Plan Review Details - Permit 06120362
Plan Review Stops For Permit 06120362
Review Stop AD ADDRESSING
Rev No 3 Status F Date 2007-08-15 Cont ID  
Sent By lursu Date 2007-08-15 Time 15:39 Rev Time 0.00
Received By lursu Date 2007-08-15 Time 15:39 Sent To  
Notes
2007-08-15 15:43:09PREVIOUS COMMENTS DATED JAN3,2007 ARE STILL VALID FOR
 THIS PERMIT.AS SOON AS THE UOT IS RECORDED AND A NEW
 PCN IS ISSUED BY THE PROPERTY APPRAISER'S OFFICE THAN A
 NEW SITE ADDRESS WILL BE APPROVED BY THE CITY FOR THE
 NEW UNIT.IF THE MAIN ENTRANCE OF THE NEW UNIT IS FROM
 THE 7TH FLOOR THAN THE EXISTING ADDRESS OF THAT UNIT
 WILL APPLY TO THE NEW UNIT.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL.
  
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:LURSU@

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-01-03 Cont ID  
Sent By lursu Date 2007-01-03 Time 11:09 Rev Time 0.00
Received By lursu Date 2007-01-03 Time 11:09 Sent To  
Notes
2007-01-03 11:10:53IF WORK INVOLVES THE COMBINATION OF TWO UNITS FROM THE
 7TH FLOOR WITH THE UNIT FROM THE 8 TH FL A UNITY OF
 TITLE IS NECESSARY FOR THESE TWO UNITS .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-12-14 Cont ID  
Sent By lursu Date 2006-12-14 Time 08:54 Rev Time 0.00
Received By lursu Date 2006-12-13 Time 12:05 Sent To PC
Notes
2006-12-14 08:56:33CORRECT ADDRESSS IS 120 S OLIVE AVE WITHPCN =
 7443432240 ( CONDO PCN) INSTEAD OF 74434322400001010.
 APLICATION MUST BE CORRECTED.
 ATTACH PERMIT TO UNIT 0001 FOR FLOOR 7TH UNDER PCN =
 7443432240.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]
2006-12-13 12:06:40PCN # AND OWNER INFO IN OUR SYSTEM DOES NOT MATCH WHAT
 PERMIT & PAPA HAS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-28 Cont ID  
Sent By jjohnsto Date 2007-08-28 Time 13:50 Rev Time 6.00
Received By jjohnsto Date 2007-08-28 Time 13:50 Sent To  
Notes
2007-08-28 13:54:21CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
  
 PERMIT NO. 06120362
 PROJECT NAME THE GUARANTY BUILDING
 ADDRESS 120 SOUTH OLIVE AVENUE
 CONTRACTOR: L. DAVIS CONSTRUCTION, INC.
  DATE: AUGUST28,2007
  
 PLANREVIEW
 JAMES JOHNSTON CBO
 BUILDING PLANS EXAMINER LL
 TEL:561-805-6713FAX:
 561-805-6731
 [email protected]
  
  
 (1) SUBMITTING PLAN CORRECTIONS:
 WHEN RE-SUBMITTING PLANS WITH CORRECTIONS PLEASE
 PROCEED AS FOLLOWS:
  A.INDICATE THE CORRECTED ITEMS BY CLOUDING ON THE
 NEW CORRECTED SHEET
  B.REMOVE THE OLD SHEET FROM THE PLAN AND INSERT
 THE NEWLY CORRECTED SHEET
  C.PUT OLD THE OLD SHEETS TOGETHER AS ONE SET AND
 SUBMIT TO THE BUILDING DEPT. ALONG
 WITH THE NEW CORRECTED PLANS. THIS IS NECESSARY
 FOR THE PLAN REVIEWER TO CRITIQUE
 THE CORRECTION REQUIRED FROM THE PREVIOUS PLAN
 REVIEW.
 D.SUBMIT A COVER LETTER IDENTIFYING THE CORRECTION
 MADE LISTING THE ITEM REFERENCED
 IN THE REVIEWER?S COMMENTS.
  
 (2) ADDRESS CHANGE:
  THE CORRECT ADDRESS OF THE PROPERTY IS ON THE
 ARCHITECTURAL SHEETS BUT, NOT ON THE
 ENGINEERING SHEETS. PLEASE NOTIFY THE ENGINEER TO MAKE
 THE REQUIRED CHANGE.
  
  THE PROPERTY CONTROL NUMBERS ON RECORD FOR THIS
 BUILDINGAT THE PALM BEACH COUNTY
 PROPERTY APPRAISAL?S OFFICE DO NOT HAVE A CONTROL
 NUMBER LISTED FOR THE EIGHTH FLOOR.
 THE NUMBERS STOP AT THE SEVENTH FLOOR.THEY ARE GOING
 TO ASSIGN A SEVENTH FLOOR NUMBER
 TO THE EIGHTH FLOOR.
 INCLUDED ARE THE FOLLOWING NUMBERS ASSIGNED TO GUARANTY
 NCP, LLC, THAT WILL BE SUITABLE TO INCLUDE THE EIGHTH
 FLOOR. PLEASE SELECT ONE.
 PROPERTY CONTROL NUMBERS THAT END IN:701,702,703,
 705
 CORRECT PERMIT APPLICATION TO REFLECT THE CONTROL
 NUMBER SELECTED.
  
 (3) PROJECT REQUIRED INFORMATION:
  THE COVER SHEET CS-1IN THE BLOCK TITLED ?SPECIFIC
 PROJECT REQUIREMENTS?.
  AND SHEET S-2STRUCTURAL NOTES
 PLEASE CORRECT /ADD THE INFORMATION LISTED HERE-IN.
  
