DOES NOT SEEM TO HAVE BEEN MET.
 PLEASE EITHER PROVIDE PHOTO-METRICS FOR EGRESS PATHS OR
 ADD AN ADDITIONAL TWO EMERGENCY LIGHT FIXTURES.
  
  
 10) NOTE: PLEASE PROVIDE MORE INFORMATION FOR THE
 EXISTING SERVICE.PLEASE SEE THE EXISTING SERVICE
 CONDUCTORS FROM THE GUTTER TO THE MAIN ARE SHOWN FOR A
 THREE PHASE SERVICE, YET RISER AND PANELS BOTH SHOW A
 SINGLE PHASE SERVICE.
 PLEASE COORDINATE.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
  
 11) NOTE: PLEASE SEE RISER, RISER SHOWS A 200A PANEL
 "H", YET NO PANEL SCHEDULE HAS BEEN SUBMITTED FOR THIS.
 PLEASE SEE PANEL SCHEDULES SUBMITTED INDICATE A PANEL B
 AND A AND NO PANEL H IS SHOWN. PLEASE SEE PANEL B AND
 AS BEING 100A NOT 200AMP.
 PLEASE CLARIFY THE ENTIRE RISER FOR NEW AND EXISTING.
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE: PLEASE SEE BASED ON THE PANEL SCHEDULE "A",
 CORRELATE THE FEEDERS AND OVER CURRENT PROTECTION WITH
 THE RISER. PANEL SCHEDULE SHOWS THIS A SINGLE POLE
 20AMP CIRCUIT.
 PLEASE SEE NEC 2005, 240.4, 310.16, 215.5 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 13) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 THE EXISTING SERVICE AND THE NEW LOADS BEING ADDED.
 PLEASE SEE NEC 220,
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 14) NOTE: PLEASE KNOW VALUE FOR COMPLETE SCOPE OF WORK
 SHALL INCLUDE ALL LABOR AND MATERIALS WHETHER OR NOT
 EQUIPMENT IS OWNER SUPPLIED. FBC ADMIN SECTION 108.3
  
 15) NOTE: PLEASE INDICATE A "FLOATING NEUTRAL" IS TO BE
 VERIFIED IN WHAT IS SHOWN AS AN EXISTING METER.
 REQUIRED FOR ALL METERS AFTER THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE 250.6, AND 250.24B.
  
 16) NOTE: PLEASE SEE 210.8B3 FOR GFP PROTECTION FOR ALL
 15/20A 120V RECEPTS IN KITCHEN/ KITCHEN AREAS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-03-15 Cont ID  
Sent By mawillia Date 2007-03-15 Time 19:06 Rev Time 0.00
Received By mawillia Date 2007-03-15 Time 18:51 Sent To  
Notes
2007-03-15 19:06:06*****APPROVED*****
  
  
  
 ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEW HAVE BEEN
 ADDRESSED.THE APPROPIATE PLAN SHEET(S) WILL BE
 STAMPED WHEN ALL REVIEWS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-12 Cont ID  
Sent By mawillia Date 2007-02-12 Time 10:47 Rev Time 0.00
Received By mawillia Date 2007-02-12 Time 10:47 Sent To  
Notes
2007-02-12 11:00:54*****DENIED*****
  
  
 PLEASE BE ADVISED THAT THE PREVIOUS PLAN REVIEW
 COMMENTS OF 01/16/2007 STILL HAVE NOT BEEN ADDRESSED
  
  
 4.THE SUITE NUMBER WHERE THE SCOPE OF THE WORK WILL
 BE CONDUCTED SHOULD BE IN THE TITLE BLOCK OF THE
 SUBMITTED PLANS.
  
 6.IS OR WILL THE BUILDING/TENANT SPACE BE EQUIPPED
 WITH A FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM?
  
 7.INDICATE THE LOCATION OF THE FIRE EXTINGUISHER(S).
  
 8.COMMERCIAL COOKING EQUIPMENT WHALL BE IN ACCORDANCE
 WITH NFPA 96.SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED.
  
