| Plan Review Stops For Permit 06120458 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2006-12-26 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-12-26 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-12-26 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2006-12-26 15:05:21 | ***APPROVED*** | | | | | | 1) IN ADDITION TO ELECTRONIC SUPERVISION, DOUBLE CHECK | | | DETECTOR ASSEMBLY TO BE SECURED WITH CHAIN AND LOCK. | | | | | | 2) FIRE HYDRANT SHALL BE LOCATED NOT FURTHER THAN 150' | | | FROM FIRE DEPARTMENT CONNECTION. | | | | | | 3) SYSTEM SHALL BE HYDROSTATICALLY TESTED AT 200 LBS | | | FOR (2) HOURS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | (561) 805-6722 OR 804-4756 |
|
|