Plan Review Details - Permit 06120405
Plan Review Stops For Permit 06120405
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-29 Cont ID  
Sent By adarroug Date 2007-01-29 Time 11:04 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 11:04 Sent To M
Notes
2007-01-29 11:05:07TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-18 Cont ID  
Sent By tgordon Date 2006-12-18 Time 14:55 Rev Time 0.00
Received By tgordon Date 2006-12-17 Time 13:26 Sent To  
Notes
2006-12-17 13:26:20TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-01 Cont ID  
Sent By tgordon Date 2007-02-01 Time 12:21 Rev Time 0.45
Received By tgordon Date 2007-02-01 Time 12:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-18 Cont ID  
Sent By tgordon Date 2006-12-18 Time 14:42 Rev Time 0.45
Received By tgordon Date 2006-12-18 Time 14:42 Sent To  
Notes
2006-12-18 14:54:59*** DENIED ***
 1) VALUE ON PERMIT APPLICATION MUST INCLUDE ALL
 MATERIALS AND LABOR, PLEASE CORRECT VALUE OR WE WILL
 NEED TO ADJUST IT USING MARSHALL & SWIFT BUILDING COST
 REPORT, PER 2004 FBC WPB AMEND. 108.3.
  
 2) PLEASE SUBMIT TWO COPY'S OF PLANS, ONLY ONE WAS
 SUBMITTED.
  
 3) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR ROOF
 TOP CONDENSER STANDS.
  
 4) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-600.1.C.2.
  
 5) NEED TO FILE A NOTICE OF COMMENCEMENT, PER F. S.
 713.13 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.