 9.ON SHEET # 2.0E, LIGHTING PLAN, REAR EXIT (B1)
 CORRECT THE FOLLOWING ISSUE:(2) THERE IS A DOOR THAT
 OPENS INTO THE PATH OF THE REAR EXIT CORRIDOR.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM
 WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-16 Cont ID  
Sent By mawillia Date 2007-01-16 Time 10:29 Rev Time 0.00
Received By mawillia Date 2007-01-16 Time 10:29 Sent To  
Notes
2007-01-16 11:26:16*****DENIED*****
  
  
 1. NFPA 101, 2003 EDITION, SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPNSE ACCESS TO THE
 SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.THE SUITE NUMBER WHERE THE SCOPE OF THE WORK WILL
 BE CONDUCTED SHOULD BE IN THE TITLE BLOCK OF THE
 SUBMITTED PLANS.
  
 5.IT APPEARS THAT THE SCOPE OF WORK IS A CONVERSION
 FROM A BUSINESS OCCUPANCY TO A MERCANTILE OCCUPANCY.
 PLEASE BE ADVISED THAT THIS STRUCTURE SHALL BE
 CONSIDERED AS A NEW MERCANTILE OCCUPANCY.
  
 6.IS OR WILL THE BUILDING/TENANT SPACE BE EQUIPPED
 WITH A FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM?
  
 7.PROVIDE A LIFE SAFETY PLAN SHEET SHOWING THE TRAVEL
 DISTANCE TO REACH AN EXIT.THE LOCATION OF EXIT
 LIGHTS, EMERGENCY LIGHTS, AND FIRE EXTINGUISHERS MAY
 ALSO BE INCLUDED.
  
 8.COMMERCIAL COOKING EQUIPMENT WHALL BE IN ACCORDANCE
 WITH NFPA 96.SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED.
  
 9.ON SHEET # 2.0E, LIGHTING PLAN, THERE ARE TWO EXITS
 NOTED.CORRECT THE FOLLOWING ISSUES:(1) THE FRONT
 EXIT DOOR WOULD NOT BE ABLE TO OPEN FULLY DUE TO THE
 FURINITURE (2) THERE IS A DOOR THAT OPENS INTO THE PATH
 OF THE REAR EXIT CORRIDOR.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM
 WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-05-09 Cont ID  
Sent By mperson Date 2007-05-09 Time 10:11 Rev Time 0.45
Received By mperson Date 2007-05-09 Time 10:11 Sent To PC
Notes
2007-05-09 10:18:27GAS REVISION SHEET 3.0P CHANGED RANGE AND BTU LOAD.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-03-13 Cont ID  
Sent By mperson Date 2007-03-13 Time 08:49 Rev Time 0.33
Received By mperson Date 2007-03-13 Time 08:49 Sent To  
Notes
2007-03-13 08:53:06****************PROVISO****************
 SEPERATE PLANS AND PERMIT REQUIRED FOR BURIED LP TANK
 TO SHUT OFF VALVE.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-02-09 Cont ID  
Sent By mperson Date 2007-02-09 Time 14:28 Rev Time 0.00
Received By mperson Date 2007-02-09 Time 14:28 Sent To  
Notes
2007-02-09 15:13:09DENIED 2ND TIME
 REFERENCE: FBC-2004 FUEL GAS
  
 PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
  
 ****IMPORTANT**** PLEASE SEE THE NOTES BELOW ARE TAKEN
 DIRECTLY FROM THR PREVIOUS REVIEW WITH A (NO). (OK) OR
 (NO/OK).
  
 A) A (NO), WILL CONTAIN A FURTHER EXPLANATION AS TO
 WHY THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH
 THE PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW
 NOTE #1.
  
 B) A (OK), WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE **NEW NOTES** THE PREVIOUS REVIEW NOTE
 WILL BE REMOVED.
  
 C) A (NO/OK), WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW WILL BE NOTED **PREVIOUS REVIEW
 NOTE#1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND BE LABELED
 **NEW NOTES**
  
 1. (NO)SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING
 LENGTHS INDICATED ON SHEET 3.0P GAS RISER. PLEASE
 CORRECT AND RESUBMIT.
  
