| Plan Review Stops For Permit 06120620 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-04-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-04-03 |
Time |
14:33 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-04-03 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-03-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-03-06 |
Time |
11:52 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2007-03-06 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2007-03-06 11:53:56 | BUILDING PLAN REVIEW | | | PERMIT: 06120620 | | | ADD: 2505 W METROCENTRE BLVD | | | CONT: MILESTONECUSTOM HOMES | | | TEL: (561)436-3679 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | | | | | | | BUILDING PROVISO: | | | | | | BREAK ROOM SINK, NO ELEVATION DETAILS: SINKS: | | | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | | BE MOUNTED WITH THE COUNTER NO HIGHER | | | THAN 34" ABOVE THE FINISH FLOOR. | | | 11-4.24.3 KNEE CLEARANCE THAT IS AT | | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | | SHALL BE PROVIDED UNDERNEATH SINKS. | | | 11-4.24.5 CLEAR FLOOR SPACE. | | | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES | | | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 | | | SHALL | | | BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD | | | APPROACH. | | | THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE | | | ROUTE AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) | | | UNDERNEATH THE SINK. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-01-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-01-11 |
Time |
11:29 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-01-11 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2007-01-11 11:39:09 | BUILDING PLAN REVIEW | | | PERMIT: 06120620 | | | ADD: 2505 W METROCENTRE BLVD | | | CONT: MILESTONECUSTOM HOMES | | | TEL: (561)436-3679 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) BREAK ROOM SINK, NO ELEVATION DETAILS: SINKS: | | | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | | BE MOUNTED WITH THE COUNTER NO HIGHER | | | THAN 34" ABOVE THE FINISH FLOOR. | | | 11-4.24.3 KNEE CLEARANCE THAT IS AT | | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | | SHALL BE PROVIDED UNDERNEATH SINKS. | | | 11-4.24.5 CLEAR FLOOR SPACE. | | | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES | | | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 | | | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD | | | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN | | | ACCESSIBLE | | | ROUTE AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) | | | | | | UNDERNEATH THE SINK. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-09-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-09-27 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-09-27 |
Time |
14:35 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-04-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-04-09 |
Time |
13:24 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-04-09 |
Time |
12:26 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-03-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-03-06 |
Time |
10:51 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-03-06 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2007-03-06 10:50:37 | | | | DENIED/INCOMPLETE INFORMATION | | | | | | THE INPUT DATA REPORT INDICATES 1 LUMINAIRE @ 1910 | | | WATTS. PLEASE INDICATE COMPLIANCE WITH ALL FIXTURES TO | | | BE USED. ALSO SUBMIT A LEGEND OF FIXTURE TYPES AND | | | WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN THE | | | CALCULATIONS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-01-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-01-16 |
Time |
16:44 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-01-16 |
Time |
06:41 |
Sent To |
|
|
| Notes |
| 2007-01-16 16:44:08 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | PER 13-103.2 FBC INDICATE THE DEVICES ON THE PLAN TO | | | COMPLY WITH 13-415.FBC | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-04-06 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-04-06 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-04-06 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2007-04-06 13:02:59 | NEW SHEETS, C-1 & E-1 STAMPED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-03-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-06 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-06 |
Time |
12:11 |
Sent To |
|
|
| Notes |