 CODE:FBC2004 WITH 2006 SUPPLEMENTS AND FLORIDA
 BUILDING CODE 2004,FBC 2004
 EXISTING BUILDINGS AND HISTORIC BUILDINGS
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE CHAPTER 1,2004
 ALTERATION:LEVEL III
 INTERIOR RENOVATION OF THE SEVENTH AND EIGHTH FLOOR
 WITH ELEVATOR AND STAIRWAY
 CONSTRUCTION TYPE:I-B
 FBC TABLE 503NOTE: YOU CANNOT US E II-B BECAUSE IT IS
 ONLY GOOD FOR FOUR STORIES
  FIRE RATING FOR FRAMING MEMBERS
  
  
  
 (4) A. ALL FRAMING MEMBERS MUST BE TWO HOUR FIRE RATED
 BUT, BECAUSE OF THE FIRE SPRINKLER
 SYSTEM, YOU CAN REDUCE THE RATING BY ONE HOUR.
  
  B. PROVIDE A FIRE SPRINKLER PLAN OF THE HEADS AT THE
 SEVENTHFLOOR ALTERATION AREA.
  
  C. ADD TO PLAN ?8TH FLOOR COMPLETE ALTERATION WITH
 CHANGE OF OCCUPANCY FROM STORAGE TO
  BUSINESS?
  SUBMIT A PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION FOR THE EIGHTH FLOOR IMPACT FEES
  THAT WILL BE DUE WITH THIS CHANGE OF OCCUPANCY AND
 ALTERATION.
  PROPERTY APPRAISER?S OFFICE TEL:561-233-5025 FOR
 INFORMATION.
  
  D. PLEASE NOTE: FLORIDA STATUTE399 ?CHANGE OF
 OCCUPANCY? FOR THE EIGHTH FLOOR.
  
  WINDOW AND DOOR ANCHORAGE
 (7) A. PROVIDE DOOR /JAMB / HEADER DETAIL FOR FASTENING
 TO POURED CELLS.
  
  STAIRS
 (8) FBC 1009.3STAIR RISER MINIMUM 7?.SEE PLAN
 SHEET A-4 DETAIL 4 CHANGE RISER HEIGHT
  
  WIND LOADS
 (11) FBC1609.1THE BUILDING IS MORE THAN 60 FEET
 TO THE MEAN ROOF HEIGHT (SEE SURVEY).
  PLEASE FURNISHTHE WIND LOADS ON THE ROOFPER THIS
 SECTION.CHANGE BUILDING HEIGHT
  ON SHEET S-2 BUILDING DETAIL AND NOTES BELOW ?WIND
 LOAD SCHEDULE? THAT STATE 2001
  FLORIDA BUILDING CODE.SEE TABLE 1609.6.2.1(1). ALSO
 ASCE 7 2002 SHOULD BE USED AS A
 DESIGN.
 PLEASE SEE THE ATTACHED (2) COPIES MEMO FROM THE
 BUILDING OFFICIAL FOR WIND BORN
 DEBRIS / IMPACT PROTECTION FOR ARCHITECT / ENGINEER?S
 USE.
  
  PRODUCT APPROVALS
 (12) PRODUCT APPROVALS ARE REQUIRED FOR WINDOWS /
 DOORS/MULLIONS/ROOFING ASSEMBLIES
  WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE
 9B-72
  SUBMIT TWO COPIES OF EACH APPROVAL WITH THE
 ARCHITECT?S AND ENGINEER?S SIGNATURE
 STATING ?TO THE BEST OF THEIR KNOWLEDGE THE PRODUCT
 APPROVAL COMPLIES WITH THE PLANS
 AND SPECIFICATIONS.SEE WEB SITEWWW.FLORIDABUILDING
  
 (16) FIRE SAFETY STANDARDS
 WPB ADMINISTRATIVE CODE 105.13.4.4
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT AND ENGINEER OF
 RECORD SHALL STATE THE FOLLOWING? TO THE BEST OF THE
 ARCHITECT AND ENGINEERS KNOWLEDGE THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND FLORIDA STATUE 633.
  
 (17) SPECIAL INSPECTOR
 WPB AMENDMENT105.13.6REQUEST FOR A SPECIAL
 INSPECTOR AS REQUIRED BY FLORIDA STATUE
  553.79(5)TO THE MINIMUMINSPECTIONS REQUIRED BY
 THIS CODE. CONTACT HAROLD PISKURA,
  MANAGER OF THE SPECIAL INSPECTOR?S PROGRAM
 (561)-805-6711 BEFORE THE PERMIT MAY BE ISSUED.
  
 (18) LOOSE MATERIAL DURING A HURRICANE
  FBC109.3.10WHEN A HURRICANE WATCH HAS BEEN
 ISSUED, ALL LOOSE CONSTRUCTION MATERIAL
  AND EQUIPMENT MUST BE SECURED FOR 24 HOURS OR UNTIL
 THE WATCH HAS BEEN LIFTED.
  
 (19) PROVIDE SPECIFICATIONS FOR HILTIPRODUCT HIT-HY
 20330 ML/1
  PIN INFORMATION AS TO:
  SIZE,TYPE,LENGTH,CHEMICAL COMPOUND,SLEEVE
  
 (20) FBC707.4DOES ELEVATOR GO TO TOP FLOOR AND IS
 THE SHAFT RATED TWO HOUR?PLEASE STATE ON PLAN
  
 (21) IDENTIFY THE SUPPORTING COLUMN LOCATIONS ON THE
 SEVENTH FLOOR THAT ASSUME THE LOAD OF
  THE STEEL TUBE COLUMNS ON THE EIGHTH FLOOR.
  