 2. (OK)
  
 3. (NO)SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: NOW THAT THE GAS TYPE IS INDICATED AS LP, PLEASE
 INDICATE ON THE RESUBMITTED DRAWINGS THE TANK LOCATION,
 LOCATION OF 1ST AND 2ND STAGE REGULATORS AND ALL
 RELATED PIPING WITH CUT LENGTHS AND SIZES.
  
 4. (NO)SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE:PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS
 FOR THE GAS APPLIANCES TO VERIFY BTU LOADS, THE
 EMERGENCY SHUT OFF VALVE TO VERIFY COMPLIANCE AND THE
 1ST AND 2ND STAGE REGULATORS TO VERIFY COMPLIANCE.
  
 **NEW COMMENT**
  
 5. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 6. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 **********IMPORTANT INFORMATION
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-01-16 Cont ID  
Sent By mperson Date 2007-01-17 Time 16:43 Rev Time 0.00
Received By mperson Date 2007-01-16 Time 16:43 Sent To  
Notes
2007-01-16 16:58:09DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PALN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING
 LENGTHS INDICATED ON SHEET 3.0P. GAS RISER PLEASE
 CORRECT AND RESUBMIT.
  
 2. TYPE OF GAS, (LP OR NATURAL)
 NOTE: PLEASE CORRELATE THE TYPE OF GAS BEING USED,
 SHEET 3.0P HAS BOTH NATURAL GAS AND A LP TANK INDICATED
 ON THE GAS RISER.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: EVEN THOUGH A TOTAL LENGTH OF 15' IS INDICATED ON
 THE GAS RISER ON SHEET 3.0P, COMMENT NUMBER ONE (1)
 NEEDS TO BE COMPLETED IN ORDER TO VERIFY THIS COMMENT
 AND THE INDICATED LONGEST LENGTH OF 15'.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS
 FOR THE GAS APPLIANCES AND THE EMERGENCY SHUT OFF
 VALVE.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 10:23 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 10:23 Sent To G
Notes
2007-05-04 10:23:48TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 09:30 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 09:30 Sent To B
Notes
2007-04-20 09:31:06TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 08:28 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 08:28 Sent To E
Notes
2007-04-16 08:28:23TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-07 Cont ID  
Sent By adarroug Date 2007-03-07 Time 14:20 Rev Time 0.00
Received By adarroug Date 2007-03-07 Time 14:20 Sent To  
Notes
2007-03-07 14:25:38TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 11:02 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 11:01 Sent To  
Notes
2007-02-05 08:18:59TO "COMM" BD#11--EXPEDITED PERMIT--
2007-02-01 11:03:07WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-17 Cont ID  
Sent By mperson Date 2007-01-17 Time 08:31 Rev Time 0.00
Received By mperson Date 2006-12-26 Time 14:58 Sent To  
Notes
2007-01-08 19:47:30 
  
  
 ***EPEDITED PLAN REVIEW.RB***
2006-12-26 14:58:31TO "COMM' BD#26
 WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-04-20 Cont ID  
Sent By tgordon Date 2007-03-14 Time 10:31 Rev Time 0.00
Received By tgordon Date 2007-03-14 Time 08:02 Sent To  
Notes
2007-03-14 08:03:04*** PROVISO ***
 1)ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 WALK-IN-COOLERS, FIRE SUPPRESSION, AND HOOD. PLANS NEED
 TO BE SUBMITTED FOR HOOD AND FIRE SUP. AT TIME OF
 APPLICATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-12 Cont ID  
Sent By tgordon Date 2007-02-12 Time 08:14 Rev Time 0.25
Received By tgordon Date 2007-02-12 Time 08:14 Sent To  
Notes
2007-02-12 08:15:50*** PROVISO ***
 1)ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 WALK-IN-COOLERS, FIRE SUPPRESSION, AND HOOD. PLANS NEED
 TO BE SUBMITTED FOR HOOD AND FIRE SUP. AT TIME OF
 APPLICATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-01-09 Cont ID  
Sent By tgordon Date 2007-01-09 Time 12:18 Rev Time 0.45
Received By tgordon Date 2007-01-09 Time 12:18 Sent To  
Notes
2007-01-09 12:27:10*** PROVISO ***
 1) PROVIDE RETURN AIR TO OFFICE, PER 2004 FBC/M 601.4.
  
 2) ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 WALK-IN-COOLERS, FIRE SUPPRESSION, AND HOOD. PLANS NEED
 TO BE SUBMITTED FOR HOOD AND FIRE SUP. AT TIME OF
 APPLICATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-03-13 Cont ID  
Sent By mperson Date 2007-03-13 Time 08:47 Rev Time 0.33
Received By mperson Date 2007-03-13 Time 08:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-09 Cont ID  
Sent By mperson Date 2007-02-09 Time 08:49 Rev Time 0.00
Received By mperson Date 2007-02-09 Time 08:49 Sent To G
Notes
2007-02-09 13:43:44DENIED 2ND TIME
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS;
  
 PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
  
 ****IMPORTANT****
 PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM THE
 PREVIOUS REVIEW WITH A(NO), (OK) OR (NO/OK).
  
 A) A (NO), WILL CONTAIN A FURTHER EXPLANATION AS TO
 WHY THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH
 THE PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW
 NOTE #1
  
 B) A (OK), WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE **NEW NOTES**. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A (NO/OK), WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND BE LABELED
 **NEW NOTES**
  
 1. (NO) SHEET 3.OP INDICATES GREASE TRAP HAS BEED
 WAIVED BY THE CITY OF WEST PALM BEACH WATER UTILITIES.
 NOTE: THERE IS NO WAIVER OF THE GREASE INTERCEPTOR
 PLEASE REFERENCE THE ATTACHED SHEET FROM EVIRONMENTAL
 COMPLIANCE INDICATING A RECOMMENDED INTERCEPTOR SIZE OF
 1250 GAL. PLEASE REVISE RESUBMITTED PRINTS TO REFLECT
 THE REQUIRED 1250 GAL. GREASE INTERCEPTOR. ANY
 QUESTIONS ABOUT THE ATTACHED ENVIRONMENTAL COMPLIANCE
 SHEET PLEASE CONTACT THE FOLLOWING. (UTILITIES REP.)
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE (561) 822-2272.
  
 2. (OK)
  
 3. SHEET 3.0P SANITARY RISER AND PLUMBING PLAN; SHEET
 1.1A EQUIPMENT SCHEDULE;
 A} (OK)
 B} (OK)
 C} (NO} GREASE SYSTEM MUST DRAIN DOWN STREAM OF THE
 WET VENTED BATHROOMS PER FBC-2004, SECTION 909.1. IT IS
 INDICATED CORRECT ON THE PLUMBING PLAN, BUT IS NOT
 BEING INDICATED ON THE SANITARY ISOMETRIC RISER
 DIAGRAM. PLEASE CORRELATE THE DRAWINGS ON THE
 RESUBMITTAL.
 D} (NO) DELETE SAMPLE POINT FROM RESUBMITTED DRAWINGS
 AND ADD REQUIRED 1250 GAL. GREASE INTERCEPTOR.REFERENCE
 COMMENT #1.
 E} (OK)
 F} (OK)
  
 4. PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3 THE
 FOLLOWING INFORMATION IS REQUIRED FOR THE POTABLE WATER
 SYSTEM:
 A} (NO/OK) REFERENCE NEW COMMENTS BELOW.
 B} (OK)
 C} (OK)
  
 **NEW COMMENT**
 5. SHEET 3.0P WATER RISER: PER FBC-2004 PLUMBING,
 SECTION 606.1(7) LOCATION OF FULL-OPEN VALVE REQUIRED
 ON SUPPLY PIPE TO EVERY WATER HEATER. PLEASE INDICATE
 VALVE ON THE RESUBMITTAL.
  
 6. SHEET 3.0P WATER RISER: PER FBC-2004 PLUMBING,
 SECTION 604.9 A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK CLOSING VALVES UTILIZED. PLEASE
 ADD THIS TO SHEET 3.0P WATER RISER AND CLEARLY INDICATE
 ALL WATER-HAMMER ARRESTORS. (NOTE; PRINT STATES "ADD
 WATER-HAMMER ARRESTOR @ EA. FIXTURE GROUP") THAT IS NOT
 WHAT THE CODE STATES, DOES EACH FIXTURE GROUP HAVE
 QUICK CLOSING VALVES? PLEASE CLARIFY ON THE
 RESUBMITTAL.
  
