Plan Review Details - Permit 06120620
Plan Review Stops For Permit 06120620
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-04-03 Cont ID  
Sent By jwitmer Date 2007-04-03 Time 14:33 Rev Time 0.77
Received By jwitmer Date 2007-04-03 Time 14:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-03-06 Cont ID  
Sent By jwitmer Date 2007-03-06 Time 11:52 Rev Time 0.55
Received By jwitmer Date 2007-03-06 Time 11:48 Sent To  
Notes
2007-03-06 11:53:56BUILDING PLAN REVIEW
 PERMIT: 06120620
 ADD: 2505 W METROCENTRE BLVD
 CONT: MILESTONECUSTOM HOMES
 TEL: (561)436-3679
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
  
  
 BUILDING PROVISO:
  
 BREAK ROOM SINK, NO ELEVATION DETAILS: SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL
 BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE
 ROUTE AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM)
 UNDERNEATH THE SINK.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-11 Cont ID  
Sent By jwitmer Date 2007-01-11 Time 11:29 Rev Time 1.33
Received By jwitmer Date 2007-01-11 Time 11:29 Sent To  
Notes
2007-01-11 11:39:09BUILDING PLAN REVIEW
 PERMIT: 06120620
 ADD: 2505 W METROCENTRE BLVD
 CONT: MILESTONECUSTOM HOMES
 TEL: (561)436-3679
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) BREAK ROOM SINK, NO ELEVATION DETAILS: SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE
 ROUTE AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM)
  
 UNDERNEATH THE SINK.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-27 Cont ID  
Sent By btrobaug Date 2007-09-27 Time 16:26 Rev Time 0.00
Received By btrobaug Date 2007-09-27 Time 14:35 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-04-09 Cont ID  
Sent By btrobaug Date 2007-04-09 Time 13:24 Rev Time 1.00
Received By btrobaug Date 2007-04-09 Time 12:26 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-06 Cont ID  
Sent By btrobaug Date 2007-03-06 Time 10:51 Rev Time 1.00
Received By btrobaug Date 2007-03-06 Time 09:14 Sent To  
Notes
2007-03-06 10:50:37 
 DENIED/INCOMPLETE INFORMATION
  
 THE INPUT DATA REPORT INDICATES 1 LUMINAIRE @ 1910
 WATTS. PLEASE INDICATE COMPLIANCE WITH ALL FIXTURES TO
 BE USED. ALSO SUBMIT A LEGEND OF FIXTURE TYPES AND
 WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-16 Cont ID  
Sent By btrobaug Date 2007-01-16 Time 16:44 Rev Time 1.00
Received By btrobaug Date 2007-01-16 Time 06:41 Sent To  
Notes
2007-01-16 16:44:08 
  
 DENIED/INCOMPLETE INFORMATION
  
 PER 13-103.2 FBC INDICATE THE DEVICES ON THE PLAN TO
 COMPLY WITH 13-415.FBC
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-06 Cont ID  
Sent By mwennerg Date 2007-04-06 Time 13:02 Rev Time 0.00
Received By mwennerg Date 2007-04-06 Time 13:02 Sent To  
Notes
2007-04-06 13:02:59NEW SHEETS, C-1 & E-1 STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-03-06 Cont ID  
Sent By mawillia Date 2007-03-06 Time 12:27 Rev Time 0.00
Received By mawillia Date 2007-03-06 Time 12:11 Sent To  
Notes
2007-03-06 12:27:52*****APPROVED*****
  
  
 PLAN SHEETS A-2 AND E-1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-17 Cont ID  
Sent By mwennerg Date 2007-01-17 Time 10:49 Rev Time 0.00
Received By mwennerg Date 2007-01-17 Time 10:49 Sent To  
Notes
2007-01-17 10:54:59***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION. PLEASE
 ADD TO CODE ANALYSIS.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL IN ADDITION TO FIRE ALARM.
  
 3) NEW DUCT SMOKE DETECTORS SHALL BE WIRED TO FIRE
 ALARM AND CAUSE A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 4) PLEASE SHOW LOCATIONS OF 2A-10B,C RATED FIRE
 EXTINGUISHERS THAT SHALL NOT EXCEED 75' TRAVEL DISTANCE
 TO REACH.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 09:06 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 09:06 Sent To  
Notes
2007-09-06 09:06:36WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-11 Cont ID  
Sent By adarroug Date 2007-07-11 Time 14:13 Rev Time 0.00
Received By adarroug Date 2007-07-11 Time 14:13 Sent To M
Notes
2007-07-11 14:13:58TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 09:55 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 09:55 Sent To  
Notes
2007-03-22 09:55:40TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 11:43 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 11:43 Sent To  
Notes
2007-02-27 11:46:34TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-27 Cont ID  
Sent By mwennerg Date 2007-01-17 Time 10:55 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 08:11 Sent To  
Notes
2007-01-09 13:36:13TO "BOB"#3
2006-12-26 08:20:31WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-09-28 Cont ID  
Sent By tgordon Date 2007-09-28 Time 10:23 Rev Time 0.30
Received By tgordon Date 2007-09-28 Time 10:23 Sent To  
Notes
2007-09-28 10:25:27REVISION TO MECH. PLANS PAGE AC-1 &AC-2.
 *** PROVISO ***
 1)2004 F.B.C/M 307.2.3(1).AN AUXILIARY DRAIN PAN
 WITH A SEPARATE DRAIN SHALL BE PROVIDED UNDER THE COILS
 ON WHICH CONDENSATION WILL OCCUR. THE AUXILIARY PAN
 DRAIN SHALL DISCHARGE TO A CONSPICUOUS POINT OF
 DISPOSAL TO ALERT OCCUPANTS IN THE EVENT OF A STOPPAGE
 OF THE PRIMARY DRAIN. THE PAN SHALL HAVE A MINIMUM
 DEPTH OF 1.5 INCHES, SHALL NOT BE LESS THAN 3 INCHES
 LARGER THAN THE UNIT OR THE COIL DIMENSIONS IN WIDTH
 AND LENGTH AND SHALL BE CONSTRUCTED OF
 CORROSION-RESISTANT MATERIAL. METALLIC PANS SHALL HAVE
 A MINIMUM THICKNESS OF NOT LESS THAN 0.0276-INCH
 GALVANIZED SHEET METAL. NONMETALLIC PANS SHALL HAVE A
 MINIMUM THICKNESS OF NOT LESS THAN 0.0625 INCH.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-13 Cont ID  
Sent By tgordon Date 2007-07-13 Time 08:31 Rev Time 0.20
Received By tgordon Date 2007-07-13 Time 08:31 Sent To  
Notes
2007-07-13 08:32:11REVISION TO MECH. PLANS PAGE AC-1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-03-01 Cont ID  
Sent By tgordon Date 2007-03-01 Time 12:21 Rev Time 0.25
Received By tgordon Date 2007-03-01 Time 12:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-11 Cont ID  
Sent By tgordon Date 2007-01-11 Time 14:08 Rev Time 0.30
Received By tgordon Date 2007-01-11 Time 14:08 Sent To  
Notes
2007-01-11 14:18:17*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) RETURN AIR TRANSFER DUCT FROM LISA'S OFFICE #107 IS
 GOING TO THE SUPPLY AIR TRUNK LINE IN CORRIDOR #104,
 PLEASE CORRECT.
  
 3) 14" RETURN AIR TRANSFER DUCT FROM CONFERENCE ROOM
 #103 TO CORRIDOR #102, AND LISA'S OFFICE #107 TO
 CORRIDOR #104 NEED TO BE 18".
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE. SEE 2004 FBC/M 601.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-03-03 Cont ID  
Sent By jleech Date 2007-03-03 Time 13:23 Rev Time 0.00
Received By jleech Date 2007-03-03 Time 13:23 Sent To  
Notes
2007-03-03 13:26:41PROVISO;
 NO CABINET DOORS AT BREAK SINK. FLOOR SPACE UNDER SINK
 TO BE 30" WIDE X 27" HIGH X 19" DEEP.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-17 Cont ID  
Sent By jleech Date 2007-01-17 Time 07:23 Rev Time 0.00
Received By jleech Date 2007-01-17 Time 07:23 Sent To  
Notes
2007-01-17 07:52:35DENIED;
 1.BREAK SINK TO BE HANDICAP ACCESSIBILE MUST COMPLY
 WITH FBC-2004 BUILDING CHAPTER 11. SEE SECTIONS
 11-4.24.2 THRU 7. SHOW DETAIL ON PLANS SHOWING ALL
 MEASUREMENTS REQUIRED. SHOW CLEAR FLOOR SPACE ON FLOOR
 PLAN AT BREAK SINK (FRONTAL APPROACH REQUIRED).
 2.WATER ISOMETRIC, A WATER HAMMER ARRESTOR IS REQUIRED
 FOR ICE MACHINE. SPEC. OUT MANUFACTURE AND SIZE LIST ON
 PLANS, AND SHOW ON ISOMETRIC. TO BE INSTALLED AS CLOSE
 TO SOURCE AS PASSIBLE. FBC-2004 PLUMBING SECTION
 604.9.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695