Plan Review Details - Permit 06120388
Plan Review Stops For Permit 06120388
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-05-02 Cont ID  
Sent By jwitmer Date 2007-05-02 Time 08:46 Rev Time 1.33
Received By jwitmer Date 2007-05-02 Time 07:50 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-02-09 Cont ID  
Sent By jwitmer Date 2007-02-09 Time 07:39 Rev Time 0.77
Received By jwitmer Date 2007-02-09 Time 07:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-09 Cont ID  
Sent By jwitmer Date 2007-01-09 Time 07:07 Rev Time 1.33
Received By jwitmer Date 2007-01-09 Time 06:58 Sent To  
Notes
2007-01-09 07:59:20BUILDING PLAN REVIEW
 PERMIT: 06120388
 ADD: 440 COLUMBIA DR SUITE 500
  
 CONT: SISCA CONST
 TEL: (561)228-7517
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3A) SHEET D-1 INDICATES WORK TO BE COMPLETED IN
 THE EXISTING MENS AND WOMENS RESTROOM AND
 EXISTING CLOSET (111).
 THE DOORS TO THE EXISTING RESTROOM SWING IN TO
 THE CLEAR FLOOR SPACE REQUIRED FOR FIXTURES.
 11-4.22.2 DOORS. ALL DOORS TO
 ACCESSIBLE TOLIET ROOMS SHALL COMPLY
 WITH 11-4.13. DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
  
 3B) SHEET D-1CLOSET (111)INDICATES DOOR AND
 FRAME TO BE REMOVED:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 4) SHEET E1.1 DOESN'T INDICATE ANY EXIT LIGHTS,
 PLANS DO INDICATE DIRECTIONALS. 1006.3.1 EXITS
 SHALL BE MARKED BY AN APPROVED SIGN READILY
 VISIBLE FROM ANY DIRECTION OF RXIT ACCESS. EVERY
 EXIT SIGN SHALL BE SUITABLY ILLUMINATED BY A RELIABLE
 LIGHT SOURCE. EXTERNALLY AND INTERNALLY ILLUMINATED
 SIGNS SHALL BE VISIBLE IN BOTH NORMAL AND EMERGENCY
 LIGHTING.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-04-10 Cont ID  
Sent By btrobaug Date 2007-04-10 Time 15:18 Rev Time 1.00
Received By btrobaug Date 2007-04-10 Time 12:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-02-08 Cont ID  
Sent By btrobaug Date 2007-02-08 Time 16:04 Rev Time 1.00
Received By btrobaug Date 2007-02-08 Time 14:29 Sent To  
Notes
2007-02-08 16:04:12 
  
  
 REDLINED EMERGENCY LIGHT CIRCUITS, NUMBERED
 WRONG ON PLAN.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-09 Cont ID  
Sent By btrobaug Date 2007-01-09 Time 12:43 Rev Time 1.00
Received By btrobaug Date 2007-01-09 Time 10:32 Sent To  
Notes
2007-01-09 12:43:25 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 611 EXISTING BUILDING CODE, INDICATE COMPLIANCE
 WITH CHAPTER 13-101.1.3. SUBMIT PROPER FORMS FOR
 REVIEW.
  
 2} LOCATE THE CLOCKS ,SENSORS AND TIMERS ON THE PLAN.
 13-415.
  
 3} INDICATE FIXTURE TYPES THAT COMPLY WITH 13-415.
  
 4} THE "NEW PANEL " FEED ON SHEET E5.1 MUST INCLUDE
 CONDUCTOR NUMBER A, SIZES AND OVERCURRENT PROTECTION
 RATING STATED ON THE RISER DIAGRAM. SHOW EQUIPMENT
 GROUND SIZE AS WELL.
  
 5} THE EMERGENCY LIGHTS MUST COMPLY WITH 700.12(F)(4).
 IDENTIFY THE CIRCUIT NUMBER ON THE PLANS (SHEET E1.1),
 SO THE CONNECTING CIRCUIT WILL BE CLEAR IN THE FIELD.
  
 6} CIRCUIT THE EXIT LIGHTS ON SHEET E1.1. SHOW ON
 SCHEDULE.
  
 7} SHEET E0.1, NOTE 57 SHOULD INCLUDE EDITION(S) BEING
 REFERENCED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-06 Cont ID  
Sent By mwennerg Date 2007-04-06 Time 13:36 Rev Time 0.00
Received By mwennerg Date 2007-04-06 Time 13:36 Sent To  
Notes
2007-04-06 13:36:36REVISION DATED 3/3/07

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-02-12 Cont ID  
Sent By mawillia Date 2007-02-12 Time 12:10 Rev Time 0.00
Received By mawillia Date 2007-02-12 Time 12:09 Sent To  
Notes
2007-02-12 12:17:18*****APPROVED*****
  
  
 THE FIRE PLAN REVIEW COMMENTS OF 01/18/2007 HAVE BEEN
 ADDRESSED.SHEET E1.1 HAS BEEN STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-18 Cont ID  
Sent By mawillia Date 2007-01-18 Time 12:40 Rev Time 0.00
Received By mawillia Date 2007-01-18 Time 11:59 Sent To  
Notes
2007-01-18 13:07:24*****DENIED******
  
  
 1.ON SHEET D-1, DEMOLITION NOTE #10, ADD THE WORD
 "EXIT" BETWEEN REQUIRED ---- COMPONENTS.
  
 2.WHAT WILL BE THE INTERIOR FINISH CLASSIFICATION FOR
 THE WALLS SND CEILINGS IN THE EXITS, EXIT ACCESS
 CORRIDORS, AND IN ALL OTHER AREAS?
  
 3.ON SHEET M7.1, IT IS NOTED THATDUCT MOUNTED SMOKE
 DETECTOR EQUIPMENT WILL BE INSTALLED. IF THIS BUILDING
 IS NOT TIED INTO A FIRE ALARM SYSTEM, HOW WILL ALERT
 NOTIFICATION BE ACCOMPLISHED?
  
 4.ON SHEET E1.1, AN ADDITIONAL EXIT LIGHT (AS
 RED-LINED) IS NEEDED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED IN THE PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 11:53 Sent To M
Notes
2007-06-20 11:53:38TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-04 Cont ID  
Sent By spalmer Date 2007-04-04 Time 17:56 Rev Time 0.00
Received By spalmer Date 2007-04-04 Time 17:56 Sent To  
Notes
2007-04-04 17:56:47TO BOB # 11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-06 Cont ID  
Sent By adarroug Date 2007-02-06 Time 15:14 Rev Time 0.00
Received By adarroug Date 2007-02-06 Time 15:14 Sent To  
Notes
2007-02-06 15:15:01TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-18 Cont ID  
Sent By mawillia Date 2007-01-18 Time 11:58 Rev Time 0.00
Received By mawillia Date 2006-12-19 Time 11:42 Sent To  
Notes
2007-01-05 19:20:082007-01-05 19:20:08
 TO BOB BOARD SPACE #10 1/5
2006-12-19 11:42:34WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-06-20 Cont ID  
Sent By tgordon Date 2007-06-20 Time 16:35 Rev Time 0.30
Received By tgordon Date 2007-06-20 Time 16:35 Sent To  
Notes
2007-06-20 16:36:45REVISION TO MECH. PLANS PAGE M1.1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-04-05 Cont ID  
Sent By tgordon Date 2007-04-05 Time 11:34 Rev Time 0.30
Received By tgordon Date 2007-04-05 Time 11:34 Sent To  
Notes
2007-04-05 11:36:46REVISION TO MECH. PLANS PAGES M1.1 AND M8.1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-09 Cont ID  
Sent By tgordon Date 2007-02-09 Time 11:52 Rev Time 0.25
Received By tgordon Date 2007-02-09 Time 11:52 Sent To  
Notes
2007-02-09 11:52:57RESUB

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-01-09 Cont ID  
Sent By tgordon Date 2007-01-09 Time 16:09 Rev Time 0.30
Received By tgordon Date 2007-01-09 Time 16:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-02-12 Cont ID  
Sent By jleech Date 2007-02-12 Time 08:46 Rev Time 0.00
Received By jleech Date 2007-02-12 Time 08:46 Sent To  
Notes
2007-02-12 08:48:40PROVISO;
  
 PLUMBING DEMO TO BE DONE BY A LICENSED PLUMBING
 CONTRACTOR, PERMIT REQUIRED.