 (22) PROVIDE THICKNESS OF FLOOR SLAB ON ENGINEERING
 PLAN
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-23 Cont ID  
Sent By jwitmer Date 2007-08-28 Time 14:00 Rev Time 6.00
Received By jwitmer Date 2007-08-28 Time 08:00 Sent To E
Notes
2007-02-23 12:19:44BUILDING PLAN REVIEW
 PERMIT: 06120362
 ADDRESS: 206 S OLIVE/ 120 S OLIVE
 CONT: L. DAVIS
 TEL: (561)718-8161
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) DESCREPANCY PLEASE CORRECT THE ADDRESS OF THE
 JOBSITE,SEE PERMIT APPLICATION VS PLANS.
 106.1.2*ADDITIONAL INFORMATION REQUIRED.
 2A) THIS SITE APPEARS TO BE A OFFICE CONDOMINIUM
 SITE.THE APPLICATION INDICATES A UNIT ON THE FIRST
 FLOOR BY THE PCN USED.
 2B) THE PLANS INDICATE WORK ON THE 7TH AND 8TH FLOOR
 WHERE AS THE PALM BEACH COUNTY PROPERTY APPRAISERS
 OFFICE DOES NOT REFLECT ANY PROPERTY CONTROL NUMBERS ON
 THE 8TH FLOOR. IF THESE NEW STAIRS ARE GOING TO THE 8TH
 FLOOR THIS SQUARE FOOTAGE ON THE EIGTH FLOOR WOULD HAVE
 A SEPERATE PROPERTY CONTROL NUMBER UNLESS THIS IS
 CONSIDERD COMMON AREAS TO ALL TENANTS, SUCH AS
 RESTROOMS AND OR AN ASSOCATION OWNED SUITE OR OFFICE.
 PLEASE PROVIDE DOCUMENTATION OF OWNERSHIP.
 A UNITY OF TITLE MAY BE REQUIRED.
  
 3) THE COVERSHEET, LS-1 NOR THE STRUCTURAL SHEETS
 PROVIDE THE FOLLOWING INFORMATION:
 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WILL BE ISSUED.
 PLEASE PROVIDE THE LEVEL OF ALTERATION LISTED UNDER
 THE 2004 EXISTING BUILDING CODE.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) SQ. FT. 8TH FLOOR BEING REBUILT
 H) SQ. FT. FOOTPRINT BUILDING
 I ) SQ. FT. UNDER ROOF (TOTAL)
  
 4) THE PLANS APPEAR TO INCORPORATE A LARGER SCOPE OF
 WORK THAN LISTED ON THE DESCRIPTION OF WORK LISTED IN
 THE PERMIT APPLICATION.
 IT APPEARS THE 8TH FLOOR IS BEING REBUILT. WITH THE
 STEEL COLUMNS AND FRAMING SHOWN ON S-2 IF SO PLEASE
 INDICATE ON THE PERMIT APPLICATION DESCRIPTION OF
 PROJECT.
  
 5) NOTE: WITH THE ANSWER TO 3B USE AND OCCUPANCY NOT
 KNOWN THIS REVIEW WILL BE ASSUMING THIS TO BE A
 BUSINESS OCCUPNCY FOR THE PARAMETERS OF THIS REVIEW.
  
 6)IN AS SUCH THE REVIEW AND INSPECTION AND ISSUANCE
 OF THE CERTIFICAT OF OPERATION WILL BE ISSUED BY THE
 DEPARTMENT WHICH INDICATES THAT THE CONVEYANCE HAS HAD
 THE REQUIRED SAFETY INSPECTION AND TEST AND THE FEES
 HAVE BEEN PAID AS PROVIDED IN THIS CHAPTER 399 FS.
  
 7A) IT APPEARS THE EXTERIOR WALLS ARE TERRA-COTTA AND A
 NEW STEEL INNER FRAME-WORK IS BEING ADDED. SHEE A-4
 INDICATES A WINDOW INSTALLATION WITH BUCK BUT THIS
 DETAIL
 IF TAKEN LITTERALY MEANS THAT THE WINDOW AND BUCK WILL
 BE ATTACHED TO THE TERRA-COTTA WALL AND NOT THE
 STRUCTURAL STEEL FRAME WORK.
  
 7B)IF THE WINDOW DETAIL IS REVISED TO BE SECURED TO
 THE STRUCTURAL STEEL FRAMEWORK PLEASE PROVIDE WHAT WILL
 SEAL WEATHER FROM THE JOINT BETWEEN THE TERRA-COTTA AND
 THE
 STEEL FRAME?
  
 7C) SHEET A-4 WINDOW DETAIL INDICATES A WOOD BUCKPLEASE
 SEE COMPLIANCE COMMENTS,1714.5.4.2 MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1 1
 / 2 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER'S
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
  
 8)SHEET A-4 STAIR DETAIL, INDICATES THE RISERS TO BE
 7.5" AND THE TTREADS TO BE 10". 1009.3 STAIR TREADS AND
 RISERS. STAIR RISER HEIGHTS SHALL BE 7 INCHES (178 MM)
 MAXIMUM AND 4 INCHES (102 MM) MINIMUM. STAIR TREAD
 DEPTHS SHALL BE 11 INCHES (279 MM) MINIMUM.
  
 9) SHEET A-5 HANDRAIL DETAIL# 6, INDICATES 2" BETWEEN
 THE HANDRAIL AND WALL.11-4.9.4(3) THE CLEAR SPACE
 BETWEEN HANDRAILS AND THE WALL SHALL BE 1 1/2".
  
 10) SHEET A-5 WHITE-OUT ON DETAIL "A" - R-19
 104.2.1.3 THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO WHITE OUT".
  
 11)1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 12)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 14)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) GLAZED WINDOWS
 B) GLAZED DOORS
 C) HOLLOW METAL DOORS
 D) MULLIONS
 E) ROOFING ASSEMBLIES
  
 15)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 16)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 17)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 18) BUILDING PROVISO:
 ) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-31 Cont ID  
Sent By dpalmer Date 2007-07-31 Time 20:21 Rev Time 0.00
Received By dpalmer Date 2007-07-31 Time 18:44 Sent To  
Notes
2007-07-31 20:22:02** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS DUE TO
 INFORMATION NOW SUBMITTED OR CHANGES MADE TO PLANS.
  
  
 1) NOTE: PLEASE SEE THAT THIS BUILDING IS STILL IN
 QUESTION FOR THE SERVICE, METERING, ADDRESSING ETC.
 AT THIS TIME AS THIS HAS BEEN CHANGE TO A *CONDO* THIS
 WOULD APPEAR TO BE A CHANGE IN OCCUPANCY WHICH WOULD
 NOT ONLY REQUIRE A PERMIT FOR THE CHANGE IN OCCUPANCY
 IT WOULD ALSO REQUIRE BUILDING ELECTRICAL SYSTEMS TO BE
 BROUGHT UP TO CODE FOR COMPLETE ELECTRICAL CODE
 COMPLIANCE UNDER THE CURRENT CODES AND STANDARDS.
 THIS WOULD INCLUDE ELECTRICAL, FIRE SYSTEMS, FLORIDA
 BUILDING CODE AND OTHER TRADES. THIS INFORMATION IS
 CURRENTLY BEING CONFIRMED.
 PLEASE SEE FBC FOR CHANGES IN OCCUPANCY.
 FBC 106.1, CHAPTER 13, CHAPTER 27 ETC.
  
 2) NOTE: PLEASE SEE SOME SUPPORTING DOCUMENTATION STILL
 CONTAINS AN ADDRESS OF 106 S OLIVE.
 PLEASE KNOW AS THE COMMENT ABOVE STATES THE ADDRESS,
 THE BUILDING AND USE WILL NEED TO BE VERIFIED.
 FAC 61G15-23, 61G1-16
  
 3) NOTE: PLEASE KNOW AS THE PREVIOUS REVIEW CONTAINED
 NOTES FOR SPECIFIC CODES, THIS COMMENT WILL REMAIN OPEN
 UNTIL CHANGE IN OCCUPANCY IS CLARIFIED.
  
 4) NOTE:PLEASE CLARIFY IF THERE IS AN EQUIPMENT ROOM
 FOR ELEVATOR EQUIPMENT. PLEASE ALSO SEE 620.22, 23 AND
 24. RESPONSE MENTIONS THIS IS A LULA UNIT? PLEASE
 SUBMIT MANUFACTURES SPECS/CUT SHEETS ON THIS UNIT WHICH
 CONTAINS THIS INFORMATION. 110.3,90.7
 IF THERE IS AN EQUIPMENT ROOM AND EMERGENCY BATTERY
 BACK UP LIGHT OF SOME KIND WILL BE REQUIRED.
 LS 101 7.8, 700.16 ETC
  
 5) NOTE:PLEASE SEE THE PREVIOUS REVIEW NOTES WITH
 RESPECT TO LIGHTING CONTROLS. PLEASE SEE THAT EACH
 FLOOR IS REQUIRED TO CONTAIN A SEPARATE SYSTEM.
 PLEASE SEE THE NOTES ON PLANS MENTIONS A *TIME CLOCK
 WILL OVER RIDE THE LCP FOR A TIME OF 10HRS*? PLEASE
 SPECIFY THE TIME SCHEDULING FOR THE LCP. PLEASE SEE THE
 RESPONSE LETTER APPEARS TO REFERENCE THE CORRECT TIMES,
 HOWEVER PLEASE EXPAND ON THE MAXIMUM PERMITTED OVER
 RIDE TIMES ON PLANS.
 PLEASE CLARIFY THE LIGHTING CONTROL PANELS AS PLANS
 SEEM TO SHOWN ONE BRAND AND RESPONSE LETTER MENTIONS A
 DIFFERENT PANEL.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE
 IF INSTALLING A SYSTEM TO SEE REQUIREMENTS FOR MULTIPLE
 FLOORS. PLEASE SEE THAT IF USING ALL OCCUPANCY SENSOR
 TYPE DEVICES PLEASE STATE THE MAXIMUM TIMES, OR MAXIMUM
 TIMES ON ANY OVER RIDE DEVICES.
 PLEASE SEE THAT THE ENERGY CALCULATIONS ARE THE SAME AS
 PREVIOUSLY SUBMITTED. PLEASE SEE THE VERSION OF THE
 CALCULATIONS IS NOT CORRECT. PLEASE KNOW THE VERSION AS
 SUBMITTED IS FROM THE PREVIOUS CODE CHANGE BEFORE THE
 REVISIONS DATED DECEMBER 8TH, 2006. PLEASE SEE THE
 LIGHTING CONTROL METHODS ARE STILL SHOWN AS *MANUAL
 ON/OFF* WHICH IS NOT POSSIBLE WHEN THE PLANS CONTAIN
 AUTOMATED MEANS.
 THIS INCLUDES RELOCATED LIGHTING WHICH MAY OR MAY NOT
 BE USED BASED ON WHETHER OR NOT THEY MEET THE NEW
 CODE(S).
 PLEASE SEE 13-415.1.AB.1, 13-415.1.A,13-415.2,AND
 13-415.2.ABC.1 AND TABLES FOR USE ETC.
  
 6) NOTE: PLEASE SEE THE PHOTO-METRICS AS SUBMITTED.
 PLEASE CLARIFY WHERE THE EMERGENCY LEVELS ARE SHOWN.
 BASED ON THE FIXTURES AS SHOWN THE LEVELS APPEAR TO
 MORE THAN ADEQUATE FOR EM LEVELS, HOWEVER PLEASE KNOW
 THE RECORD PLANS SHOULD STATE EACH AS REQUIRED PER FAC
 61G15-33.004 AND THE LS SECTIONS AS GIVEN ON PREVIOUS
 REVIEW.
 PLEASE SEE 7.8.1.3, AND 7.9.2.2 WHICH REQUIRES A
 MINIMUM OF 10FT CANDLES UNDER NORMAL AND 1FT CANDLE
 UNDER EMERGENCY.
 PLEASE SEE CONTROLS FOR LIGHTING SHALL ALSO BE
 INDICATED, AND ANY OVER RIDES DEVICES OR NIGHT LIGHTS.
  
 7) NOTE: PLEASE SHOW ALL EXISTING ELECTRICAL IN THE 7TH
 FLOOR AREA FOR ELECTRICAL. THIS WOULD INCLUDE POWER AND
 LIGHT EVEN IN ROOMS NO WORK IS BEING DONE.THE SCOPE
 OF WORK BASE DON THE EXISTING BUILDING CODE AND CHANGE
 IN OCCUPANCY REQUIRES ALL TO MEET CODE EVEN IF NOT
 DOING WORK IN A PARTICULAR ROOM(S) AS SHOWN ON THE 7TH
 FLOOR.
 PLEASE KNOW THE LIGHTING WILL BE REQUIRED TO MEET
 CHAPTER 13 OF THE FBC FOR CONTROLS AND PERFORMANCE
 CALCULATIONS AS THIS SPACE IS BEING INCLUDED INTO THE
 NEW SINGLE TENANT.
  
 8) NOTE: PLEASE SEE BOTH THE AHU AND THE ELEVATOR
 EQUIPMENT IS BEING SHOWN CONNECTED TO A RECEPTACLE
 WHICH IS NOT PERMITTED.
 PLEASE SEE THESE ARE REQUIRED TO BE HARDWIRED AND
 DISCONNECTS.
 422.30,31, 440.11, 620.51 ETC.
  
 9) NOTE: PLEASE KNOW THE CONTRACTOR OWES FEES AS THE
 VALUE ON PERMIT APPLICATION WAS INCREASED.
 FEE OWES IS CURRENTLY AT $1665.00.
  
 10) NOTE: PLEASE SEE AS SOME COMMENTS ARE REPEATED FROM
 PREVIOUS REVIEW, PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND REPEATED CODE
 COMPLIANT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-05 Cont ID  
Sent By dpalmer Date 2007-01-05 Time 07:37 Rev Time 0.00
Received By dpalmer Date 2007-01-03 Time 07:47 Sent To  
Notes
2007-01-05 07:39:51** UNSAT **
  
  
 1) NOTE: PLEASE SEE PLANS SHALL BEAR THE CORRECT
 ADDRESS AND UNIT NUMBER(S) ON TITLE BLOCKS ONCE ALL ARE
 CLEARED FROM THE ADDRESSING REVIEWER.
 PLEASE ALSO KNOW THAT IS HAS COME TO OUR ATTENTION THAT
 THE BUILDING POSSIBLY NOW HAS A CONDOMINIUM ASSESSMENT
 WHICH IN TURN MAY REQUIRE A UNITY OF TITLE.
 PLEASE SEE PLANS MENTIONS 106, ADDRESS IS 120 AND THE
 PERMIT APPLICATION IS
 PLEASE ALSO SEE POSSIBLE BUILDING REVIEW COMMENTS.
  
 2) NOTE: PLEASE SEE PLANS SHALL REFERENCE ALL CODES
 WHICH ARE CURRENTLY RELEVANT TO THE DESIGN OF SAID
 PLANS AND WHICH SHALL ALSO BE STATED ON PLANS. PLEASE
 KNOW THAT AS OF OCT 1ST, 2005 THE STATE OF FLORIDA
 ADOPTED THE 2004 FBC, HOWEVER THE PLANS STATE THE 2001
 FBC. PLEASE ALSO KNOW THAT AS OF DEC 8TH, 2006 THE
 STATE OF FLORIDA HAS NOW ADOPTED THE 2006 REVISIONS TO
 THE FLORIDA BUILDING CODE AND THE 2005 NEC, NFPA-70.
 PLEASE BE SURE TO SEE ALL OF THESE NEW SECTIONS WHICH
 ARE RELEVANT TO THE DESIGNS FOR THE SCOPE OF WORK BEING
 SHOWN AND PROPOSED.
 PLEASE ALSO SEE THAT THE FOLLOWING SHALL BE STATED ON
 THE PLANS AT A MINIMUM.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 PLEASE SEE MANY ITEMS BELOW ARE FROM THESE CODES AS
 REFERENCED.
  
 3) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR AND MATERIALS. PLEASE ALSO
 SEE BUILDING REVIEW COMMENTS AS BASED ON THE SCOPE OF
 WORK SHOWN THE APPLIED VALUE IS LOW.
 FBC 108.3
  
 4) NOTE: PLEASE CLARIFY IF THERE IS AN EQUIPMENT ROOM
 FOR ELEVATOR EQUIPMENT. PLEASE ALSO SEE 620.22, 23 AND
 24.
 IF THERE IS AN EQUIPMENT ROOM AND EMERGENCY BATTERY
 BACK UP LIGHT OF SOME KIND WILL BE REQUIRED.
 LS 101 7.8, 700.16 ETC
  
 5) NOTE:PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE DUE TO THE SCOPE OF WORK FOR CREATING THIS
 ONE NEW TENANT BUILD OUT SPACE AUTOMATED LIGHTING
 CONTROLS WILL BE REQUIRED. PLEASE SUBMIT SCHEDULING.
 PLEASE SEE IF INSTALLING A SYSTEM TO SEE REQUIREMENTS
 FOR MULTIPLE FLOORS. PLEASE SEE THAT IF USING ALL
 OCCUPANCY SENSOR TYPE DEVICES PLEASE STATE THE MAXIMUM
 TIMES, OR MAXIMUM TIMES ON ANY OVER RIDE DEVICES.
 PLEASE ALSO SEE 13-415.1.AB.1 AND 13-415.2.ABC.1 AND
 TABLES FOR USE ETC.
  
 6) NOTE: PLEASE PROVIDE PHOTO-METRICS FOR STAIRS.
 PLEASE SEE 7.8.1.3, AND 7.9.2.2 WHICH REQUIRES A
 MINIMUM OF 10FT CANDLES UNDER NORMAL AND 1FT CANDLE
 UNDER EMERGENCY.
 PLEASE SEE CONTROLS FOR LIGHTING SHALL ALSO BE
 INDICATED, AND ANY OVER RIDES DEVICES OR NIGHT LIGHTS.
  
 7) NOTE: PLEASE SEE DOOR SWING AT THE BOTTOM OF THE NEW
 PROPOSED STAIRS MAY VERY WELL BE AN ISSUE WITH THE
 BUILDING AND FIRE REVIEW WHICH SEEMS TO IMPEDE WITH THE
 DIRECT PATH OF EGRESS FROM STAIRS.
 PLEASE SEE SECTIONS WHICH WILL BE STATED FROM OTHER
 REVIEWER(S). LS101 AND THE FBC
  
 8) NOTE: PLEASE INDICATE AND COMPLETE LOAD
 CALCULATIONS. THE INFORMATION AS SHOWN ON THE EXISTING
 AC-7 PANEL DOES NOT PROVIDE.
 PLEASE ALSO INCLUDE WHERE THIS PANEL IS BEING FED FROM.
 AS THIS BUILDING HAS BECOME A NEW "CONDO" PLEASE SHOW
 HOW THIS LEGAL OWNED UNIT HAS ITS OWN METER, MAIN
 DISCONNECT ETC.
 PANEL ONLY SHOWS THE NEW LOAD FOR THE NEW PANEL. LOAD
 ON THE EXISTING MDP AND NEW LOAD ADDED ETC.
 PLEASE KNOW AT THIS TIME REVIEW FOR MANY ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DONE.
 220.3, 220.10, 220.11, 220.13, ALL CONTINUOUS AND
 LARGEST MOTOR LOADS SHALL BE SHOWN AT THE REQUIRED
 125%.215.3, 230.42 ETC.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 9) NOTE: PLEASE SEE FBC 2004 11-4.28.2, .3(4) FOR
 MINIMUM LEVELS FOR STROBES AND DB LEVELS ON HORN
 DEVICES.
 PLEASE SEE 75MIN CD ETC SHALL BE SHOWN ON PLANS FOR
 DEVICES BEING CONNECTED INTO ANY BUILDING FIRE ALARM
 SYSTEM.
 PLEASE KNOW THE BASED BUILD OUT WILL BE REQUIRED TO
 SHOW ANY FIRE SPRINKLER AND BASE FIRE ALARM DEVICES,
 EVEN THOUGH SEPARATE PERMITS, PLANS ARE REQUIRED FOR
 THESE ITEMS.
 PLEASE SEE NFPA-72, NFPA-1, AND FBC ADMIN SECTION
 106.3.5.1.1
 ** PLEASE SEE FIRE MARSHAL'S REVIEW COMMENT(S).
  
 10) NOTE: PLEASE SEE SOME SHEETS WHICH ARE NOT
 ELECTRICAL CONTAIN WHITE OUT. PLEASE KNOW THAT WHITE
 OUT AND HAND WRITTEN CHANGES IS NOT PERMITTED ON ANY
 PLANS, WHETHER OR NOT THEY ARE SIGNED, DATED AND SEALED
 BY AN ARCHITECT/ ENGINEER/CONTRACTORETC.
 FS 471, 481, FAC 61G15-23,61G1-16 FBC ADMIN SECTION
 106.1.2, 106.1.3, ETC.
  
 11) NOTE: PLEASE SHOW ALL EXISTING ELECTRICAL IN THE
 7TH FLOOR AREA FOR ELECTRICAL. PLEASE KNOW THE LIGHTING
 WILL BE REQUIRED TO MEET CHAPTER 13 OF THE FBC FOR
 CONTROLS AND PERFORMANCE CALCULATIONS AS THIS SPACE IS
 BEING INCLUDED INTO THE NEW SINGLE TENANT.
  
 12) NOTE: PLEASE SEE RISER AND PANEL SCHEDULE FOR NEW
 PANEL INDICATES THIS PANEL BEING A 100AMP PANEL AND YET
 42 CIRCUITS? PLEASE VERIFY THIS AS IS IT NOT KNOWN THAT
 A 100A PANEL IS AVAILABLE IN 42 CIRCUITS.
 PLEASE REVISE AND ADJUST AS NEEDED.
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE MISSING THE CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE ENGINEERING FIRM FOR THE
 "S" SHEETS. FAC 61G15-23.002 FS 471.023 THIS IS
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY THE OTHER
 TRADE(S).
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-05 06:57:252007-01-05 06:57:25
 NOTES IN PROGRESS
2007-01-03 07:49:19IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-08-24 Cont ID  
Sent By mawillia Date 2007-08-24 Time 20:18 Rev Time 0.00
Received By mawillia Date 2007-08-24 Time 19:37 Sent To  
Notes
2007-08-24 19:42:24*****UNSAT*****
  
 THE PREVIOUS FIRE PLAN REVIEW WHICH STILL NEED TO BE
 ADDRESSED:(CAPS INDICATE HOW COMMENTS ARE TO BE
 ADDRESSED)
  
 04.CONSTRUCTION AND / OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER WITH ACCESS TO OR EGRESS FROM
 THE FLOOR(S) OR BUILDING.ADD COMMENT TO SHEET A-2
  
 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
 ADD COMMENT TO SHEET A-2
  
 07. WHAT IS THE INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS SND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREA?ADD YOUR RESPONSE " ALL
 INTERIOR FINISHES WILL MEET CLASS A FLAME SPREAD
 RATING"TO SHEET CS-1 OR A-1
  
 09.ALTHOUGH THIS ELEVATOR WILL SERVE ONLY TWO FLOORS,
 IT STILL SHALL CONFORM TO THE REQUIREMENTS OF ASME
 A17.1ADD TO SHEET A-4 - ELEVATORS TO CONFORM TO
 THE REQUIREMENTS OF ASME A17.1
  
 NEW COMMENT
  
 A.ON SHEET CS-1 UNDER THE DRAWING LIST, IT STATES
 THAT THERE IS A SHEET NUMBER A-1 HOWEVER, NO SUCH SHEET
 IS INCLUDED IN THE SUBMITTED PLANS.PLEASE ADD SHEET
 A-1 OR AMEND SHEET CS-1
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-14 Cont ID  
Sent By mawillia Date 2007-02-14 Time 14:33 Rev Time 0.00
Received By mawillia Date 2007-02-14 Time 14:33 Sent To  
Notes
2007-02-14 15:49:34*****DENIED*****
  
  
 01.THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK IS
 GOING TO CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 02.THE 2003 NFPA 101 AND 2004 FLORIDA FIRE PREVENTION
 CODE SHALL BE REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.CONSTRUCTION AND / OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER WITH ACCESS TO OR EGRESS FROM
 THE FLOOR(S) OR BUILDING.
  
 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 06.PLEASE INDICATE IF THE FLOOR(S) OR THE BUILDING
 WILL BE OCCUPIED DURING THE SCOPE OF WORK.IF SO, THIS
 WILL BE PERMITTED ONLY WHERE REQUIRED MEANS OF EGRESS
 AND REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND
 MAINTAINED, OR WHERE ALTERNATIVE LIFE SAFETY MEASURES
 ACCEPTABLE TO THE AHJ ARE IN PLACE.
  
 07. WHAT IS THE INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS SND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREA?
  
 08.SINCE THE FIRE ALARM AND FIRE SPRINKLER SYSTEM
 WILL BE MODIFIED, SEPARATE PLANS AND PERMITS WILL BE
 REQUIRED.
  
 09.ALTHOUGH THIS ELEVATOR WILL SERVE ONLY TWO FLOORS,
 IT STILL SHALL CONFORM TO THE REQUIREMENTS OF ASME
 A17.1
  
 10.EMERGENCY LIGHTING WILL BE REQUIRED IN THE NEW
 STAIR AREA.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-11 Cont ID  
Sent By adarroug Date 2007-07-11 Time 11:02 Rev Time 0.00
Received By adarroug Date 2007-07-11 Time 11:02 Sent To  
Notes
2007-07-24 10:09:48TO "COMM" BD#41
2007-07-11 11:02:49WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-23 Cont ID  
Sent By jwitmer Date 2007-02-23 Time 12:19 Rev Time 0.00
Received By jwitmer Date 2006-12-17 Time 12:58 Sent To  
Notes
2007-01-03 08:46:58TO COMM BOARD #2
 PLANS ARE NOT FOR BOB BOARD.
2006-12-17 12:58:25WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-01 Cont ID  
Sent By tgordon Date 2007-08-01 Time 09:32 Rev Time 0.30
Received By tgordon Date 2007-08-01 Time 09:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-05 Cont ID  
Sent By tgordon Date 2007-01-05 Time 09:04 Rev Time 0.50
Received By tgordon Date 2007-01-05 Time 09:04 Sent To  
Notes
2007-01-05 09:12:04*** DENIED ***
 1) CERTIFICATE OF AUTHORIZATION NUMBER AA 260000963 ON
 PLANS FOR DAVID MILLER & ASSOCIATES IS INCORRECT,
 PLEASE ENTER CORRECT NUMBER AA 26000963. SEE FAC
 61G15-23.002.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-08-30 Cont ID  
Sent By kstevens Date 2007-08-30 Time 10:57 Rev Time 0.00
Received By kstevens Date 2007-08-30 Time 10:57 Sent To  
Notes
2007-08-30 12:10:19DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW: COMMENT NUMBER TO REMAIN THE
 SAME.
  
 1. SHT A-2 MORE INFORMATION REQUIRED. NOTE INDICATES A
 VENT WILL BE REMOVED. PLEASE INDICATE WHAT TYPE OF VENT
 WILL BE REMOVED.--NOTE INDICATES THAT THE ROOF
 DRAIN WILL NEED AN EXTENTION. IF OLD PAVERS WILL BE
 REMOVED FROM THE ROOF AND NEW PAVERS WILL BE INSTALLED,
 WILL THE NEW PAVERS BE THICKER THE THOSE REMOVED? THE
 ROOF SHOWS NO SECONDARY ROOF DRAINS. PLEASE INDICATE
 THE SQUARE FOOTAGE BEING DRAINED BY THIS ROOF DRAIN.
 INCLUDE 1/2 AREA OF ALL VERTICAL WALLS, AND THE AREA
 FROM THE ROOF ABOVE DRAINING ON TO THE ROOF AREA. (A
 DOWNSPOUT IS INDICATED). SHOW THE LOCATION OF ALL ROOF
 DRAINS AND SECONDARY ROOF DRAINS OR SCUPPERS IN ROOF
 AREA WHERE NEW TILE WORK WILL BE INSTALLED. SECTIONS
 106, 1107 AND ALL SUBSECTIONS& 106.1.1 1.
 ****RESPONSE,VENT ISSUE NOT ADDRESSED
  
 2. OK
  
 3. SHT M-1 INDICATES HOT & COLD WATER TO BE STUBBED OUT
 FOR FUTURE USE. ALSO THIS SHEET SHOWS (4) 4" RAIN WATER
 LEADERSTO BE REUSED.A PLUMBING PERMIT WILL BE
 REQUIRED. SECTION 105.1.
 ****RESPONSE NOTED.
 4. OK
  
 **********NEW COMMENT**********
  
 1B. WHEN RESUBMITTING PLANS PLEASE INDICATE CORRECTIONS
 BY CLOUDING CORRECTIONS AND/OR DELETIONS.--REMOVE
 ALL OLD SHEET TO BE REPLACED WITH REVISIED SHEETS AND
 SUBMIT ALL OLD SHEETS SEPARATELY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-03 Cont ID  
Sent By kstevens Date 2007-02-03 Time 13:53 Rev Time 0.00
Received By kstevens Date 2007-02-03 Time 13:41 Sent To  
Notes
2007-02-03 14:32:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
  
 1. SHT A-2 MORE INFORMATION REQUIRED. NOTE INDICATES A
 VENT WILL BE REMOVED. PLEASE INDICATE WHAT TYPE OF VENT
 WILL BE REMOVED.--NOTE INDICATES THAT THE ROOF
 DRAIN WILL NEED AN EXTENTION. IF OLD PAVERS WILL BE
 REMOVED FROM THE ROOF AND NEW PAVERS WILL BE INSTALLED,
 WILL THE NEW PAVERS BE THICKER THE THOSE REMOVED? THE
 ROOF SHOWS NO SECONDARY ROOF DRAINS. PLEASE INDICATE
 THE SQUARE FOOTAGE BEING DRAINED BY THIS ROOF DRAIN.
 INCLUDE 1/2 AREA OF ALL VERTICAL WALLS, AND THE AREA
 FROM THE ROOF ABOVE DRAINING ON TO THE ROOF AREA. (A
 DOWNSPOUT IS INDICATED). SHOW THE LOCATION OF ALL ROOF
 DRAINS AND SECONDARY ROOF DRAINS OR SCUPPERS IN ROOF
 AREA WHERE NEW TILE WORK WILL BE INSTALLED. SECTIONS
 106, 1107 AND ALL SUBSECTIONS& 106.1.1 1.
  
 2. IT IS INDICATED THAT A NEW ROOF WILL BE INSTALLED ON
 SHT A-5 FOR THE 8TH FLOOR. PLEASE INDICATE THE LOCATION
 OF THE ROOF DRAINS, PRIMARY AND SECONDARY. SUBMIT
 CALCULATIONS FOR THE PRIMARY AND SECONDARY ROOF DRAINS.
 INCLUDE 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS. SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS.
  
 3. SHT M-1 INDICATES HOT & COLD WATER TO BE STUBED OUT
 FOR FUTURE USE. ALSO THIS SHEET SHOWS (4) 4" RAIN WATER
 LEADERSTO BE REUSED.A PLUMBING PERMIT WILL BE
 REQUIRED. SECTION 105.1.
  
 4. SEPARATE ROOF PERMIT WILL BE REQUIRED. SECTION
 105.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-07-26 Cont ID  
Sent By mflis Date 2007-07-26 Time 08:20 Rev Time 0.00
Received By mflis Date 2007-07-26 Time 08:20 Sent To  
Notes
2007-07-26 08:20:54ZONING REVIEW: PASSED
  
 - TO HISTORIC PRESERVATION FOR REVIEW 7/26/07
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status P Date 2007-01-18 Cont ID  
Sent By mflis Date 2007-01-18 Time 09:30 Rev Time 0.00
Received By mflis Date 2007-01-18 Time 09:30 Sent To  
Notes
2007-01-18 09:33:01ZONING REVIEW: PASSED
  
  
 - THE ADDRESS FOR THIS PROJECT WAS INCORRECT AND SHOULD
 BE 120 S. OLIVE
 - PROJECT IS LOCALLY DESIGNATED AND REQUIRES HISTORIC
 PRESERVATION REVIEW AND APPROVAL
 - PLEASE CONTACT FRIEDERIKE MITTNER AT 822-1457 FOR
 HISTORIC QUESTIONS
  
  
 MATT FLIS 822-1445


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved