| 2007-01-05 14:16:27 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SUBMITTED SHEETS A0, A3, AND A4 ARE UNACCEPTABLE DUE |
| | TO THE FACT SHEETS ARE NOT SIGNED AND SEALED. |
| | FAC-CODE-61G1-16001 ARCHITECT'S AND |
| | INTERIOR DESIGNER'S SEAL: |
| | EACH ARCHITECT AND INTERIOR DESIGNER |
| | SHALL ACQUIRE A SEAL WITH WHICH HE OR |
| | SHE SHALL IDENTIFY ALL PLANS, |
| | SPECIFICATIONS OR REPORTS PREPARED OR |
| | ISSUED BY HIM OR HER AND FILED FOR |
| | PUBLIC RECORD. THE SEAL SHALL BE OF A |
| | TYPE WHICH WILL MAKE AN IMPRESSION ON |
| | THE SURFACE OF PRINTS OR OTHER |
| | DUPLICATIONS OF DRAWINGS, AND AS |
| | APPROPRIATE, UPON SPECIFICATION PAGES, |
| | AND OTHER ARTICLES OF SERVICE. |
| | NOTE:ON THE RESUBMITTAL JUST REFERENCE THE MASTER |
| | PERMIT #05100303 AND DELETE RESUBMITTING SHEETS A0, A3, |
| | AND A4. |
| | |
| | 2. THE SUBMITTED GAS RISER DIAGRAM DOES NOT RELECT THE |
| | APPROVED SIGED AND SEALED PRINTS OF MASTER PERMIT |
| | #05100303. THE 2ND FLOOR TANKLESS WATER HEATER IN THE |
| | LAUNDRY ROOM IS MISSING FROM THE GAS RISER DIAGRAM. DUE |
| | TO THE INCREASE BTU LOAD GAS PIPING TO THAT AREA NEEDS |
| | TO BE INCEASED TO 1" ON THE RESUBMITTAL. ON YOUR |
| | SUBMITTED ARCH. DRAWINGS THERE IS A HAND WRITTEN CHANGE |
| | IN THE GENERATOR LOCATION THAT IS DIFFERENT THAN THE |
| | SIGNED AND SEALED MASTER PERMIT #05100303. IF IT IS THE |
| | INTENT TO CHANGE THE LOCATION OF THE GENERATOR THE |
| | ARCHITECT OF RECORD NEEDS TO MAKE SAID CHANGES WITH A |
| | REVISION. |
| | |
| | 3. ON THE RESUBMITTAL PLEASE INDICATE ALL PIPING |
| | MATERIALS. |
| | |
| | 4. PLEASE SUBMIT MANUFACTURER CUT SHEETS OF THE MP |
| | REGULATORS (2PSI TO 0.5PSI REG.) |
| | |
| | 5. THE VALUE OF THIS JOB SEEMS LOW PLEASE PROVIDE COPY |
| | OF SIGNED CONTRACT WITH VALUE ATTACHED INCLUDING MP |
| | REGULATORS. |
| | PER FBC-2004, CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | |
| | **********IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |