Plan Review Details - Permit 06120465
Plan Review Stops For Permit 06120465
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-11-26 Cont ID  
Sent By rmcdouga Date 2007-11-26 Time 16:27 Rev Time 0.00
Received By rmcdouga Date 2007-11-26 Time 16:27 Sent To  
Notes
2007-11-26 16:38:15REVISIONS TO SHEETS A-1 AND A-2 REMOVING THE WASHER,
 DRYER AND TANKLESS WATER HEATER AND RELATED PLUMBING
 AND ELECTRIC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-11-14 Cont ID  
Sent By rmcdouga Date 2007-11-14 Time 18:26 Rev Time 0.00
Received By rmcdouga Date 2007-11-14 Time 18:26 Sent To P
Notes
2007-11-14 18:43:302004 FBC
 REVISED SHEETS A-1 AND A-2.
  
 DENIED BY BUILDING
  
 1) THE INTENTION OF THE REVISED PLANS THAT WERE
 SUBMITTED IS TO DELETE CERTAIN ITEMS IN THE LAUNDRY
 ROOM ADDITION FROM THE SCOPE OF WORK. HOWEVER, THE
 ITEMS THAT WERE TO BE ELIMINATED ARE STILL SHOWN ON THE
 DRAWINGS. THE PROPER WAY TO SHOW THIS ON THE PLANS IS
 TO BLANK OUT THE ITEM AND CLOUD AND NUMBER THE AREA
 WHERE THE ITEM WAS SHOWN ON THE PLAN THAT IS BEING
 CHANGED. FBC 106.1* CITY AMENDMENTS. PLEASE CORRECT.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-13 Cont ID  
Sent By rmcdouga Date 2007-06-12 Time 14:13 Rev Time 0.00
Received By rmcdouga Date 2007-06-12 Time 14:13 Sent To  
Notes
2007-06-12 15:22:40BUILDING PROVISO
  
 PRIOR TO INSTALLATION, SUBMIT RAS 117 CALCULATIONS FOR
 THE ENHANCED FASTENING AT THE PERIMETER AND CORNER ROOF
 AREAS FOR THE FIRESTONE MODIFIED ROOF SYSTEM (NOA
 05-0830.10). THE INFORMATION THAT WAS SUBMITTED IS NOT
 ACCEPTABLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-27 Cont ID  
Sent By rmcdouga Date 2007-03-27 Time 17:41 Rev Time 0.00
Received By rmcdouga Date 2007-03-27 Time 16:44 Sent To  
Notes
2007-03-27 17:41:37DENIED BY BUILDING (2ND REVIEW)
  
 1) ALL OF THE ROOF SHEATHING IS REQUIRED TO BE FASTENED
 WITH 8D RING SHANK NAILS. PLEASE REVISED NOTES ON A2 TO
 SPECIFY 8D RING SHANK NAILS.
  
 2) THE DRAINAGE PLAN IS REQUIRED TO SHOW THAT THE
 SURFACE DRAINAGE WILL BE ROUTED TO THE STORM DRAIN OR
 OTHER APPROVED COLLECTION POINT AND NOT ONTO ADJACENT
 LOTS.
  
 3)SHOW COMPLIANCE WITH R310.4 FOR EMERGENCY EGRESS
 WHEN STORM PANELS ARE INSTALLED.
 R310.4 REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 4) THE DESIGN PRESSURE FOR THE SELECTED FIRESTONE
 MODIFIED ROOF SYSTEM IS 52.5 PSF, WHICH IS TOO LOW FOR
 ROOF ZONES 2 AND 3. SUBMIT RAS 117 CALCULATIONS FOR
 INCEASED FASTENER DENSITIES FOR THESE AREAS AS ALLOWED
 BY GENERAL LIMITATION NUMBER 7 ON PAGE 34 OF THE NOA.
  
