Plan Review Details - Permit 06120570
Plan Review Stops For Permit 06120570
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-11-08 Cont ID  
Sent By shill Date 2007-11-08 Time 13:22 Rev Time 0.00
Received By shill Date 2007-11-08 Time 13:22 Sent To  
Notes
2007-11-08 13:25:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 FROM PREVIOUS LISTS:
  
 1.)PROVIDE INFORMATION ABOUT THE EXISTING DOOR.
 PROVIDE A DESCRIPTION:
  
 IS THE EXISTING DOOR GLAZED?
 DIMENSIONS OF GLAZING IN THE EXISTING DOOR
  
 THIS IS THE SIXTH REQUEST FOR INFORMATION IN REGARDS TO
 THE EXISTING DOOR.PLEASE PROVIDE REQUESTED
 INFORMATION.
  
 THE PLAN STATES "CHANGEOUT 1 DOOR OPENING NO SIZE
 CHANGE FIBERGLASS DOOR GLAZED."I UNDERSTAND THAT THE
 OPENING SIZE IS NOT CHANGING.THIS STATEMENT DOES NOT
 ADDRESS MY VERY SPECIFIC QUESTIONS IN REGARDS TO THE
 GLAZING.PROVIDE THE REQUESTED INFORMATION, IS THE
 EXISTING DOOR GLAZED?IF IT IS, PROVIDE DIMENSIONS OF
 THE GLAZING IN THE EXISTING DOOR.
  
 NUMEROUS NOTES REFER TO THE 25% RULE.ALTHOUGH THE 25%
 RULE CAN BE APPLIED, THIS IS FOR REPLACEMENT GLAZING
 ONLY.YOU CANNOT ADD NEW GLAZED OPENINGS OR INCREASE
 THE AREA OF GLAZING.
  
 TO GET THIS PERMIT, YOU MUST EITHER PROVIDE HURRICANE
 SHUTTER INFORMATION OR PROVIDE THE INFORMATION
 REQUESTED SO THAT CODE COMPLIANCE CAN BE DETERMINED.
  
 IF YOU DO NOT UNDERSTAND THIS CORRECTION, PLEASE CALL
 ME FOR ASSISTANCE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-04-30 Cont ID  
Sent By shill Date 2007-04-30 Time 15:55 Rev Time 0.00
Received By shill Date 2007-04-30 Time 15:55 Sent To  
Notes
2007-04-30 16:00:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)PROVIDE INFORMATION ABOUT THE EXISTING DOOR.
 PROVIDE A DESCRIPTION:
  
 SIZE OF DOOR
 IS THE EXISTING DOOR GLAZED?
 DIMENSIONS OF GLAZING IN THE EXISTING DOOR
  
 THIS IS THE FIFTH REQUEST FOR INFORMATION IN REGARDS TO
 THE EXISTING DOOR.PLEASE PROVIDE REQUESTED
 INFORMATION.
  
 THE PLAN STATES "CHANGEOUT 1 DOOR OPENING NO SIZE
 CHANGE FIBERGLASS DOOR GLAZED."I UNDERSTAND THAT THE
 OPENING SIZE IS NOT CHANGING.THIS STATEMENT DOES NOT
 ADDRESS MY VERY SPECIFIC QUESTIONS IN REGARDS TO THE
 GLAZING.PROVIDE THE REQUESTED INFORMATION, IS THE
 EXISTING DOOR GLAZED?IF IT IS, PROVIDE DIMENSIONS OF
 THE GLAZING IN THE EXISTING DOOR.
  
 NUMEROUS NOTES REFER TO THE 25% RULE.NOTE THAT THIS
 DOES NOT APPLY ON APPLICATONS AFTER JANUARY,2007.
  
 TO GET THIS PERMIT, YOU MUST EITHER PROVIDE HURRICANE
 SHUTTER INFORMATION OR PROVIDE THE INFORMATION
 REQUESTED SO THAT CODE COMPLIANCE CAN BE DETERMINED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-03-23 Cont ID  
Sent By shill Date 2007-03-23 Time 18:07 Rev Time 0.00
Received By shill Date 2007-03-23 Time 18:07 Sent To  
Notes
2007-03-23 18:07:33****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)PROVIDE INFORMATION ABOUT THE EXISTING DOOR.
 PROVIDE A DESCRIPTION:
  
 SIZE OF DOOR
 IS THE EXISTING DOOR GLAZED?
 DIMENSIONS OF GLAZING IN THE EXISTING DOOR
  
 THIS IS THE FOURTH REQUEST FOR INFORMATION IN REGARDS
 TO THE EXISTING DOOR.PLEASE PROVIDE REQUESTED
 INFORMATION.
  
 NEW COMMENT:
  
 2.) FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG.THE FLORIDA STATE
 PRODUCT APPROVAL PROVIDED IS EXPIRED, FBC2001 RATHER
 THAN FBC2004.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-03-08 Cont ID  
Sent By shill Date 2007-03-08 Time 13:57 Rev Time 0.00
Received By shill Date 2007-03-08 Time 13:57 Sent To  
Notes
2007-03-08 13:59:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)PROVIDE INFORMATION ABOUT THE EXISTING DOOR.
 PROVIDE A DESCRIPTION:
  
 SIZE OF DOOR
 IS THE EXISTING DOOR GLAZED?
 DIMENSIONS OF GLAZING IN THE EXISTING DOOR
  
 THIS IS THE THIRD REQUEST FOR INFORMATION IN REGARDS TO
 THE EXISTING DOOR.PLEASE PROVIDE REQUESTED
 INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-20 Cont ID  
Sent By shill Date 2007-02-20 Time 17:06 Rev Time 0.00
Received By shill Date 2007-02-20 Time 17:06 Sent To  
Notes
2007-02-20 17:07:29***CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 FROM PREVIOUS LIST, NOT ADDRESSED:
  
 WINDOW OR DOOR PERMIT APPLICATION, ONLY CHECKED ITEMS
 APPLY
  
  
 _XX_4. IS THE EXISTING DOOR A GLAZED DOOR?
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-26 Cont ID  
Sent By shill Date 2007-01-26 Time 16:33 Rev Time 0.00
Received By shill Date 2007-01-26 Time 16:33 Sent To  
Notes
2007-01-26 16:34:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 WINDOW OR DOOR PERMIT APPLICATION, ONLY CHECKED ITEMS
 APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 ____2.PROVIDE BUILDING HEIGHT.DESIGN PRESSURES
 FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.IMPACT PROTECTION REQUIRED,FBC1609.1.4.IF
 LESS THAN 25% OF THE TOTAL GLAZED AREA IS BEING
 REPLACED, PROVIDE CALCULATIONS FBC EB507.3.IS THE
 EXISTING DOOR A GLAZED DOOR?
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____6.PROVIDE A FLOOR PLAN SHOWING: WINDOW
 LOCATIONS, SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE
 EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE
 FOR BEDROOMS, FBC R310, FBC EB 505.1.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 16:09 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 16:09 Sent To B
Notes
2007-11-07 16:10:08TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-30 Cont ID  
Sent By adarroug Date 2007-04-30 Time 11:17 Rev Time 0.00
Received By adarroug Date 2007-04-30 Time 11:17 Sent To B
Notes
2007-04-30 11:17:38TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-23 Cont ID  
Sent By adarroug Date 2007-03-23 Time 11:37 Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 11:37 Sent To B
Notes
2007-03-23 11:37:25TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-07 Cont ID  
Sent By adarroug Date 2007-03-07 Time 10:00 Rev Time 0.00
Received By adarroug Date 2007-03-07 Time 10:00 Sent To B
Notes
2007-03-07 10:00:34TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 16:12 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 16:12 Sent To B
Notes
2007-02-15 16:12:38TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-26 Cont ID  
Sent By shill Date 2007-01-26 Time 16:34 Rev Time 0.00
Received By shill Date 2006-12-21 Time 15:11 Sent To  
Notes
2006-12-21 15:11:42TO "MISC" BOX#1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***