 7. SHEET 3.0P WATER RISER: PER FBC-2004 CHAPTER 1,
 CITY OF WEST PALM BEACH AMENDMENTS, SECTION 106.1
 INFORMATION ON CONSTRUCTION DOCUMENTS: CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND OF THE EXTENT OF THE WORK
 PROPOSED. PLEASE CLEARLY IDENTIFY ALL FIXTURES ON THE
 RESUBMITTED WATER RISER.
  
 8. PLEASE REFERENCE ELECTRICAL COMMENT #17.
  
 **********IMPORTANT INFORMATION
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-16 Cont ID  
Sent By mperson Date 2007-01-16 Time 15:25 Rev Time 0.00
Received By mperson Date 2007-01-16 Time 15:25 Sent To G
Notes
2007-01-16 16:37:08DENIED
 REFERENCE: FBC-2004 PLUMBING, FBC-2004 CHAPTER 1 CITY
 OF WEST PALM BEACH AMENDMENTS, FLORIDA STATE STATUTES,
 AND FLORIDA ADMINISTRATIVE CODE
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 3.0P OF 7 INDICATES (GREASE TRAP HAS BEEN
 WAIVED BY THE CITY OF WEST PALM BEACH WATER UTILITIES)
 NOTE: PER WASTE CODE #3434 FOR THIS WAIVER PLEASE
 CONTACT THE FOLLOWING.
 ENVIRONMENTAL COMPLIANCE MANAGER, LYNN MASSON PHONE=
 (561) 822-2271
 FAX= (561) 822-2279
 E-MAIL= [email protected]
  
 2. PLEASE NOTE ELECTRICAL COMMENT #3 ON THE TITLE BLOCK
 REFLECTING METRO DESIGN GROUP PER FS 471.023, 481.229,
 AND FAC 61G15-23.002. PLEASE CORRECT AND RESUBMIT.
  
 3. SHEET 3.0P OF 7 SANITARY RISER AND PLUMBING PLAN AND
 SHEET 1.1A OF 7 EQUIPMENT SCHEDULE:
 A} VENT REQUIRED FOR MOP SINK PER FBC-2004 PLUMBING
 SECTION 901.2.1.
 B} MOP SINK PLUMBING IS MISSING FROM PLUMBING PLAN,
 REQUIRED PER FBC-2004 CHAPTER 1 SECTION 106.1.1.C}
 GREASE SYSTEM MUST DRAIN DOWN STREAM OF WET VENTED
 BATHROOMS PER FBC-2004 PLUMBING, SECTION 909.1.
 D} SAMPLE POINT MUST BE LOCATED IN THE FLOW OF THE
 GREASE WASTE, NOT ON A CHANGE OF DIRECTION CLEANOUT AS
 INDICATED.
 E} THERE IS NO INDIRECT WASTE SIZE INDICATED FOR THE 3"
 FS FOR ITEM #19 DELI CASE REFRIGERATED ON SHEET 1.1A OF
 7 EQUIPMENT SCHEDULE OR ON THE SANITARY RISER ON SHEET
 3.0P OF 7. IF THERE IS NO INDIRECT DRAIN A TRAP SEAL
 PRIMER VALVE REQUIRED PER FBC-2004 PLUMBING, SECTION
 1002.4. PLEASE CLARIFY AND CORRECT THIS ON THE
 RESUBMITTAL.
 F} SHEET 1.1A OF 7 EQUIPMENT SCHEDULE: ITEM #5 DRAIN
 SHOULD BE INDICATED IN THE INDIRECT DRAIN SIZE COL. NOT
 THE DIRECT DRAIN SIZE COL. AS INDICATED. PLEASE CORRECT
 AND RESUBMIT.
  
 4. PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3 THE
 FOLLOWING INFORMATION IS REQUIRED FOR THE POTABLE WATER
 SYSTEM:
 A} WATER RISER DIAGRAM WITH SIZES,SHUT OFF VALVE, AND
 WATER HAMMER ARRESTOR LOCATION (IF REQUIRED)
 B} LOCATION OF THE WATER SUPPLY LINE.
 C} LOCATION OF THE BACKFLOW PREVENTOR.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721