| 2007-03-06 12:27:52 | *****APPROVED***** | | | | | | | | | PLAN SHEETS A-2 AND E-1 WERE STAMPED, INITIALED, AND | | | DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-01-17 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-01-17 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-01-17 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2007-01-17 10:54:59 | ***DENIED*** | | | | | | 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | | SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION. PLEASE | | | ADD TO CODE ANALYSIS. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE | | | SPRINKLER REMODEL IN ADDITION TO FIRE ALARM. | | | | | | 3) NEW DUCT SMOKE DETECTORS SHALL BE WIRED TO FIRE | | | ALARM AND CAUSE A GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 4) PLEASE SHOW LOCATIONS OF 2A-10B,C RATED FIRE | | | EXTINGUISHERS THAT SHALL NOT EXCEED 75' TRAVEL DISTANCE | | | TO REACH. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | (561) 805-6722 OR 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-06 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-06 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2007-09-06 09:06:36 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-07-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-11 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-11 |
Time |
14:13 |
Sent To |
M |
|
| Notes |
| 2007-07-11 14:13:58 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-03-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-22 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-22 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2007-03-22 09:55:40 | TO "BOB"#10 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-02-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-27 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-27 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2007-02-27 11:46:34 | TO "BOB"#8 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-02-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-01-17 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-26 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2007-01-09 13:36:13 | TO "BOB"#3 | | 2006-12-26 08:20:31 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-09-28 |
Time |
10:23 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-09-28 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2007-09-28 10:25:27 | REVISION TO MECH. PLANS PAGE AC-1 &AC-2. | | | *** PROVISO *** | | | 1)2004 F.B.C/M 307.2.3(1).AN AUXILIARY DRAIN PAN | | | WITH A SEPARATE DRAIN SHALL BE PROVIDED UNDER THE COILS | | | ON WHICH CONDENSATION WILL OCCUR. THE AUXILIARY PAN | | | DRAIN SHALL DISCHARGE TO A CONSPICUOUS POINT OF | | | DISPOSAL TO ALERT OCCUPANTS IN THE EVENT OF A STOPPAGE | | | OF THE PRIMARY DRAIN. THE PAN SHALL HAVE A MINIMUM | | | DEPTH OF 1.5 INCHES, SHALL NOT BE LESS THAN 3 INCHES | | | LARGER THAN THE UNIT OR THE COIL DIMENSIONS IN WIDTH | | | AND LENGTH AND SHALL BE CONSTRUCTED OF | | | CORROSION-RESISTANT MATERIAL. METALLIC PANS SHALL HAVE | | | A MINIMUM THICKNESS OF NOT LESS THAN 0.0276-INCH | | | GALVANIZED SHEET METAL. NONMETALLIC PANS SHALL HAVE A | | | MINIMUM THICKNESS OF NOT LESS THAN 0.0625 INCH. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-07-13 |
Time |
08:31 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-07-13 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2007-07-13 08:32:11 | REVISION TO MECH. PLANS PAGE AC-1. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-03-01 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-03-01 |
Time |
12:21 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-03-01 |
Time |
12:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-01-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-01-11 |
Time |
14:08 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-01-11 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2007-01-11 14:18:17 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) RETURN AIR TRANSFER DUCT FROM LISA'S OFFICE #107 IS | | | GOING TO THE SUPPLY AIR TRUNK LINE IN CORRIDOR #104, | | | PLEASE CORRECT. | | | | | | 3) 14" RETURN AIR TRANSFER DUCT FROM CONFERENCE ROOM | | | #103 TO CORRIDOR #102, AND LISA'S OFFICE #107 TO | | | CORRIDOR #104 NEED TO BE 18". | | | BALANCED RETURN AIR MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. SEE 2004 FBC/M 601.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-03-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-03-03 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-03-03 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2007-03-03 13:26:41 | PROVISO; | | | NO CABINET DOORS AT BREAK SINK. FLOOR SPACE UNDER SINK | | | TO BE 30" WIDE X 27" HIGH X 19" DEEP. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-01-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-01-17 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-01-17 |
Time |
07:23 |
Sent To |
|
|
| Notes |
| 2007-01-17 07:52:35 | DENIED; | | | 1.BREAK SINK TO BE HANDICAP ACCESSIBILE MUST COMPLY | | | WITH FBC-2004 BUILDING CHAPTER 11. SEE SECTIONS | | | 11-4.24.2 THRU 7. SHOW DETAIL ON PLANS SHOWING ALL | | | MEASUREMENTS REQUIRED. SHOW CLEAR FLOOR SPACE ON FLOOR | | | PLAN AT BREAK SINK (FRONTAL APPROACH REQUIRED). | | | 2.WATER ISOMETRIC, A WATER HAMMER ARRESTOR IS REQUIRED | | | FOR ICE MACHINE. SPEC. OUT MANUFACTURE AND SIZE LIST ON | | | PLANS, AND SHOW ON ISOMETRIC. TO BE INSTALLED AS CLOSE | | | TO SOURCE AS PASSIBLE. FBC-2004 PLUMBING SECTION | | | 604.9. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|