Plan Review Details - Permit 06120586
Plan Review Stops For Permit 06120586
Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-11-15 Cont ID  
Sent By lursu Date 2007-11-15 Time 09:58 Rev Time 0.00
Received By lursu Date 2007-11-07 Time 14:17 Sent To  
Notes
2007-11-15 10:11:14 
 SINCE THIS PARCEL IS VACANT AS OF TODAY AND NO SITE
 ADDRESS HAS BEEN ISSUED BEFORE PLEASE USE ON THE
 REVISED SET OF PLANS A NEW SITE ADDRESS AS :
 1810 EMBASSY DR , WEST PALM BEACH , FL 33401.ALSO THIS
 SITE ADDRESS WILL BE USED ALONG WITH THE PARCEL CONTROL
 NUMBER = 74434317040120042, AS THE COMMON AREA SITE
 ADDRESS USED FOR PERMITTING AND ANY OTHER PROCESSES
 PRIOR OF ISSUING THE CO .EACH INDIVIDUAL UNIT WILL
 RECEIVE A UNIQUE SITE ADDRESS AT THE TIME OF THE
 PROJECT COMPLETION .
 IF BUILDING PERMITS WILL BE NEEDED FOR EACH INDIVIDUAL
 UNIT THEN THE SITE ADDRESS FOR EACH UNIT WILL BE USED.
  
 THE RECOMMENDED SITE ADDRESSES FOR THE UNITS STARTING
 EAST GOING WEST ARE:
 1804 ,1806,1808,1812,1814,1816,1818 & 1820EMBASSY DR
 , WEST PALM BEACH, FL 33401.AN OFFICIAL SITE ADDRESS
 NOTIFICATION LETTER WILL BE SENT TO THE PROPERTY
 OWNER.
  
 QUESTIONS/COMMENTS PLEASE CALL :
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
2007-11-07 14:17:27COPY OF APPL. SENT TO LILI

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-12-26 Cont ID  
Sent By lursu Date 2006-12-26 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2007-01-23 Time 07:13 Sent To  
Notes
2006-12-26 11:18:57FOR THESE 8NEW BUILDINGS NEW UNIQUE SITE ADDRESS MUST
 BE ASSIGNED TO EACH OF THEM.
 PLEASE PROVIDE THE APPROVED SITE PLAN AND THE SURVEY
 FOR THIS LOCATION.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]
2006-12-20 16:44:08APPL. SHOWS 1800 EMBASSY DR.--COPY OF APPL SENT TO LILI

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-07-09 Cont ID  
Sent By jwitmer Date 2008-07-09 Time 13:11 Rev Time 2.22
Received By jwitmer Date 2008-07-09 Time 13:11 Sent To  
Notes
2008-07-09 14:28:46BUILDING PLAN REVIEW
 PERMIT: 06120586
 ADD: 1800 EMBASSYDR
 CONT: E. W. REED, INC.
 TEL: (305)218-0900
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 JULY- 09/08
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SEMI- COMPLIED, THIS REVIEW ONLY ONE SOILS REPORT
 WAS SUBMITTED, TWO ORIGINAL REPORTS WITH ORIGINAL
 SIGNATURES AND RAISED SEALS ARE REQUIRED.FBC 1802.2.1
 QUESTIONABLE SOILS, 1802.2.1 QUESTIONABLE SOIL. WHERE
 THE SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR
 WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED
 IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL
 REQUIRE THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 4 ) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERMORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF DUST, NOISE, WATER
 OR DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE POSITIVE PATTERNS OF THE
 AFFECTED SITES. ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL DEVELOPMENT,
 INCLUDING ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS,
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALLY PREPARED DRAINAGE
 PLAN CLEARLY INDICATING COMPLIANCE WITH THIS PARAGRAPH.
 UPON COMPLETION OF THE IMPROVEMENT, A CERTIFICATE FROM
 A LICENSED ENGINEER SHALL BE SUBMITTED TO THE INSPECTOR
 IN ORDER TO RECEIVE APPROVAL OF THE FINAL INSPECTION.
  
 5 )BUILDING PROVISO: 109.3.10.1 HURICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A
 MANNER AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO
 PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00. IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT
 TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 6-15) COMPLIED.
  
  
 16)THIRD REQUEST, PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH SUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 HAVE FLORIDA APPROVAL:
 PGT SLIDINGGLASS DOORS NOA 07-0607.02
 PGT MULLIONS NOA 06-01125.06
 PGT SH-700NOA 07-0322.06
 PGT HORIZONTAL ROLLERNOA 07-0815.09
 PGT PW-701 FIXED NOA 07-0418.06
 CLOPAY SECTIONAL DOORS NOA 05-0316.01
 POLYFOAM NOA 06-0201.02EAGLE ROOFING PRODUCTS
 GAF MATERIALS BUILT UP ROOF
  
 17)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
  
 C) EXTERIOR WALL LOUVERS
 D) TRUSS ANCHORS
 E) BUILT UP ROOF SYSTEMS PRPODUCT APPROVAL SUBMITTED
 IS FOR INSULATED TYPE DECK SYSTEMS!
 THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 X___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 X___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 X___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 X___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 18-21) COMPLIED
  
 22-25) COMPLIED.
  
 26)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 27)THE NEW ENERGY CALCS ARE NOT DESIGNED FOR THIS
 STRUCTURE,
 A)THEY ARE INDICATED TO BE FOR A 2 UNIT STURCTURE
 WITH ONLY 6 BEDROOMS.
 B) CONDITIONED SPACE INDICATES FLOOR AREA 4238 THE
 FIRST FLOOR ITSELF HAS 12,472 SQ FT.
 C) RAISED WOOD FLOOR ENERGY CALCS INDICATE A R=19 WHERE
 AS SHEET A10 DETAIL 4/4 THE CEILING INDICATES R=11
 D) FRAMED WALLS STEEL PLAANS DO NOT INDICATE ANY R
 VALUE
 CALCULATIONS FOR DOORS AND WINDOWS DO NOT INDICATE THE
 AMOUNT OF GLAZED UNITS IN WINDOWS AND GLAZED DOORS
 E) THE DOOR COUNT FOR ADJACEENT SPACES AS WELL AS
 EXTERIOR DOORS ALSO DOES NOT INDICATE THE CORECT AMOUNT
 OF OPENINGS FOR THE 8 UNIT STRUCTURE.
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-30 Cont ID  
Sent By jwitmer Date 2007-11-30 Time 16:37 Rev Time 4.44
Received By jwitmer Date 2007-11-30 Time 16:37 Sent To  
Notes
2007-11-30 16:43:57BUILDING PLAN REVIEW
 PERMIT: 06120586
 ADD: 1800 EMBASSYDR
 CONT: E. W. REED, INC.
 TEL: (305)218-0900
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 NOV. 30,2007
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)FBC 1802.2.1 QUESTIONABLE SOILS, 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6
 .
  
 4 ) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERMORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF DUST, NOISE, WATER
 OR DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE POSITIVE PATTERNS OF THE
 AFFECTED SITES. ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL DEVELOPMENT,
 INCLUDING ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS,
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALLY PREPARED DRAINAGE
 PLAN CLEARLY INDICATING COMPLIANCE WITH THIS PARAGRAPH.
 UPON COMPLETION OF THE IMPROVEMENT, A CERTIFICATE FROM
 A LICENSED ENGINEER SHALL BE SUBMITTED TO THE INSPECTOR
 IN ORDER TO RECEIVE APPROVAL OF THE FINAL INSPECTION.
  
 5 )BUILDING PROVISO: 109.3.10.1 HURICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A
 MANNER AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO
 PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00. IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT
 TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 6) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7-15) COMPLIED.
  
  
 16) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF THE
 PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 17)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS:
 CASEMENT
 HORIZONTAL ROLLERS
 MULLIONS
 B) DOORS:
 EXTERIOR HOLLOW CORE METAL DOORS
 SLIDING GLASS DOORS
 SECTIONAL GARAGE DOORS
 C) EXTERIOR WALL LOUVERS
 D) TRUSS ANCHORS
 E) ROOFING ASSEMBLIES
 BUILT UP OR MODIFIED
 ROOF TILE UNDERLAYMENTS
 ROOF TILE
 ROOF TILE ADHESIVES
 THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 X___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 X___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 X___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 X___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 X___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 18-21) COMPLIED
  
 22) 1714.5.5.1 MULLIONS.
 MULLIONS, OTHER THAN MULLIONS WHICH ARE AN INTEGRAL
 PART OF A WINDOW OR GLASS DOOR ASSEMBLY TESTED AND
 LABELED IN ACCORDANCE WITH SECTION 1714.5.2.1 , SHALL
 BE TESTED BY AN APPROVED TESTING LABORATORY OR BE
 ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING
 PRACTICE. BOTH METHODS SHALL USE PERFORMANCE CRITERIA
 CITED IN SECTIONS 1714.5.5.2 , 1714.5.5.3 AND
 1714.5.5.4 .
  
 1714.5.5.2 LOAD TRANSFER.
 MULLIONS SHALL BE DESIGNED TO TRANSFER THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR
 ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE.
  
 23-25) COMPLIED.
  
 26)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 27) NEW COMMENT SEE ENERGY CALCULATIONS ON FORM
 600A-2001 PLEASE CORRECT TO THE 2004 VERSION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-23 Cont ID  
Sent By jwitmer Date 2007-01-23 Time 07:14 Rev Time 5.55
Received By jwitmer Date 2007-01-23 Time 07:14 Sent To  
Notes
2007-01-23 08:05:51BUILDING PLAN REVIEW
 PERMIT: 06120586
 ADD: 1800 EMBASSYDR
 CONT: E. W. REED, INC.
 TEL: (305)218-0900
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE
 NOTICE OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. )
 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 SHEET A-1 INDICATES III MISSING "A OR B"
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G ) NUMBER OF UNITS
 H ) NUMBER OF FLOORS
 1 ) NUMBER OF BEDROOMS
 J ) NUMBER OF ROOMS
 K ) NUMBER OF BEDROOMS
 L ) SQ. FT. LIV SPACE/ FL
 M ) SQ. FT. FOOTPRINT
 N ) SQ. FT. UNDER ROOF (TOTAL)
 O ) OCCUPANT LOAD
  
 3)FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED,
 THE BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE.
 SUCH INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS
 1802.4 THROUGH 1802.6 .
  
 4 ) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 5 ) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 6) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7)SHEET A-3 INDICATES TOWNHOUSE STYLE CONSTRUCTION.
 NOTE THESE UNITS ARE CLASSIFIED AS A R-2 EITHER CONDOS
 OR RENTAL UNITS AND WILL REVIEWED AS SUCH.
  
 8) SHEETS A-4- A-5 PLANS INDICATE WINDOWS OVER TUB
 AREAS IN BOTH CASES NO NOTES ON THE WINDOW SCHEDULE
 INDICATING A HAZARDOUS LOCATION.
 2406.3(5)5.GLAZING IN DOORS AND ENCLOSURES FOR HOT
 TUBS, WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND
 SHOWERS. GLAZING IN ANY PORTION OF A BUILDING WALL
 ENCLOSING THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED
 EDGE OF THE GLAZING IS LESS THAN 60 INCHES (1524 MM)
 ABOVE A STANDING SURFACE.
  
 9) SHEET A-5 PLEASE PROVIDE A SECTION THROUGH POWDER
 ROOM 102.
 1208.2(2)
 2.IF ANY ROOM IN A BUILDING HAS A SLOPED CEILING ,
 THE PRESCRIBED CEILING HEIGHT FOR THE ROOM IS REQUIRED
 IN ONE-HALF THE AREA THEREOF. ANY PORTION OF THE ROOM
 MEASURING LESS THAN 5 FEET (1524 MM) FROM THE FINISHED
 FLOOR TO THE CEILING SHALL NOT BE INCLUDED IN ANY
 COMPUTATION OF THE MINIMUM AREA THEREOF.
  
 10)A-7 INDICATES THE USE OF THE 1& 2 FAMILY
 RESIDENTIAL CODE WITH CODE SECTIONS R312.1 & R312.2
 PLEASE CORRECT THESE UNITS ARE AS STATED R-2 NOT R-3.
  
 11) SHEET A-9 DETAIL"B" PLEASE MAKE NOTE OF THE ASTM
 C-1063 THE NAILING ON HORIZONTAL FRAMING MEMBERS TO BE
 AT 4" ON CENTER WITH A MINIMUM OF 1 3/4" NAILING INTO
 FRAMING MEMBER.
  
 12) SHEET A-9 DETAIL "A" PLEASE PROVIDE CALCULATIONS
 FOR VENTILATION AND MEETING THE REQUIREMENTS OF :
 1203.2 THE NET FREE VENTILATING AREA SHALL NOT BE LESS
 THAN 1 / 150 OF THE AREA OF THE SPACE VENTILATED, WITH
 50 PERCENT OF THE REQUIRED VENTILATING AREA PROVIDED BY
 VENTILATORS LOCATED IN THE UPPER PORTION OF THE SPACE
 TO BE VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR
 CORNICE VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE VENTS.
  
 13)SHEET A-10 DETAIL # 1 AGAIN MAKES REFRENCE TO THE
 RESIDENTIAL CODE PLEASE CORRECT, THIS IS A R-2
 OCCUPANCY NOT R-3.
  
 14)SHEET A-12 DETAIL# 1 PLEASE REMOVE REFENCE TO THE
 ONE AND TWO FAMILY RESIDENTIAL CODE ALSO A-13.
  
 15) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 16) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 17)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS:
 CASEMENT
 HORIZONTAL ROLLERS
 MULLIONS
 B) DOORS:
 EXTERIOR HOLLOW CORE METAL DOORS
 SLIDING GLASS DOORS
 SECTIONAL GARAGE DOORS
 C) EXTERIOR WALL LOUVERS
 D) TRUSS ANCHORS
 E) ROOFING ASSEMBLIES
 BUILT UP OR MODIFIED
 ROOF TILE UNDERLAYMENTS
 ROOF TILE
 ROOF TILE ADHESIVES
 THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 X___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 X___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 X___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 X___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 X___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 18) PLEASE PROVIDE INFORMATION AS TO TYPE OF MATERIAL
 TO BE USED ON RIDGE AND HIP
 BOARDS AND ATTACHMENT METHOD. CONCRETE TILE 1507.3:
 1507.3.7 ATTACHMENT.
 CLAY AND CONCRETE ROOF TILES SHALL BE FASTENED IN
 ACCORDANCE WITH SECTION 1609 OR IN ACCORDANCE WITH
 FRSA/RTI INSTALLATION MANUAL, 4TH EDITION.
  
 1507.3.8 APPLICATION.
 TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS OR RECOMMENDATIONS OF THE
 FRSA/RTI 07320, 4TH EDITION.
  
 19) 1503.3.6 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 20) S- SHEETS DO NOT PROVIDE BUCK DETAILS FOR WINDOWS,
 DOORS OR GARAGE SECTIONAL DOOR.
 1714.5.4.1 ANCHORING REQUIREMENTS.
 WINDOW AND DOOR ASSEMBLIES SHALL BE ANCHORED IN
 ACCORDANCE WITH THE PUBLISHED MANUFACTURER?S
 RECOMMENDATIONS TO ACHIEVE THE DESIGN PRESSURE
 SPECIFIED. SUBSTITUTE ANCHORING SYSTEMS USED FOR
 SUBSTRATES NOT SPECIFIED BY THE FENESTRATION
 MANUFACTURER SHALL PROVIDE EQUAL OR GREATER ANCHORING
 PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING
 PRACTICE.
  
 21) 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL
 SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1 1
 / 2 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
 WHERE THE WOOD BUCK THICKNESS IS 1 1 / 2 INCHES (38 MM)
 OR GREATER, THE BUCK SHALL BE SECURELY FASTENED TO
 TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBTRATE AND THE BUCK SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME. WINDOW
 AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN
 FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE
 FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE
 MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY
 TO THE SECURED WOOD BUCK
  
 22) 1714.5.5.1 MULLIONS.
 MULLIONS, OTHER THAN MULLIONS WHICH ARE AN INTEGRAL
 PART OF A WINDOW OR GLASS DOOR ASSEMBLY TESTED AND
 LABELED IN ACCORDANCE WITH SECTION 1714.5.2.1 , SHALL
 BE TESTED BY AN APPROVED TESTING LABORATORY OR BE
 ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING
 PRACTICE. BOTH METHODS SHALL USE PERFORMANCE CRITERIA
 CITED IN SECTIONS 1714.5.5.2 , 1714.5.5.3 AND
 1714.5.5.4 .
  
 1714.5.5.2 LOAD TRANSFER.
 MULLIONS SHALL BE DESIGNED TO TRANSFER THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR
 ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE.
  
 23) S-4 PLEASE UPDATE ACI-318 AND ACI- 530 TO THE
 REFRENCED STANDARDS IN CHAPTER 35.
  
 24)SHEET E-1 VS M-1 2ND FLOOR HAL 201 BE AWARE OF THE
 CLOSENESS OF SMOKE DETECTORS TO RETURN AIR VENTS.
  
 25) SHEET A-5 INDICATES AN OPTION BEDROOM# 4, WHERE AS
 BOTH THE MECHANICAL AND ELECTRICAL ARE MISSING THIS
 OPTION. PLEASE PROVIDE AND SMOKE DETECTORS.
  
 26)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-07-24 Cont ID  
Sent By dpalmer Date 2008-07-24 Time 09:19 Rev Time 0.00
Received By dpalmer Date 2008-07-24 Time 09:19 Sent To PC
Notes
2008-07-24 09:20:02** DENIED REVIEW **
  
 ** THERE ARE COMMENTS WHICH COME FROM PREVIOUS REVIEW
 COMMENTS HOWEVER THEY ARE NEW BASED ON INFORMATION NOW
 ON PLANS.
 THERE ARE ALSO SOME REPEAT COMMENTS
  
 1) NOTE: PLEASE SEE THE NEW SERVICE ENTRANCE CONDUCTORS
 WHICH ARE NOW BEING SHOWN ARE NOT COMPLETE. NO CONDUIT
 SIZE IS SHOWN. THE REVIEW FOR CODE COMPLIANCE FOR
 CONDUIT FILL CAN NOT BE DONE. (TABLE 9)
  
 2) NOTE: PLEASE ALSO SEE THE NEW SERVICE ENTRANCE
 CONDUCTORS DO NOT MEET THE MINIMUM SIZE REQUIRED PER
 240.4B FOR DEVICES OVER 800AMPS.
 PLEASE ADJUST. 310.16
  
 3) NOTE: PLEASE SUPPLY AIC RATING OF THE 1200AMP MAIN
 AS PREVIOUSLY REQUESTED.
 110.9.
 PLANS NOTE AIC RATING OF PANELS AND BREAKERS HOWEVER
 DOES NOT INDICATE MAIN RATING.
  
 4) NOTE: PLEASE SEE UNIT B ON E-3 WHICH IS SHOWING SD
 FOR SMOKE DETECTOR. THIS CAN BE REDLINED AND DOES NOT
 NEED TO REPRINT SHEETS AT THIS TIME.
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-29 Cont ID  
Sent By dpalmer Date 2007-11-29 Time 12:28 Rev Time 0.00
Received By dpalmer Date 2007-11-28 Time 16:43 Sent To  
Notes
2007-11-29 12:29:06** DENIED 2ND REVIEW **
  
 ** PLEASE KNOW AS STATED ON PREVIOUS REVIEW AS THERE
 WERE CHANGES WHICH WERE NEEDED AND ITEMS NOT SUBMITTED
 ON PREVIOUS PLANS THERE MAY BE NEW COMMENTS GENERATED
 ON THE 2ND REVIEW.
 ** PLEASE SEE THESE ARE COMMENTS BASED ON THE PLANS
 SUBMITTED AND SOME ITEMS FROM PREVIOUS REVIEW WHICH
 STILL NEED TO BE ADDRESSED ALONG WITH NEW COMMENTS.
  
  
 1) NOTE: PLEASE SEE AS MENTIONED ON PREVIOUS REVIEW
 NOTE # 27 THE ADDRESS WAS YET TO BE DETERMINED AND LOOK
 FOR COMMENTS FROM THE ADDRESSING REVIEWER.
 PLEASE SEE THE NEW ADDRESS OF 1810 EMBASSY DR WAS
 GENERATED. AS THESE ARE NOT FEE SIMPLE TOWNHOUSES AND
 PLANS HAVE HAD CHANGES INDICATING THIS, PLEASE ADJUST
 ADDRESS IN TITLE BLOCKS TO 1810.
  
 2) NOTE: PLEASE SEE AS PREVIOUSLY MENTIONED IN NOTE #2,
 PLEASE BE SURE ALL SMOKE ALARMS MEET NFPA-72 11.8.3
 WHICH REQUIRES ALL SMOKE DEVICES TO BE A MINIMUM OF 3FT
 FROM BATH DOORS AND 20FT FROM COOKING APPLIANCES. THERE
 ARE EXCEPTIONS FOR COOKING APPLIANCES IF DEVICE IS OF A
 PHOTO-ELECTRIC TYPE AND/OR RESETTING TYPE.
 PLEASE SEE UNIT A MASTER BEDROOM FOR EXAMPLE.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTES # 3, #4 AND #10.
 PLEASE SEE THERE ARE STILL SOME AREAS WHERE SOME GFI
 RECEPTACLES DO NOT MEET 210.52C1-5 AND 210.8A6.
 PLEASE SEE E-2 UNIT A, ISLAND FOR ONE EXAMPLE. (GFI)
 PLEASE SEE E-2 UNIT A,PENINSULAR AND SEPARATE SPACES
 AND COUNTER SPACE FOR EXAMPLE.
  
 4) NOTE: PLEASE SEE PREVIOUS NOTE #8 FOR LISTING OF ALL
 RELEVANT CODES WHICH WERE REQUIRED TO BE ADJUSTED AND
 PLACED ON PLANS.
 RESPONSE WAS THAT ALL CODES WERE ADDED TO A AND SHEET
 E-4, WHICH WAS OK AND CORRECT HOWEVER PLEASE SEE E-2
 AND E-3 AS THE 2002 NFPA-70 ( NEC) IS STILL REFERENCED
 IN NOTES.
 PLEASE ADJUST.
  
 5) NOTE: PLEASE KNOW AS MENTIONED IN PREVIOUS REVIEW
 NOTES #11,12 ETC THE SERVICE WAS CHANGED FROM PREVIOUS
 PLANS AND NEW COMMENTS ARE NOW BEING MADE.
 PLEASE SEE THE FOLLOWING COMMENTS FOR SERVICE RISER:
 NOTES 6-11
  
 6) NOTE: PLEASE SEE MISSING CONDUITS FROM FPL TO
 SERVICE. AS FPL DOES NOT INSTALL THESE CONDUITS, THESE
 FALL UNDER THE NEC AND SIZING REQUIREMENTS FOR
 SERVICE.
 ***IMPORTANT: PLEASE VERIFY WITH THE FPL SERVICE
 PLANNER THAT THE SERVICE ENTRANCE CONDUCTORS ARE
 ACTUALLY GOING TO BE PULLED IN AND INSTALLED BY FPL.
 ALMOST ALL PROJECTS WHERE AN ON-SITE TRANSFORMER IS
 BEING INSTALLED BY FPL THE CONDUITS AND CONDUCTORS
 INCLUDING SERVICE ENTRANCE CONDUCTORS FROM SERVICE TO
 TRANSFORMER ARE BEING REQUIRED TO BE INSTALLED BY THE
 ELECTRICAL CONTRACTOR AND WILL BE THE RESPONSIBILITY OF
 THE OWNER. PLEASE KNOW AS MENTIONED ABOVE, IF CONDUITS
 AND CONDUCTORS ARE INSTALLED BY ELECTRICAL CONTRACTOR,
 THESE WILL BOTH FALL UNDER THE NEC AND ARE NEEDED TO BE
 SHOWN ON PLANS/SERVICE RISER.
 PLEASE OBTAIN LETTER FROM THE SERVICE PLANNER IF THESE
 WILL BE INSTALLED BY FPL.
 FBC 106.3.5.1.2, 106.1.2
  
 7) NOTE: PLEASE SEE THE CONDUIT SIZE IS MISSING FOR
 FEEDERS TO UNITS AND ARE UNABLE TO REVIEW AT THIS TIME
 FOR CODE COMPLIANCE. PLEASE SEE CONDUIT FILL TABLE IN
 CHAPTER 9 (C).
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE SEE THE CONDUIT FOR HOUSE PANEL IS TOO
 SMALL FOR CONDUCTORS ARE SHOWN. NO CONSIDERATION HAS
 BEEN GIVEN FOR LENGTH AT THIS TIME.
 PLEASE ADJUST SIZE OF CONDUIT.
 FBC 106.3.5.1.2
  
 9) NOTE: PLEASE SEE THE SERVICE METER CENTER IS BEING
 SHOWN AS 1160AMPS WHICH IS NOT A STANDARD SIZE PER
 240.6. PLEASE PROVIDE THE STANDARD SIZE OF EQUIPMENT.
 FBC106.3.5.1.2
  
 10) PLEASE SEE THE METER CENTER DOES NOT INDICATE ANY
 MAIN AS REQUIRED PER 230.70, 230.71.
 FBC 106.3.5.1.2
  
 11) PLEASE SEE NO AIC RATING(S) FOR MAINS AND BREAKERS
 ARE INDICATED AS REQUIRED.110.9, FBC 106.1.2,
 106.3.5.1.2
  
 12) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE # 23
 REQUESTED COMPLETED LOAD CALCULATIONS WHICH WERE
 SUBMITTED HOWEVER PLEASE SEE 422.13 AS THE WATER
 HEATERS ARE NOW CONSIDERED A CONTINUOUS LOAD UNDER THE
 NEW CODE AND IS REQUIRED TO BE FIGURED AT 125%.
 PLEASE ADJUST CALCULATIONS.
 FBC 106.3.5.1.2
  
 13) NOTE: PLEASE SEE PREVIOUS NOTES #14 AND #28 AS
 ROOMS ARE AREAS NEEDED TO BE SHOWN ON PLANS,
 SPECIFICALLY DINING AREAS/ROOMS. PLEASE SEE AS
 PREVIOUSLY NOTED THE DINING AREAS AND/OR ROOMS SHALL BE
 ON ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS.
 PLEASE SEE E-3 UNIT B OPTION AS THE DINING RECEPTACLES
 ARE BEING SHOWN ON A GENERAL LIGHTING CIRCUIT WHICH IS
 NOT PERMITTED.
  
 14) NOTE: PLEASE SEE THE LOCATION OF THE ELECTRICAL
 SERVICE IS OF CONCERN. PLEASE SEE BASED ON THE SIZE OF
 SUCH EQUIPMENT AND BASED ON THE SCALE AND LOCATION AS
 SHOWN ON PLANS THERE SEEMS THERE WILL BE AN ISSUE FOR
 MINIMUM WORKING CLEARANCES AND PROTECTION OF EQUIPMENT.
 AS THE LOCATION HAS A DRIVEWAY/PARKING AREA IS RIGHT IN
 FRONT OF EQUIPMENT, NOT ONLY WILL THE EQUIPMENT REQUIRE
 MINIMUM CLEARANCES, BUT ALSO PROTECTION BY BOLLARDS TO
 PREVENT DAMAGE. PLEASE PROVIDE MINIMUM CLEARANCES,
 BOLLARD DETAIL, SITE DETAIL INCLUDED WITH THE ELEVATION
 DETAIL.
 PLEASE SEE BASED ON SCALE THE EQUIPMENT AS THIS IS VERY
 LARGE IN NATURE MAY PROTRUDE INTO DRIVE AREA.
 110.26
  
 15) NOTE: PLEASE PROVIDE INFORMATION AND ELECTRICAL
 PLANS FOR HOUSE PANEL AND EQUIPMENT.
 PLEASE SEE THAT NO PANEL SCHEDULE WAS SUBMITTED WITH
 OVER CURRENT PROTECTION, CIRCUITS, CONDUCTORS ETC.
 PLEASE SEE NO ELECTRICAL PLANS WERE SUBMITTED SHOWING
 LOCATION OF ELECTRICAL ON HOUSE PANEL.
 FBC 106.3.5.1.2
 NEC 2005 240.4, 310.16 ETC
  
 16) NOTE: PLEASE SEE 408.4, PLEASE PROVIDE MORE
 SPECIFIC DESIGNATIONS ON CIRCUITS AS SHOWN ON PANEL
 SCHEDULES.
 PLEASE SEE THE USE OF * GENERAL LIGHTING* SHOULD SHOW
 OR INDICATE THE ROOMS AND AREAS IN WHICH THESE CIRCUITS
 FEED. FOR EXAMPLE: BEDROOM #2 LIGHTING, LIVING ROOM
 LTS/RECEPTS ETC.
 THIS WAS A CHANGE IN THE 2005 CODE WHICH REQUIRES MORE
 SPECIFIC DETAILS.
 PLEASE ALSO SEE THE CIRCUITING AS SHOWN FOR UNIT *B*
 INDICATES CIRCUITING TO PANEL *A*.
 THESE DESIGNATIONS SEEM TO BE A MISPRINT AND SHOULD BE
 *B-3*, B27, B21 ETC.
 408.4.
 FBC 106.3.5.1.2, 106.5
  
 17) NOTE: PLEASE SHOW ON SITE ELECTRICAL PLANS THE
 LOCATIONS OF ALL CONDENSING UNITS, DISCONNECTS AND GFI
 RECEPTACLES.
 440.11, 110.26, 210.63, 210.8
 FBC 106.1.2
  
 18) NOTE: PLEASE SEE PREVIOUS NOTE #24 FOR 210.52.
 THERE IS STILL SOME RECEPTACLES MISSING AND NOT LOCATED
 AS REQUIRED PER 210.52.
 PLEASE SEE SOME OF THESE ARE REDLINED ON ONE OF THE SET
 OF PLANS.
 PLEASE SEE MISSING RECEPTACLES WITHIN 6FT OF DOORWAY
 OPENINGS.
 PLEASE ALSO KNOW THAT PERMANENT RAIL AREAS ARE
 CONSIDERED WALL SPACE.
  
 19) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** ONCE AGAIN AS THERE ARE SOME ITEMS NOT YET SUBMITTED
 FOR REVIEW THERE MAY BE NEW COMMENTS GENERATED ON THE
 NEXT REVIEW AS THESE ITEMS CAN NOT BE REVIEWED AT THIS
 TIME.
  
 *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-12 Cont ID  
Sent By dpalmer Date 2007-01-12 Time 18:52 Rev Time 0.00
Received By dpalmer Date 2007-01-12 Time 17:18 Sent To  
Notes
2007-01-12 18:52:49** UNSAT **
  
 ** PLEASE SEE THESE ARE COMMENTS BASED ON THE PLANS
 SUBMITTED. PLEASE SEE THAT THERE MAY BE COMMENTS ON THE
 NEXT REVIEW WHICH MAY BE NEW AS SOME INFORMATION AS
 SHOWN ON THESE PLANS WILL BE CHANGING SYSTEMS.
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC AS THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE PLANS ARE BEING SUBMITTED AND
 LABELED AS TOWNHOUSE UNITS, HOWEVER PLEASE SEE IF THESE
 ARE INDEED FEE SIMPLE "TOWNHOUSES" AS PER FBC
 DEFINITIONS, PLEASE SEE REQUIREMENTS OF THE FBC AND
 ELECTRICAL CODE WHICH WOULD CHANGE MANY ITEMS IN THE
 DESIGN AND PLEASE KNOW SEPARATE PERMIT APPLICATIONS,
 PLANS AND FEES WOULD BE REQUIRED ON EACH FEE SIMPLE
 TOWNHOUSE. PLEASE SEE AS ALL UNITS ARE CONNECTED BY A
 COMMON AREA AND ONE BUILDING THIS DOES NOT SEEM
 POSSIBLE.
 PLEASE KNOW THE PLANS AS SUBMITTED IS FOR ONE BUILDING
 AND PLEASE SEE COMMENTS FOR ELECTRICAL SERVICE(S) AS
 SUBMITTED.
  
 PLEASE SEE COMMENTS FROM OTHER TRADES
 FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION.
  
 2) NOTE: PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES ALL
 SMOKE DEVICES TO BE A MINIMUM OF 3FT FROM BATH DOORS
 AND 20FT FROM COOKING APPLIANCES. THERE ARE EXCEPTIONS
 FOR COOKING APPLIANCES IF DEVICE IS OF AN PHOTOELECTRIC
 TYPE AND/OR RESETTING TYPE.
  
 3) NOTE: PLEASE SEE SOME RECEPTACLES SPACED ALONG
 KITCHEN COUNTER SPACE. IT APPEARS SOME NEED TO BE
 RELOCATED TO MEET 210.52C1
  
 4) NOTE: PLEASE SEE ALL RECEPTACLES SERVING KITCHEN
 COUNTER SPACE SHALL BE SHOWN AS GFI/GFI PROTECTED.
 210.8A6.
  
 5) NOTE: PLEASE SEE NO RECEPTACLE BEING SHOWN FOR THE
 DISPOSAL FOR DISCONNECTING MEANS.
 422.31
  
 6) NOTE: PLEASE CLARIFY THE TYPE FIRE PROTECTION BEING
 INSTALLED FOR BUILDING. PLEASE SEENFPA-72 11-5.1.1,
 11.8.3. PLEASE SEE NFPA-72 DEFINITIONS AS PLANS CALL
 FOR SD FOR SMOKE DETECTORS THIS IS OK, HOWEVER PLEASE
 KNOW IF THESE ARE INDEED SMOKE DETECTORS AS DEFINED IN
 NFPA72, THESE WOULD BE DEVICES WHICH ONLY DETECT AND
 WOULD SIGNAL TO OTHER ALARM/HORN DEVICES. NO ALARM HORN
 DEVICES ARE SHOWN. PLEASE INDICATE IF PART OF A FUTURE
 LV FA SYSTEM.
 PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED
 DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY
 WOULD BE LABELED AS SA FOR SMOKE ALARMS.
 PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT
 THE SOUTHERN SECTION IAEI MEETING FROM NFPA THAT IF
 UNITS ARE INDEED DEVICES WHICH DETECT AND SOUND AN
 ALARM, PLANS SHOULD SHOW THEM AS SA'S AND THIS IS NOT
 NEW CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST
 TO SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06
 SHOULD BE CHANGING IF AND WHERE APPLICABLE. PLEASE SEE
 SECTIONS OF THE FBC AS STATED ON PLANS WHICH ACTUALLY
 CONTAIN THE WORDING OF SMOKE ALARMS IN THE FBC.
 IF PART OF A LV FIRE/SECURITY SYSTEM PLEASE INDICATE AS
 SUCH. PLEASE SHOW DEVICES THEN FOR SOUNDING. PLEASE
 ALSO SEE MISSING SMOKE DETECTION/ SMOKE ALARM DEVICE IN
 UNIT "C" FIRST FLOOR.
  
 7) NOTE: PLEASE SEE FBC 2004 13-103.1.1.1 WHICH
 REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED.
 PLEASE NOTE ON PLANS ACCORDINGLY AND INDICATE
 FIXTURES.
  
 8) NOTE: PLEASE BE SURE PLANS REFLECT THE CODES IN
 WHICH THE DESIGN IS UNDER AND PERMITTED UNDER. PLEASE
 LIST THE FOLLOWING AT A MINIMUM FOR ELECTRICAL SHEETS
 AND ARCHITECTURAL SHEETS.
 2005 NFPA-70 (NEC), 2002-NFPA-72 NATIONAL FIRE ALARM
 CODE
 ** PLEASE KNOW FOR INFORMATIONAL PURPOSE, AS OF
 DECEMBER 8TH, 2006 THE STATE OF FLORIDA ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70(
 NEC). AS THIS PROJECT WAS SUBMITTED FOR PERMIT BEFORE
 THIS DATE, THIS PROJECT IS UNDER THE PREVIOUS CODES AS
 STATED ABOVE. PLEASE SEE THAT THERE ARE STRUCTURAL
 DESIGN CHANGES ALSO DONE UNDER THE NEW 2006 REVISIONS
 TO THE FBC. PLEASE SEE BUILDING REVIEW NOTES FOR DESIGN
 PRESSURES ETC. (NOTED FOR INFORMATION ONLY)
  
 9) NOTE: PLEASE SEE THE HWH IS BEING SHOWN WITH
 RECEPTACLE FOR THE CONNECTION OF THIS UNIT WHICH IS NOT
 PERMITTED. PLAN NEEDS TO SHOW A DISCONNECT/J-BOX IF
 BREAKER IS GOING TO BE USED TO MEET THE CODE. PLEASE
 SEE EXCEPTIONS FOR WITHIN SITE.
 422.30, 4220.31
  
 10) NOTE: PLEASE SEE MISSING GFI RECEPTS FOR KITCHEN
 PENINSULAR PER 210.52C3, 210.8A6
  
 11) NOTE: PLEASE SEE THE FOLLOWING COMMENT, HOWEVER
 PLEASE STILL SEE RISER DOES NOT INDICATE ANY MAIN
 DISCONNECT FOR SERVICE. THE FOLLOWING COMMENT AND HOW
 PLANS WILL BE SUBMITTED WILL DICTATE WHAT TYPE OF
 SERVICE AND HOW MUCH WILL CHANGE; HOWEVER IN EITHER
 CASE MAINS ARE REQUIRED.
 230.70, 230.71, 240.4 ETC
  
 12) NOTE: PLEASE SEE AS THIS IS ONE BUILDING; PLEASE
 SEE 230.2 AS THE PROPOSED SERVICESFOR EACH UNIT ARE
 NOT GRANTED AS SHOWN ON PLANS. PLEASE REVISE SERVICE
 RISER DIAGRAM FOR GROUPING OF MAINS INTO ONE SERVICE.
 PLEASE KNOW IF THESE ARE SUBMITTED AS TRUE
 TOWNHOUSES/FEE SIMPLE, PROPERTY LINES, SEPARATE PERMIT
 APPLICATIONS ETC, AND THEN INDIVIDUAL SERVICES TO EACH
 UNIT MAY BE PERMITTED. THIS WILL CHANGE RISER AS SHOWN
 OR NOT?
 PLEASE REVISE RISER DIAGRAM.
  
 13) NOTE: PLEASE SEE RISER AS SHOWN NOW SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR FROM THE METER TO THE
 PANEL. WITHOUT SHOWING MAIN ON RISER IT IS NOT POSSIBLE
 TO CORRECTLY DETERMINE THE LOCATION OF THE EGC. PLEASE
 SEE 250.6, 250.24B AS THE EGC IS NOT PERMITTED BEFORE
 THE FIRST MEANS OF DISCONNECT.
  
 14) NOTE: PLEASE SHOW ALL ROOMS AND AREA DESIGNATIONS
 ON PLANS. PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SUBMITTED. PLEASE
 SEE THERE ARE SOME ITEMS WHICH CAN NOT BE REVIEWED FOR
 CODE COMPLIANCE AT THIS TIME DUE TO THIS INFORMATION
 NOT SHOWN.
 NEC 408.4, 310.16, 240.4 ETC.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTIONS.
  
 15) NOTE: PLEASE SEE 250.66 FOR SIZING OF THE GROUNDING
 ELECTRODE CONDUCTOR. DEPENDING ON THE SERVICE AND WHAT
 THE BUILDING FINALLY COMES DOWN TO AND THE SIZE OF THE
 SERVICE, THIS WILL DETERMINE THE SIZE OF THE GEC.
 PLEASE SEE THE 150A METER AS SHOWN INDICATES A 1/0?
  
 16) NOTE: PLEASE KNOW BASED ON SOME OF THE CIRCUITING
 AT THIS TIME NOT BEING SHOWN; PLEASE BE SURE TO SEE
 210.12 FOR AFCI PROTECTED CIRCUITS. THIS APPEARS TO BE
 ADDRESSED, BUT CAN NOT BE CONFIRMED AT THIS TIME.
  
 17) NOTE: PLEASE SEE MISSING THE REQUIRED GFI FOR SOME
 CONDENSING UNITS PER 210.63, 210.8A3 (UNIT "A").
  
 23) NOTE: PLEASE SEE SUBMIT COMPLETE LOAD CALCULATIONS
 FOR SERVICE. 220.84, 220.12, 220.42, 220.44 ETC. PLEASE
 KNOW DEPENDING ON THE NEW SERVICE AND LOAD,
 CONSIDERATION OF 230.2 WILL BE REVIEWED, HOWEVER PLEASE
 KNOW AT THIS TIME THE SINGLE METER/SERVICE FOR EACH IS
 OK, HOWEVER IF ONE MAIN AND A METER BANK IS INSTALLED
 FOR MULTI-FAMILY/CONDO SERVICE, THISH WILL REQUIRE
 CALCULATIONS FOR SUCH.
  
 24) NOTE:PLEASE SEE 210.52 FOR AREAS FOR REQUIRED
 RECEPTS WHICH ARE MISSING ON PLANS. PLEASE SEE UNIT
 "A/B" ETC.
 PLEASE SEE ONE SET OF PLANS ARE REDLINED FOR LOCATIONS
 WHICH ARE MISSING DEVICES WITHIN 6FT OF DOOR, 2FT OR
 MORE OF WALL SPACE AND HALLWAYS AS NOTED.
  
 25) NOTE: PLEASE COMPLETE RISER DIAGRAM WITH ALL
 FEEDERS TO UNITS AND CORRELATE WITH THE OVER CURRENT
 PROTECTION DEVICES OF THAT FOR EACH UNIT ONCE RISER IS
 FINALIZED.
 215.5, 310.16, 240.4 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 26) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING
 CONDUCTORS FROM MAINS TO EACH UNIT PER 250.122.
 250.24B, 250.110, ETC. (WHERE REQUIRED AND
 APPLICABLE).
  
 27) NOTE: PLEASE SEE THAT THE ADDRESS FOR THIS PROJECT
 SHALL BE PLACED ON THE TITLE BLOCKS. PLEASE KNOW AT
 THIS TIME, THIS IS A MULTI-FAMILY SINGLE BUILDING WITH
 THE ADDRESS OF 1800 EMBASSY DR. PLEASE SEE NOTE FROM
 ADDRESSING REVIEWER FOR ADDRESS?S ALSO DEPENDING ON HOW
 THESE ARE BEING PERMITTED AND SUBMITTED.
 THIS IS NOT AND HAS NOT BEEN SUBMITTED AS TOWNHOUSES,
 OR CONDO'S.
 FAC 61G15-23.002, FAC 61G1-16.004
  
 28) NOTE: PLEASE CLARIFY DINING ROOM/AREA ON PLANS SO
 THAT ONCE CIRCUITING IS SHOWN COMPLIANCE WITH 210.52B1,
 210.11C1 AND 220.52 CAN BE VERIFIED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2008-07-11 Cont ID  
Sent By rchokshi Date 2008-07-11 Time 13:42 Rev Time 0.00
Received By rchokshi Date 2008-07-11 Time 13:10 Sent To  
Notes
2008-07-11 13:32:34PLEASE PROVIDE FOLLOWING INFO:
  
 1. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 YOUR RESPOSEFOR REV 2 NOT ENOUGH,YOU NEED TO PROVE
 IN A DOCUMENTS/CALCULATIONS THATYOU HAVE CONSIDERED
 FLOOD ZONE OF THISAREA,&5, 10, 25, 100 YEARRAIN
 FLOOD CRITERIA, AND CROWN OF THE ROAD HAVE BEEN
 CONSIDERED. FIRST FLOOR ELEVATION SHOULD BE HIGHER THAN
 CROWN OF THE ROAD BY ATLEAST 1 FOOT. ORIGINAL PLANS
 WERE APROVED IN 1970'S PER YOUR LETTER BUT THAT IS,
 TOO LONG TIME TO CONTINUE IN EFFECT, NORMALLYITIS A
 5 YEAR PERMIT LIMIT. IF YOU DO NOT BUILD IN 5 YEARS YOU
 NEED TO RE APPLY UNLESS YOU HAVE A LETTER ALLOWING YOU
 TO BUILD ANY TIME.
  
 OUR RESPONSE FOR REV 3FOR YOUR LETTER OF 5/28/08 FROM
 DOUG WINTER COMP., INC.WE NEED A RESPONSE FROM MOCK
 ROOS FOR YOUR LETTER OF 5/13/08 TO MOCK ROOS.
  
 2. PLEASE PROVIDE A COPY OF SFWMD PERMIT, GEO TECH
 REPORT.,
 OUR RESPONSE FOR REV 2 :AGAIN,SFWMD PERMIT IS GOOD
 FOR FIVE YEARS.
  
 OUR RESPONSE FOR REV 3 FOR YOUR LETTER 5/28/08: SINCE
 MOCK ROOS IS REVIEWING STORM WATER CALS, LET MOCK ROOS
 DECIDE.
  
  
 3.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ? PLEASE SHOW ON DRAWINGPERVIOUS
 AREA, LIKE GREEN, LAKES, ETC,IMPERVIOUS AREA.
  
 OUR RESPONSEFOR REV 2:AGAIN YOU ARE SAYING IN YOUR
 LETTER THAT IT IS PART OF THE MASTER PLAN OF 1970'S.
 WELL,1970 IS WAY TOO BACK.PLEASE PROVIDE THE STORM
 WATER QUALITY CALCULATIONS. WE NEED EX-FILTRATION
 TRENCH CALCULATION ALSO.
  
 OUR RESPONSE FOR REV 3 FOR YOUR LETTER 5/28/08: WE NEED
 STORM WATER QUALITY CALS.MOCK-ROOS REVIEWS IT. YOU
 NEED TO SUBMIT STORM WATER QUALITY CALS TO 1000 45TH
 STREET ENGINEERING, SO THEY COULD GIVE IT TO MOCK ROOS
 FOR REVIEW.WE DO NOT ISSUE PERMIT UNTIL 1000 45TH
 ST. ENGINEERING APPROVES.
  
 4WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 OUR RESPONSEFOR REV 3: MANNY G. PUT ARED STAMP WITH
 HIS SIGNATURE WHEN HE APPROVES YOUR DRAWINGS. WE DID
 NOT SEE STAMPS ON YOUR DRAWINGS YET.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-12-04 Cont ID  
Sent By rchokshi Date 2007-12-04 Time 11:15 Rev Time 0.00
Received By rchokshi Date 2007-12-04 Time 10:40 Sent To  
Notes
2007-12-04 11:15:35PLEASE PROVIDE FOLLOWING INFO:
  
 1. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 YOUR RESPOSE NOT ENOUGH,YOU NEED TO PROVE IN A
 DOCUMENTS/CALCULATIONS THATYOU HAVE CONSIDERED FLOOD
 ZONE OF THISAREA,&5, 10, 25, 100 YEARRAIN FLOOD
 CRITERIA, AND CROWN OF THE ROAD HAVE BEEN CONSIDERED.
 FIRST FLOOR ELEVATION SHOULD BE HIGHER THAN CROWN OF
 THE ROAD BY ATLEAST 1 FOOT. ORIGINAL PLANS WERE APROVED
 IN 1970'S PER YOUR LETTER BUT THAT IS,TOO LONG TIME
 TO CONTINUE IN EFFECT, NORMALLYITIS A5 YEAR
 PERMIT LIMIT. IF YOU DO NOT BUILD IN 5 YEARS YOU NEED
 TO RE APPLY UNLESS YOU HAVE A LETTER ALLOWING YOU TO
 BUILD ANY TIME,WE DO NOT THINK SO.
  
 2. PLEASE PROVIDE A COPY OF SFWMD PERMIT, GEO TECH
 REPORT.,
 OUR RESPONSE:AGAIN,SFWMD PERMIT IS GOOD FOR FIVE
 YEARS.
  
 3.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ? PLEASE SHOW ON DRAWINGPERVIOUS
 AREA, LIKE GREEN, LAKES, ETC,IMPERVIOUS AREA.
 OUR RESPONSE:AGAIN YOU ARE SAYING IN YOUR LETTER THAT
 IT IS PART OF THE MASTER PLAN OF 1970'S.WELL,1970
 IS WAY TOO BACK.PLEASE PROVIDE THE STORM WATER
 QUALITY CALCULATIONS. WE NEED EX-FILTRATION TRENCH
 CALCULATION ALSO.
  
 4. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE BEST PIPE TO CONNECT WITH THE STORM
 WATERFROM ALL OTHER STORM WATER PIPES. PLEASE SHOW
 DETAIL OF THE CONTROL STRUCTURES WITH ELEVATIONS,
 NOTCHES, BLEEDING ELEVATION, ETC
  
 5. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 OUR RESPONSE: YOU NEED SILT FENCE ON SOUTH SIDE AND
 EAST SIDE ALSO. SILT FENCE SHOULD BE ALL AROUND THE
 PROPERTY LINE PER FDEP.
  
 6. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-01-25 Cont ID  
Sent By rchokshi Date 2007-01-25 Time 15:21 Rev Time 0.00
Received By rchokshi Date 2007-01-25 Time 15:13 Sent To  
Notes
2007-01-25 15:21:06PLEASE PROVIDE FOLLOWING INFO:
  
 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT, GEO TECH
 REPORT.,
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL.
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED 11.
 ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND YOUR
 SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-07-22 Cont ID  
Sent By mawillia Date 2008-07-22 Time 16:12 Rev Time 0.00
Received By mawillia Date 2008-07-22 Time 15:18 Sent To E
Notes
2008-07-22 15:28:28*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A-1 AND A-6 WERE STAMPED,
 INITIALED, AND DATED.PLAN SHEETS E-2 AND E-3 TO BE
 FIRE-STAMPED WHEN THE ELECTRICAL EXAMINER HAS BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-12-12 Cont ID  
Sent By mawillia Date 2007-12-12 Time 13:16 Rev Time 0.00
Received By mawillia Date 2007-12-12 Time 12:20 Sent To  
Notes
2007-12-12 12:31:12*****UNSAT*****
  
 THE FOLLOWING COMMENTS (OF 13) FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 01.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET. THE NUMBER 1810 (NOT 1800) SHOWS
 UP IN OUR SYSTEM AS THE NUMERICAL FOR THIS PROJECT
 SITE.LILI URSU MAY BE CONTACTED AT 561-822-1239 FOR
 ADDRESS MATTERS.
  
 05.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
 ACKNOWLEDGE THE COMMENT ON AN APPROPIATE PLAN SHEET;
 PLEASE BE ADVISED THAT NFPA 241 INCLUDES NEW
 CONSTRUCTION.
  
 06.THE CONSTRUCTION OPERATION AND /OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER EMERGENCY ACCESS RESPONSE TO THE SAID
 PROPERTY OR THE VICINITY THEREOF.ADD TO GENERAL
 NOTES, SHEET A-0
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-15 Cont ID  
Sent By mawillia Date 2007-02-15 Time 14:32 Rev Time 0.00
Received By mawillia Date 2007-02-15 Time 14:32 Sent To  
Notes
2007-02-15 15:01:02*****DENIED*****
  
  
 01.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 02.PLEASE SUBMIT THE FOLLOWING INFORMATION:
 *CONSTRUCTION TYPE* OCCUPANCY TYPE*BUILDING HEIGHT
 * BUILDING SQUARE FOOTAGE *INTERIOR FINISH
 CLASSIFICATIONS * ANY OTHER PERTINENT INFORMATION TO
 ASSIST IN THE PLAN REVIEW.
  
 03.WILL THE STRUCTURE HAVE A FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEM?IF SO, PROVIDE A LAYOUT OF THE FIRE
 PROTECTION SYSTEM(S) FOR REVIEW.
  
 04.NFPA 101 - 2003 EDITION AND THE FORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 05.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 06.THE CONSTRUCTION OPERATION AND /OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER EMERGENCY ACCESS RESPONSE TO THE SAID
 PROPERTY OR THE VICINITY THEREOF.
  
 07.THE SITE PLAN (SHEET A-1) DOES NOT SHOW ANY FIRE
 HYDRANTS.INDICATE THE LOCATION OF FIRE HYDRANT(S)
 WITHIN 300 FEET OF THE STRUCTURE.PLEASE BE ADVISED
 THAT AN ADDITIONAL HYDRANT MAY BE REQUIRED IF THIS
 DISTANCE IS GREATER THAN 500 FEET.
  
 08IT APPEARS THAT THIS STRUCTURE WILL BE SETBACK
 FROM EMBASSY DRIVE.IF THIS TRUE, AS PER WEST PALM
 BEACH CODE, A MONUMENT SIGN OR MARQUEE SHALL POST THE
 ADDRESS RANGE FOR THE DEVELOPMENT.THESE NUMBERS SHALL
 BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH.
  
 09.PLEASE INDICATE ON PLANS THAT ALL FIRE RATED DOORS
 (103,108,111) SHALL BE EQUIPPED WITH SELF CLOSING
 DEVICES AND SHALL POSTIVELY CLOSE UPON RELEASE.
  
 10.ON THE APPROPIATE EXTERIOR ELEVATION SHEET,
 DISPLAY THE ADDRESS FOR THE UNITS.
  
 11.PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) ARE
 TIED INTO A FIRE ALARM SYSTEM.SMOKE ALARMS (SA), ON
 THE OTHER HAND, RECEIVE THEIR OPERATING POWER FROM THE
 BUILDING ELECTRICAL SYSTEM.SEE ELECTRICAL SHEETS.
  
 12.SMOKE ALARMS ARE TO BE ARRANGED SO THAT THE
 OPERATION OF ANY SMOKE ALARMSHALL CAUSE THE ALARM IN
 ALL SMOKE ALARMS WITHIN THE DWELLING UNIT TO SOUND.
  
 13.A FIRE HYDRANT IS SHOWN ON SHEET LP-1 BUT NOT ON
 SHEET A-1.IS THIS AN EXISTING HYDRANT OR A PROPOSED
 HYDRANT TO BE INSTALLED?
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-20 Cont ID  
Sent By adarroug Date 2008-06-20 Time 10:51 Rev Time 0.00
Received By adarroug Date 2008-06-20 Time 10:51 Sent To  
Notes
2008-06-23 09:52:24TO "COMM" BD#62
2008-06-20 10:52:32WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 14:13 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 14:13 Sent To  
Notes
2007-11-21 11:06:03TO "COMM" BD#7/PLANS ON RACK
2007-11-07 14:13:44WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-15 Cont ID  
Sent By mawillia Date 2007-02-15 Time 17:34 Rev Time 0.00
Received By mawillia Date 2006-12-20 Time 16:43 Sent To  
Notes
2007-01-11 10:12:57TO "COMM" BD#31
2006-12-20 16:43:20WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-24 Cont ID  
Sent By tgordon Date 2008-06-24 Time 13:58 Rev Time 1.30
Received By tgordon Date 2008-06-24 Time 13:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-27 Cont ID  
Sent By tgordon Date 2007-11-27 Time 08:14 Rev Time 1.15
Received By tgordon Date 2007-11-27 Time 08:14 Sent To  
Notes
2007-11-27 08:23:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, PER
 2004 FBC 13-600.3.A, (12-8-06 REVISION). NOT 2001.
  
 2 ENERGY CALCULATIONS NEED TO BE SIGNED BY THE PREPARER
 AND THE OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2.
  
 3) COULD NOT FIND THE A/C SYSTEMS LISTED ON THE
 MECHANICAL PLANS (PAGE M-1 & M-2) ON THE ARI DIRECTORY
 WEB SITE. PLEASE SUBMIT THE ARI REFERENCE NUMBER OR A
 COPY OF THE ARI PERFORMANCE CERTIFICATE, SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 4) LAST REVIEW 1-22-07 NOTE #7 STATED THE RETURN AIR
 TRANSFER DUCTS WERE UNDER SIZED, THIS WAS IN REFERENCE
 TO THE FLEX DUCTS NOT THE GRILLS, PLEASE BE ADVISED IF
 THEY REMAIN THE SAME A PRESSURE DIFFERENTIAL TEST WILL
 BE DONE AT FINAL INSPECTION AND CORRECTIONS MAY BE
 REQUIRED, SEE 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By tgordon Date 2007-01-22 Time 08:51 Rev Time 1.15
Received By tgordon Date 2007-01-22 Time 08:51 Sent To P
Notes
2007-01-22 09:15:11*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #1, PLEASE CORRECT.
  
 2) SEE ENERGY CALCULATIONS TOTAL COOLING BTU'S 264,000,
 AND PLANS ARE SHOWING 8 UNITS AT 59,000 = 472,000 TOTAL
 BTU'S, THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 3) PLEASE SUBMIT MANUAL J CALCULATIONS FOR MODEL "A"
 ONE UNIT ONLY 2081 SQUARE FEET, AND MODEL "B" ONE UNIT
 ONLY 2157 SQUARE FEET.
  
 4) FORTH BEDROOM OPTION IS MISSING FROM MECHANICAL
 PLANS PAGE M-2, PLEASE CORRECT.
  
 5) SEE PAGE M-2 FIRST FLOOR PLAN POWER ROOM #102,
 EXHAUST UP TO ATTIC, EXHAUST AIR MUST DISCHARGE TO THE
 OUTDOORS, SEE 2004 FBC/M 501.2. PLEASE CORRECT.
  
 6) SEE PAGE M-1 FIRST FLOOR PLAN, THE CLOTHES DRYER
 VENT MAY NOT DISCHARGE ON TO THE A/C CONDENSER UNIT,
 SEE 2004 FBC/M 401.5.2. PLEASE CORRECT.
  
 7) RETURN AIR TRANSFER DUCTS TO ALL ROOM ARE
 UNDER-SIZED, BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-07-21 Cont ID  
Sent By kstevens Date 2008-07-21 Time 10:30 Rev Time 0.00
Received By kstevens Date 2008-07-21 Time 10:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By kstevens Date 2007-12-03 Time 18:49 Rev Time 0.00
Received By kstevens Date 2007-12-03 Time 18:49 Sent To  
Notes
2007-12-03 18:53:36DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. SUBMIT WATER RISER DIAGRAMS FOR EACH UNIT TYPE. SHOW
 ALL PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. (WASH MACHINES, DISH
 WASHERS, & ICE MAKERS). WATER HAMMER ARRESTORS SHALL BE
 LOCATED IN AN "EFFECTIVE RANGE", (NOT IN THE CEILING),
 PER PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
 SECTION 106.3.5.1.3(3)(13).
 ****RESPONSE NOTED, BUT THE RISER FOR BOTH UNITS "A"
 &"B" BOTH SHOW THE WATER LINE AS IT ENTERS INSIDE THE
 BUILDING CHANGING TO 1/2" THEN CHANGES TO 1" TO THE
 HEATER ETC. PLEASE CLARIFY. ALSO SHUT OFF VALVES SHALL
 BE INSTALL ON THE SUPPLY LINE TO EACH HOSE BIBB.
 SECTION 606.2(2).
  
 6. OK
 7. OK - INFORMATIONAL
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By kstevens Date 2007-02-06 Time 09:56 Rev Time 0.00
Received By kstevens Date 2007-02-06 Time 09:56 Sent To  
Notes
2007-02-06 10:30:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P-1 UNIT A SANITARY RISER DIAGRAM. THE AUTOMATIC
 CLOTHES WASHER FIXTURE SHALL CONNECT TO A BRANCH DRAIN
 OR DRAINAGE STACK A MINIMUM OF 3" IN DIAMETER. SECTION
 406.3.--THE FITTING SHOWN AT THE TOP OF THE STACK
 IS NOT APPROVED. THERE SHOULD BE A WYE DOWNSTREAM AND A
 SWEEP ABOVE THE WYE TO CONNECT THE THREE BATHROOM
 GROUPS. (SEE RED LINE EXAMPLE ON ONE SET OF PLANS).
  
 2. SHT P-1 WATER HEATER DETAIL, IF A BACKFLOW PREVENTOR
 IS REQUIRED, THEN THERMAL EXPANSION CONTROL WILL BE
 REQUIRED PER SECTION 607.3.2.
  
 3. SHT P-2 UNIT B SANITARY RISER DIAGRAM. THE AUTOMATIC
 CLOTHES WASHER FIXTURE SHALL CONNECT TO A BRANCH DRAIN
 A MINIMUM OF 3" IN DIAMETER. SECTION 406.3.--THE
 TUB AND THE WATER CLOSET AT THE BASE OF THE STACK ARE
 NOT VENTED. SECTION 901.2.1.--ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUP SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT.
 SECTION 909.1. THE SECOND FLOOR MASTER BATH & BATH #2
 SHALL CONNECT DOWNSTREAM OF THE BATHROOM FIXTURES IN
 OPTIONAL BATHROOM #4. THE AAV FOR OPTIONAL BATHROOM #4
 SHALL BE INSTALLED FOR THE BRANCH LINE FOR THE BATHROOM
 ONLY. AS SHOWN IT IS VENTING ONLY THE LAV. (SEE RED
 LINE EXAMPLES ON ONE SET OF PLANS).
  
 4. MORE INFORMATION IS REQUIRED. ARE THE UNITS TO BE
 INDIVIDUALLY METERED? IF THERE IS A SINGLE WATER METER,
 AN RPZV BACKFLOW WILL BE REQUIRED. SECTION 608.13.2.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 5. SUBMIT WATER RISER DIAGRAMS FOR EACH UNIT TYPE. SHOW
 ALL PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. (WASH MACHINES, DISH
 WASHERS, & ICE MAKERS). WATER HAMMER ARRESTORS SHALL BE
 LOCATED IN AN "EFFECTIVE RANGE", (NOT IN THE CEILING),
 PER PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
 SECTION 106.3.5.1.3(3)(13)
  
 6. SUBMIT PLUMBING FLOOR PLANS FOR EACH UNIT SHOWING
 THE SANITARY, WATER, P/T DISCHARGE LINE, EMERGENCY W/H
 PAN DRAIN LINE, THE WATER SERVICE, AND SANITARY SEWER
 LOCATIONS. SECTION 106.3.5.1.3(4)(10).
  
 7. AN IRRIGATION PERMIT AND PLANS ARE REQUIRED. SECTION
 105.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2008-07-03 Time   Rev Time 0.00
Received By jroach Date 2008-06-26 Time 10:18 Sent To  
Notes
2008-07-03 08:38:35***FAILED***
  
 1) SITE PLAN APPROVAL HAS EXPIRED.A NEW APPLICATION
 SHALL BE SUBMITTED FOR AN INFORMAL SITE PLAN REVIEW TO
 THE CITY'S PLANNING AND ZONING DEPARTMENT.AS SHOWN IN
 THE ATTACHED LETTER TO MR. JON SCHMIDT, DATED JUNE 20,
 2008, NO EXTENSION MAY BE GRANTED AS THE APPLICATION
 HAS ALREADY BEEN ISSUED A PREVIOUS EXTENSION, AND HAS
 EXPIRED.
  
 2) TWO (2) COPIES OF A CURRENT/ACCURATE SURVEY WAS NOT
 SUBMITTED WITH THE PACKAGE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-12-18 Cont ID  
Sent By jroach Date 2007-12-18 Time 15:30 Rev Time 0.00
Received By jroach Date 2007-12-18 Time 15:30 Sent To  
Notes
2007-12-18 15:35:53***FAILED***
  
 1) SITE PLAN APPROVAL HAS EXPIRED.A NEW APPLICATION
 SHALL BE SUBMITTED FOR AN INFORMAL SITE PLAN REVIEW TO
 THE CITY'S PLANNING AND ZONING DEPARTMENT.
  
 2) TWO (2) COPIES OF A CURRENT/ACCURATE SURVEY WAS NOT
 SUBMITTED WITH THE PACKAGE.
  
 3) PLEASE REMOVE ONE OF THE SITE PLANS EACH CONTAIN
 DIFFERENT INFORMATION.IT WOULD PROBABLY BE BEST TO
 COPY THE SITE DATA TABLE, ETC. ONTO SHEE A-1 AND REMOVE
 SHEET SP-1.
  
 4) THE CIVIL PLANS DO NOT MATCH THE SITE/LANDSCAPE
 PLANS.THE CIVIL PLANS SHOW A SIDEWALK CONNECTING THE
 HC SPACE TO THE END UNIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-25 Cont ID  
Sent By jroach Date 2007-01-25 Time 14:59 Rev Time 0.00
Received By jroach Date 2007-01-25 Time 14:59 Sent To  
Notes
2007-01-25 15:09:29***FAILED***
  
 1)PLEASE CLARIFY AS TO WHETHER OR NOT THE TWO (2)
 SURFACE PARKING SPACES WILL BE PROVIDED NEAR EMBASSY
 DRIVE.THESE SPACES ARE SHOWN ON THE LANDSCAPE PLANS,
 BUT NOT ON THE SITE PLAN, NOR THE CIVIL PLANS.PLEASE
 ENSURE THAT ALL PLANS ARE CONSISTENT.
  
 2) PLEASE NOTE ON THE PLANS THAT THE FENCE WILL BE
 PROVIDED UNDER A SEPARATE PERMIT.....AS A SEPARATE
 PERMIT WILL BE REQUIRED.PLEASE PROVIDE A DETAIL
 ELEVATION OF THE PROPOSED FENCE.UPON APPLYING FOR THE
 FENCE PERMIT, A COMPLETED AND SIGNED EASEMENT RELEASE
 FORM SHALL BE PROVIDED FROM THE CITY'S PUBLIC UTILITIES
 DEPARTMENT.AS THE FENCE IS PROPOSED TO CROSS AN
 EASEMENT, EASEMENT RELEASES SHALL BE PROVIDED FROM ALL
 OF THE UTILITY COMPANIES (ADELPHIA, FP&L, FLORIDA
 PUBLIC UTILITIES, AND BELLSOUTH).
  
 3) A DATA TABLE SHALL BE PROVIDED ON THE SITE PLAN
 PROVIDING ALL THE NECESSARY CODE COMPLIANT INFORMATION.
 PLEASE CONTACT ME FOR A LIST OF THE NECESSARY DATA.
  
 4) PLEASE DESIGNATE THE SHADE TREES AND FLOWERING TREES
 WITHIN THE PLANT LIST.
  
 5) THE PLANT LIST DOES NOT CORRESPOND TO THE LANDSCAPE
 CALCULATION TABLE AS FAR AS THE NUMBER OF TREES/SHRUBS,
 ETC.
  
 6) NOT ALL PAVEMENT IS SHOWN ON THE CIVIL PLANS (I.E.
 SIDEWALKS, PATIOS, ETC.).
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.