Plan Review Details - Permit 06120514
Plan Review Stops For Permit 06120514
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-01-03 Cont ID  
Sent By shill Date 2007-01-03 Time 08:48 Rev Time 0.00
Received By shill Date 2007-01-03 Time 08:48 Sent To  
Notes
2007-01-03 08:50:03***PLAN REVIEW ONLY***CONTRACTOR TO APPLY FOR PERMIT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-24 Cont ID  
Sent By dpalmer Date 2006-12-24 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2006-12-24 Time 16:32 Sent To  
Notes
2006-12-24 16:38:12*** UNSAT ***
  
  
 ** PLEASE KNOW AS THIS REVIEW THE PLAN REVIEW FEES HAVE
 NOT YET BEEN PAID.
  
 1) NOTE: PLEASE KNOW AS PLANS HAVE ONLY BEEN SUBMITTED
 FOR PLAN REVIEW, THE PERMIT APPLICATION WILL BE PART OF
 THE REVIEW. PLEASE ALSO KNOW THE MINIMUM CODES SHALL BE
 STATED ON PLANS FOR WHICH THEY WERE DESIGNED UNDER.
 PLEASE KNOW AS OF DEC 8TH, 2006 THE FBC AND THE NFPA-70
 (NEC) CHANGED.
 NEC IS 2005 AND REVISIONS TO THE FBC WENT INTO AFFECT.
  
 2) NOTE:WHEN PERMIT APPLICATION IS MADE, PLEASE SEE
 VALUE ON PLANS FOR SCOPE OF WORK SUBMITTED SHALL
 INCLUDE ALL LABOR AND MATERIALS EVEN IF
 EQUIPMENT/MATERIALS IS OWNER SUPPLIED.
 FBC 108.3
  
 3) NOTE: PLEASE SEE ADDRESS ON TITLE BLOCKS FOR CAMP,
 DRESSER & MCKEE INC, DOES NOT CORRELATE WITH THE
 STATE'S WEBSITE. PLEASE OBTAIN WRITTEN DOCUMENTATION
 FROM THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION THAT THE ADDRESS AS SHOWN LOCALLY IS OK,
 WHICH DOES NOT CORRESPOND TO THE STATE'S TAMPA
 ADDRESS.
  
 OPT#2, PLEASE ADJUST TITLE BLOCKS TO REFLECT THE
 ADDRESS AS LISTED ON STATE'S WEBSITE. PLEASE SEE THAT I
 HAVE ATTACHED A PRINT FROM THE STATE DBPR'S WEBSITE
 WHICH REFLECTS THIS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2006-12-28 Cont ID  
Sent By rchokshi Date 2006-12-28 Time 15:13 Rev Time 0.00
Received By rchokshi Date 2006-12-28 Time 15:09 Sent To  
Notes
2006-12-28 15:13:39THEREIS NOTHING IN THE DRAWING THAT I AM SUPPOSED TO
 REVIEWENG POINT OF VIEW FOR THIS JOB.I TALKED TO
 LUIS M. IF I AM MISSING TO REVIEW.LUIS & I AGREED
 THATWRITE "N"NOT APPLICABLE.
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-25 Cont ID  
Sent By mawillia Date 2007-01-25 Time 16:36 Rev Time 0.00
Received By mawillia Date 2007-01-25 Time 16:36 Sent To  
Notes
2007-01-25 17:07:15*****DENIED*****
  
  
 NOT ENOUGH INFORMATION ON THE PROPOSED SCOPE OF WORK TO
 CONDUCT AN ADEQUATE FIRE FIRE PLAN REVIEW.PLEASE BE
 ADVISED THAT:
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.CONSTRUTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER WITH EMERGENCY RESPONSE ACCESS TO
 THE SAID PROPERTY OR VICINITY THEREOF.
  
 3.ACCESS TO FIRE HYDRANTS, FIRE DEPARTMENT
 CONNECTIONS, OR ANY OTHER FIRE PROTECTION EQUIPMENT
 SHALL BE MAINTAINED AT ALL TIMES.
  
 4.PROVIDE ONE OR MORE DEDICATED FIRE EXTINGUISHERS
 THAT HAVE A MINIMUM CAPABILITY OF 40:BC LOCATED WITHIN
 100 FEET OF THE WORK AREA.
  
 5.CUTTING/WELDING OPERATIONS USED IN THE SCOPE OF
 WORK SHALL COMPLY WITH NFPA 51B.
  
  
 TO EXPEDITE THE FIRE PLAN REVIEW PROCESS,SEE OTHER
 PLAN REVIEW COMMENTS AND INCLUDE A RESPONSE LETTER
 INDICATING HOW/WHERE EACH OF THE ABOVE ITEMS WERE
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-25 Cont ID  
Sent By mawillia Date 2007-01-25 Time 17:22 Rev Time 0.00
Received By mawillia Date 2006-12-20 Time 16:58 Sent To  
Notes
2006-12-22 14:11:20TO "COMM" BD#17---EXPEDITED PERMIT---
2006-12-20 16:58:46WAITING FOR "COMM" BD--CITY PROJECT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-01-04 Cont ID  
Sent By pkrauss Date 2007-01-04 Time 11:09 Rev Time 0.00
Received By pkrauss Date 2007-01-04 Time 09:30 Sent To  
Notes
2007-01-04 11:17:45********PLAN CHECK ONLY*********
  
 PROVISO:
 PLEASE PROVIDE MANUFACTURER'S SUBMITTAL
 DATA/INSTALLATION INSTRUCTIONS FOR THE EXHAUST
 SILENCERS ON THE JOBSITE AT THE TIME OF INSPECTION.
  
 PLANS WILL BE "PASSED" WHEN ITEMS FROM OTHER
 DISCIPLINES ARE ADDRESSED AND PLANS ARE SUBMITTED FOR
 "PERMIT".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-02 Cont ID  
Sent By kstevens Date 2007-01-02 Time 10:45 Rev Time 0.00
Received By kstevens Date 2007-01-02 Time 10:45 Sent To  
Notes
2007-01-02 14:13:29DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 PLAN REVIEW ONLY;
  
 1. ADDRESS FOR CAMP, DRESSER & MCKEE DOES NOT REFLECT
 THE ADDRESS ON THE DBPR WEBSITE. PLEASE CLARIFY. ALL
 TITLE BLOCKS SHALL INDICATE THE ADDRESS PER FAC
 61G1-16.004(1) & FS 481.025. (SEE ATTACHED SHEET FROM
 DBPR WEBSITE).
  
 2. SHT M-3 INDICATES A 2" PVC SUPPLY TO A "HB". PER THE
 ABBREVIATION SHEET THAT WOULD BE A HOSE BIBB. PLEASE
 CLARIFY THAT A 2" SUPPLY IS REQUIRED FOR THE "HB" AND
 THAT THE "HB" IS A HOSE BIBB. ALSO IF IT IS A HOSE
 BIBB, A SHUT OFF VALVE IS REQUIRED ON THE SUPPLY LINE
 TO EACH HOSE BIBB. SECTIONS 106.1.1 AND 606.1(2).
  
 3. SHT M-3 INDICATES PVC TO THE RPZV BACKFLOW AND ON TO
 THE VAPEX UNITS 1 & 2. CLARIFICATION IS REQUIRED, AS
 PVC PIPE IS NOT APPROVED FOR DISTRIBUTION PIPING INSIDE
 THE STRUCTURE. PLEASE INDICATE IF THE PIPING IS INSIDE
 THE STRUCTURE OR OUTSIDE. SECTION 106.1.1 AND TABLE
 605.4.
  
 4. SHT CD-2 DETAIL J. THE CITY WPB STANDARD FOR THE
 BACKFLOW CALLS FOR BALL VALVES. DETAIL J INDICATES GATE
 VALVES. PLEASE CHANGE DETAIL TO CORRELATE WITH THE CITY
 UTILITY STANDARD.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-01-12 Cont ID  
Sent By kdfreema Date 2007-01-12 Time 13:58 Rev Time 0.00
Received By kdfreema Date 2007-01-12 Time 13:58 Sent To  
Notes
***NONE***