Plan Review Details - Permit 06120408
Plan Review Stops For Permit 06120408
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-22 Cont ID  
Sent By shill Date 2007-02-22 Time 18:52 Rev Time 0.00
Received By shill Date 2007-02-22 Time 18:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-02 Cont ID  
Sent By shill Date 2007-02-02 Time 12:17 Rev Time 0.00
Received By shill Date 2007-02-02 Time 12:17 Sent To  
Notes
2007-02-02 12:18:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)THE APPLICATION AND PRODUCT APPROVALS ARE NOT IN
 THE RESUBMITTAL.PLEASE PROVIDE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-26 Cont ID  
Sent By shill Date 2007-01-26 Time 07:38 Rev Time 0.00
Received By shill Date 2007-01-26 Time 07:38 Sent To  
Notes
2007-01-26 07:40:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED,
 FS713.13.
  
 ____2.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY
 AN ENGINEER. DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.AN INSTALLATION SCHEDULE WAS SUBMITTED
 BUT AS MANY ITEMS ARE MISSING (INCLUDING ANCHOR SPACING
 FOR OPENINGS 1 THROUGH 5) CODE COMPLIANCE CANNOT BE
 DETERMINED.PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
 PLEASE SEE THE ANCHOR SCHEDULE ON THE PRODUCT APPROVAL.
 IF THE 13INCH SPACING WAS COMPLIANT FOR ALL CONNECTION
 TYPES, THIS WOULD HAVE BEEN ACCEPTABLE.HOWEVER, IT IS
 NOT COMPLIANT FOR SOME CONNECTION TYPES AND CONNECTION
 TYPE WAS NOT CIRCLED OR SPECIFIED ON THE ANCHOR
 SCHEDULE.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 ____8.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 4
 ABOVE.
  
 ____9.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2).
 NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED
 EFFECTIVE DECEMBER 8, 2006 FBC1609.4.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-16 Cont ID  
Sent By adarroug Date 2007-02-16 Time 08:55 Rev Time 0.00
Received By adarroug Date 2007-02-16 Time 08:55 Sent To B
Notes
2007-02-16 08:55:31TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 10:56 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 10:56 Sent To B
Notes
2007-02-02 10:56:27TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-26 Cont ID  
Sent By shill Date 2007-01-26 Time 07:40 Rev Time 0.00
Received By shill Date 2006-12-17 Time 13:45 Sent To  
Notes
2006-12-17 13:45:33TO "MISC" BOX#1