 5) GLASS BLOCK INSTALLED WITH MORTAR IN ACCORDANCE WITH
 FBC SECTION 2110 IS NOT REQUIRED TO BE PROTECTED WITH
 STORM PANELS.
  
 6) THE STORM PANEL INSTALLATION SCHEDULE SUBMITTED
 CONTAINS SOME ERRORS. THE CALK-IN ANCHORS ARE REQUIRED
 TO HAVE A 7/8 " EMBEDMENT, NOT 1/8". THE EDGE DISTANCE
 REFERS TO THE SPACE BETWEEN THE EDGE OF THE OPENING AND
 THE STORM PANEL ANCHORS. THE FASTENER SPACING IS
 RELATED TO THE EDGE DISTANCE. SEE THE ANCHOR SPACING
 TABLES IN THE PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-30 Cont ID  
Sent By rmcdouga Date 2007-01-30 Time 12:00 Rev Time 0.00
Received By rmcdouga Date 2007-01-30 Time 06:46 Sent To  
Notes
2007-01-30 12:00:03DENIED BY BUILDING
  
 1)EXISTING COMPUTER ROOM/ BEDROOM MUST COMPLY WITH
 R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED. BASEMENTS
 WITH HABITABLE SPACE AND EVERY SLEEPING ROOM SHALL HAVE
 AT LEAST ONE OPENABLE EMERGENCY ESCAPE AND RESCUE
 OPENING.
 IF COMPUTER ROOM IS NOT USED AS A SLEEPING ROOM, THIS
 MUST BE SPECIFIED ON THE PLANS.
  
 2)ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE WITH
 SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC
 RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL
 BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT
 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS
 SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130
 MPH OR GREATER DESIGNWIND SPEEDS IN ACCORDANCE WITH
 FIGURE R803.2.3.1. PLEASE REVISE NOTES ON A2.
  
 3)SPECIFY THE REQUIRED DESIGN LOADS FOR THE TRUSS TOP
 AND BOTTOM CORDS ON THE PLANS. FBC 106.1.2
  
 4) SUBMIT A DRAINAGE PLAN SHOWING COMPLIANCE WITH
 R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 5) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS .
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 6) THE PRODUCT APPROVALS FOR THE DOUBLE OUTSWING FRONT
 DOORS DO NOT HAVE GLAZING IN THE DOORS. THE PLANS SHOW
 DOORS WITH GLAZING. PLEASE CLARIFY.
  
 7) SPECIFY THE OPENING PRESSURES FOR THE NEW DOOR TO
 THE LAUNDRY/STORAGE ROOM ON THE PLANS.
  
 8) INDICATE WHICH ONE OF THE APPROVED SYSTEMS FROM THE
 FIRESTONE MODIFIED ROOF SYSTEM NOA WILL BE INSTALLED.
 PLEASE CIRCLE THE APPROPRIATE ONE. ALSO CIRCLE THE
 FASTENING OPTION AND MAXIMUM DESIGN PRESSURE FOR THE
 SELECTED SYSTEM. SUBMIT RAS 117 CALCULATIONS FOR THE
 ENHANCED FASTENING REQUIREMENTS AT PERIMETER AND CORNER
 AREAS, WHICH IS ALLOWED BY LIMITATION #7.
  
 9) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE
 SPECIFING THE OPENINGS THAT WILL BE SHUTTERED. SPECIFY
 THE FASTENER TYPE AND SPACING, THE OPENING SIZES, THE
 SPANS, EDGE DISTANCE, THE CONNECTION TYPE, PRESSURE,
 ETC.
  
 10)SUBMIT ENERGY CALCULATIONS AS REQUIRED BY 2OO4 FBC
 CHAPTER 13.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-11-26 Cont ID  
Sent By dpalmer Date 2007-11-26 Time 10:54 Rev Time 0.00
Received By dpalmer Date 2007-11-26 Time 10:42 Sent To P
Notes
2007-11-26 10:55:17SA'S AS REQUIRED PER FBC R313 ARE ON A SEPARATE STAMPED
 SHEET.
 NFPA-72 11.5.1.1.1

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-11-09 Cont ID  
Sent By dpalmer Date 2007-11-09 Time 12:33 Rev Time 0.00
Received By dpalmer Date 2007-11-09 Time 12:33 Sent To P
Notes
2007-11-09 12:33:30** PROVISO **
  
 1) NOTE:PLANS SUBMITTED FOR REVISION #3 DO NOT
 INDICATE THE SCOPE OF WORK FOR DELETION OF TANK-LESS
 WATER HEATER. AS PER OWNER AND SPOKE TO ARCHITECT, THE
 TANK-LESS WATER HEATER ALONG WITH WASHER, DRYER AND
 SINK ARE NO LONGER IN SCOPE OF WORK TO BE DONE. NO
 ROUGH IN OR STUB OUTS FOR THESE ITEMS.
 ** PLANS WILL STILL NEED TO BE REVISED FOR ALL ITEMS AS
 PANEL SCHEDULE AND PLANS STILL CALL FOR WORK TO BE
 DONE, NOT ALL WAS DELETED. *EXAMPLE TANK-LESS WH.
  
 2) NOTE: THE PREVIOUS STAMPED PLANS STILL CONTAIN AN
 ATTACHMENT FOR THE EXISTING DWELLING TO COMPLY WITH FBC
 R313 AND NFPA-72 11.5.1.1.1 FOR SMOKE ALARMS.
  
 ** THESE ABOVE ITEMS SHALL ALL BE REVISED ON PLANS AND
 SUBMITTED FOR REVIEW AND STAMPING BEFORE FINAL
 INSPECTIONS.
 PLANS MUST BE ON SITE FOR ALL INSPECTIONS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTIONS SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-11-02 Cont ID  
Sent By dpalmer Date 2007-11-02 Time 12:30 Rev Time 0.00
Received By dpalmer Date 2007-11-02 Time 12:30 Sent To P
Notes
2007-11-02 12:30:52 
 ** DENIED REVISION **
  
 1) NOTE: PLEASE SUBMIT REVISIONS WHICH INDICATE THE
 ACTUAL ITEMS BEING REVISED. PLEASE SEE THE REVISION
 COVER SHEET MENTIONS THE CONNECTIONS TO THE WASHER AND
 DRYER ARE BEING DELETED, HOWEVER PLANS STILL INDICATE
 THE NEW WASHER AND DRYER?
 IT IS UNCLEAR WHAT IS BEING REVISED.
  
 2) NOTE: PLEASE SEE THE PLANS SUBMITTED NEED TO HAVE
 BOTH SETS SIGNED, DATED AND SEALED BY THE ARCHITECT OF
 RECORD.
 PLEASE SEE OF THE THREE SUBMITTED ONLY ONE CONTAINS AN
 ORIGINAL SIGNATURE AND SEAL.
 FBC ADMIN SECTION 106.1, 106.5.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
  
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-05-11 Cont ID  
Sent By dpalmer Date 2007-05-11 Time 12:21 Rev Time 0.00
Received By dpalmer Date 2007-05-11 Time 11:55 Sent To P
Notes
2007-05-11 12:21:46REDLINED 110.26 FOR TKLESS WH DISCONNECT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-24 Cont ID  
Sent By dpalmer Date 2007-03-24 Time 11:38 Rev Time 0.00
Received By dpalmer Date 2007-03-24 Time 11:08 Sent To P
Notes
2007-03-24 11:39:19 
  
 ****** UNSAT 2ND REVIEW******
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE MISSING DISCONNECT FOR THE NEW
 TANKLESS WATER HEATER PER 422.30,31.
 PLEASE SEE 110.26 FOR CLEARANCE.
  
 2) NOTE: PLEASE SEE THE FBC 2004 R313.1.1 AS SMOKE
 ALARMS ARE REQUIRE INSIDE AND OUTSIDE ALL SLEEPING
 ROOMS. THE 2004 FBC W/ THE 2006 REVISION WAS CHANGED TO
 REQUIRE THESE EVEN WHEN NOT DOING WORK INSIDE THE
 EXISTING DWELLING.
 PLEASE SHOW ON A LAYOUT OF THE EXISTING DWELLING. THESE
 SHALL BE SHOWN AS SA FOR SMOKE ALARMS NOT SD. SMOKE
 DETECTORS ARE DEVICES WHICH ONLY DETECT THE SMOKE AND
 DO NOT SOUND AN ALARM.
 SEE NFPA-72 DEFINITIONS.
 PLEASE SEE NFPA-72 11.5.1.1.1, AND 11.8.3 FOR
 PLACEMENT.
  
 3) NOTE: PLEASE SEE THE RECEPTACLE FOR THE WASHER AS IT
 IS WITHIN 6FT OF THE LAUNDRY SINK SHALL BE GFI
 PROTECTED EVEN IF THIS IS A DEDICATE DEVICE.PLEASE
 SEE THAT THIS IS REQUIRED FOR ALL RECEPTACLES WITHIN
 6FT OF LAUNDRY TUB WHICH ARE 15/20AMP AND 125V.
 THIS HAS CHANGED IN THE 2005 NEC.210.8A7
  
  
 ** PLEASE CALL TO OVER COMMENTS ONCE ALL OTHER TRADES
 ARE COMPLETED ON THEIR REVIEW. IF ALL OTHER TRADES ARE
 OK, THEN THIS MAY BE SET UP AS A * PROVISO* WHICH
 PERMITS ISSUANCE OF PERMIT AND REVISED PLANS WILL BE
 REQUIRED BEFORE INSPECTION.
 IF PLANS COME BACK WITH ANY COMMENTS FROM OTHER TRADES
 FOR ANY REASON, PLEASE MAKE CORRECTIONS AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-24 11:08:57FROM ZONING ON 3/21

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-29 Cont ID  
Sent By dpalmer Date 2006-12-29 Time 07:48 Rev Time 0.00
Received By dpalmer Date 2006-12-29 Time 07:01 Sent To M
Notes
2006-12-29 07:52:03** UNSAT **
  
 1) NOTE: PLEASE INDICATE ON PANEL SCHEDULE ALL NEW AND
 EXISTING CIRCUITS AS SOME ITEMS ON PLANS ARE SHOWN AS
 NEW AND PANEL SCHEDULE SHOWS THEM AS NEW , YET SOME
 ITEMS ON PLANS APPEAR TO BE SHOWN NEW , YET PANEL
 SCHEDULE DOES NOT SHOW THESE AS NEW?
 PLEASE ALSO CLARIFY NEW SMALL APPLIANCE CIRCUIT BEING
 SHOWN ON PANEL SCHEDULE. PLEASE SEE THIS IS BEING
 SHOWN, YET NO WORK IS BEING SHOWN IN ANY AREAS WHICH
 WOULD CONSIDER THIS AS A SMALL APPLIANCE CIRCUIT.
 PLEASE SEE 210.52B1
 PLEASE ALSO SEE 408.4.
  
 2) NOTE: PLEASE SUBMIT THE MANUFACTURES SPEC/CUT SHEETS
 FOR THE NEW TANK LESS WATER HEATER. PLEASE BE SURE IT
 CONTAINS A LISTING FROM NATIONALLY RECOGNIZED TESTING
 LABORATORY AS REQUIRED PER 110.3, 90.7.
 FBC ADMIN SECTION 106.1.2.
  
 3) NOTE: PLEASE LIST THE 2005 NEC ON PLANS. PLEASE KNOW
 AS INFORMATIONAL PURPOSE THE STATE ADOPTED THE NEW
 REVISIONS TO THE 2004 FBC AND THE NEW NFPA-70 (NEC)
 2005 AS OF DECEMBER 8, 2006. ALL PERMIT APPLICATIONS
 MADE AFTER THIS DATE WILL BE UNDER THESE NEW CODES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-21 Cont ID  
Sent By adarroug Date 2007-11-21 Time 10:23 Rev Time 0.00
Received By adarroug Date 2007-11-21 Time 10:23 Sent To E
Notes
2007-11-21 10:23:40TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-31 Cont ID  
Sent By adarroug Date 2007-10-31 Time 16:51 Rev Time 0.00
Received By adarroug Date 2007-10-31 Time 16:51 Sent To E
Notes
2007-10-31 16:52:49TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-05-09 Cont ID  
Sent By shill Date 2007-05-09 Time 16:37 Rev Time 0.00
Received By shill Date 2007-05-09 Time 16:37 Sent To E
Notes
2007-05-09 16:37:56TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 11:03 Rev Time 0.00
Received By shill Date 2007-05-03 Time 11:03 Sent To Z
Notes
2007-05-03 11:04:08TO "Z" BOX/RESUB--NEW SHEETS FOR "Z" AND "P"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 08:09 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 08:09 Sent To E
Notes
2007-03-22 08:09:36TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-15 Cont ID  
Sent By adarroug Date 2007-03-15 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-03-15 Time 11:53 Sent To Z
Notes
2007-03-15 11:54:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-28 Cont ID  
Sent By adarroug Date 2006-12-28 Time 11:10 Rev Time 0.00
Received By adarroug Date 2006-12-28 Time 11:10 Sent To E
Notes
2006-12-28 11:11:01TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-30 Cont ID  
Sent By rmcdouga Date 2007-01-30 Time 12:00 Rev Time 0.00
Received By rmcdouga Date 2006-12-18 Time 11:38 Sent To  
Notes
2006-12-18 11:38:26TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-01-02 Cont ID  
Sent By tgordon Date 2007-01-02 Time 09:39 Rev Time 0.15
Received By tgordon Date 2007-01-02 Time 09:39 Sent To P
Notes
2007-01-02 09:40:40NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 4 Status N Date 2007-11-16 Cont ID  
Sent By jleech Date 2007-11-16 Time 09:56 Rev Time 0.00
Received By jleech Date 2007-11-16 Time 09:56 Sent To  
Notes
2007-11-16 09:57:39PLUMBING SCOUP OF WORK WAS DELETED FROM PLANS

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-05-16 Cont ID  
Sent By jleech Date 2007-05-16 Time 09:18 Rev Time 0.00
Received By jleech Date 2007-05-16 Time 09:18 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-03-27 Cont ID  
Sent By jleech Date 2007-03-27 Time 07:25 Rev Time 0.00
Received By jleech Date 2007-03-27 Time 07:25 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-01-06 Cont ID  
Sent By jleech Date 2007-01-06 Time 12:02 Rev Time 0.00
Received By jleech Date 2007-01-06 Time 12:02 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2007-05-07 Cont ID  
Sent By adavila Date 2007-05-07 Time 15:36 Rev Time 0.00
Received By adavila Date 2007-05-04 Time 15:36 Sent To I
Notes
2007-05-07 15:36:38PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-03-21 Cont ID  
Sent By adavila Date 2007-03-21 Time 08:59 Rev Time 0.00
Received By adavila Date 2007-03-21 Time 08:44 Sent To I
Notes
2007-03-21 09:00:06PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-27 Cont ID  
Sent By mmclean Date 2006-12-27 Time 07:59 Rev Time 0.00
Received By mmclean Date 2006-12-27 Time 07:59 Sent To I
Notes
2006-12-27 08:01:52DENIED,
 1. THE SURVEYS SUBMITTED DOES NOT PROVIDE THE SIDE
 SETBACK.
 2. PLEASE MARK ON THE TWO COPIES OF SURVEYS THE
 DISTANCE OF THE NEW ADDITION FROM SIDE PROPERTY LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN