Plan Review Details - Permit 06120546
Plan Review Stops For Permit 06120546
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-02-16 Cont ID  
Sent By mperson Date 2007-02-16 Time 08:24 Rev Time 0.33
Received By mperson Date 2007-02-16 Time 08:24 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-01-02 Cont ID  
Sent By mperson Date 2007-01-02 Time 10:41 Rev Time 0.45
Received By mperson Date 2007-01-02 Time 10:41 Sent To PC
Notes
2007-01-02 11:27:09DENIED
 REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: PLEASE INDICATE ON THE RESUBMITTED DRAWINGS THAT
 THE 100' INDICATED IS THE TOTAL DEVELOPED LENGTH FROM
 THE METER TO THE POOL HEATER.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: PLEASE INDICATE THE ABOVE GROUND PIPING MATERIAL
 BEING USED, THE ONLY MATERIAL INDICATED ON DRAWINGS
 BEING USED IS PE. PLEASE CORRECT THIS ON THE
 RESUBMITTAL.
  
 3. TYPE OF GAS, (LP OR NATURAL) MUST BE INDICATED ON
 THE RESUBMITTED DRAWINGS.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: PLEASE INDICATE ON THE RESUBMITED DRAWINGS THE
 EXISTING HOUSE BTU LOAD TO VERIFY WETHER THE MP
 REGULATOR SPECIFIED IS COMPLIANT.
  
 5. THE MP REGULATOR SPECIFIED FOR THE POOL HEATER IS
 WRONG. PLEASE REFERENCE THE ATTACHED MAXITROL
 SPECIFICATION SHEET FOR THE RESUBMITTAL. THE MAXIMUM
 INDIVIDUAL LOAD FOR A MAXITROL-5AL IS 300,000 BTU'S THE
 INDICATED POOL HEATER IS 399,000 BTU'S. THE CORRECT MP
 REGULATOR SHOULD BE A MAXITROL 325-7L. PLEASE CORRECT
 THIS ON THE RESUBMITTAL.
  
 6. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 15:55 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 15:55 Sent To G
Notes
2007-02-14 15:56:14TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-02 Cont ID  
Sent By mperson Date 2007-01-02 Time 11:30 Rev Time 0.00
Received By mperson Date 2006-12-20 Time 10:09 Sent To  
Notes
2006-12-20 10:09:48TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved