| 2007-01-17 09:31:33 | BUILDING PLAN REVIEW |
| | PERMIT: 06120355 |
| | ADD: 900 S OLIVE AVE |
| | CONT: ROBLING ARCHITECTURE |
| | TEL: (561)662-0000 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1SSTREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN |
| | THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE |
| | IS NULL |
| | & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3) PLEASE CORRECT THE ADDRESS AND PROPERTY CONTROL |
| | NUMBER ON THE PERMIT APPLICATION. |
| | PLANS INDICATE WORK TO BE ACCOMPLISHED ON JEFFERSON RD. |
| | PLEASE CONTACT LILI URSA AT 822-1239 |
| | FOR A NEW ADDRESS AND PLEASE CORRECR THE PROPERTY |
| | CONTROL NUMBER TO REFLECT THE CORRECT LOT. 106.1.2.* |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 4) PLEASE PROVIDE ENERGY CALCS. CHAPTER 13 FBC. |
| | |
| | 5) PLEASE PROVIDE SOILS REPORTS,FBC 1802.2.1 |
| | QUESTIONABLE SOILS, |
| | 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING |
| | POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING |
| | VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. |
| | SUCH INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 6) PLEASE PROVIDE A SITE PLAN PROVIDING THE FOLLOWING: |
| | 11-4.1.2 ACCESSIBLE SITE AND EXTERIOR FACILITIES: NEW |
| | CONSTRUCTION. |
| | THIS EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS, |
| | STRUCTURES, OR FACILITIES WHICH WERE EITHER UNDER |
| | CONSTRUCTION OR UNDER CONTRACT FOR CONSTRUCTION ON |
| | OCTOBER 1, 1997. |
| | NOTHING IN THIS CODE SHALL BE CONSTRUED TO RELIEVE THE |
| | OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM THE |
| | DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS |
| | ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, REGARDLESS |
| | OF WHETHER THE CODE REQUIRES AN ELEVATOR TO BE |
| | INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY, |
| | EXCEPT: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES, |
| | MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND |
| | AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND |
| | PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS, |
| | ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT |
| | DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC |
| | ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE |
| | SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND |
| | THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT |
| | LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION |
| | BOOTHS. HOWEVER AS PROVIDED IN SECTION 553.509, FLORIDA |
| | STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES MUST, |
| | AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE |
| | ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY |
| | BE REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS |
| | OTHERWISE EXEMPT UNDER SECTION 11-4.1.3 (5) OF THIS |
| | CODE. |
| | AN ACCESSIBLE SITE SHALL MEET THE FOLLOWING MINIMUM |
| | REQUIREMENTS: |
| | (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH |
| | SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF |
| | THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE |
| | PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED, |
| | AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE |
| | BUILDING ENTRANCE. |
| | (2)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH |
| | SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS, |
| | ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND |
| | ACCESSIBLE SPACES THAT ARE ON THE SAME SITE. |
| | (3)ALL OBJECTS THAT PROTRUDE FROM SURFACES OR |
| | POSTS INTO CIRCULATION PATHS SHALL COMPLY WITH SECTION |
| | 11-4.4 . |
| | (4)GROUND SURFACES ALONG ACCESSIBLE ROUTES AND IN |
| | ACCESSIBLE SPACES SHALL COMPLY WITH SECTION 11-4.5 . |
| | |
| | 7) PLANS DO NOT PROVIDE DETAILS TO THE ENTRY OF ANY |
| | EXTERIOR DOORS. |
| | 1003.5.2 |
| | WHERE CHANGE IN ELEVATION OF 12 INCHES (305 MM) OR LESS |
| | OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT |
| | DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL BE |
| | PROVIDED. |
| | 1003.5.2 |
| | WHERE CHANGE IN ELEVATION OF 12 INCHES (305 MM) OR LESS |
| | OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT |
| | DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL BE |
| | PROVIDED. |
| | |
| | 8)SHEET A-3 INDICATES THE USE OF 2 SINKS PLANS |
| | INDICATE A CLEAR FLOOR SPACE FOR FRONT APPROACH BUT |
| | THERE IS NO |
| | ELEVATION INDICATING THE FRONT OF THE CABINET |
| | CONFIGURATION. PLEASE PROVIDE. |
| | SINKS: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT |
| | LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| | SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 |
| | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD |
| | APPROACH. |
| | THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE |
| | AND |
| | SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH |
| | THE SINK. |
| | |
| | 9) PLANS DO NOT INDICATE THE USE OF A VAPOR RETARDER. |
| | 1816.1.4 |
| | IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE |
| | PREVENTION, CHEMICALLY TREATED SOIL SHALL BE PROTECTED |
| | WITH A MINIMUM 6 MILLIMETER VAPOR RETARDER TO PROTECT |
| | AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE |
| | VAPOR RETARDER PLACEMENT, RETREATMENT IS REQUIRED. ANY |
| | WORK, INCLUDING PLACEMENT OF REINFORCING STEEL, DONE |
| | AFTER CHEMICAL TREATMENT UNTIL THE CONCRETE FLOOR IS |
| | POURED, SHALL BE DONE IN SUCH MANNER AS TO AVOID |
| | PENETRATING OR DISTURBING TREATED SOIL. |
| | |
| | 10)PLANS DO NOT INDICATE THE USE OF TERMITE |
| | PROTECTION, PLEASE INDICATE WHICH METHOD OF PROVIDING |
| | SUBTERRANEAN TERMITE PROTECTION SHALL BE USED. 1816.1 |
| | TERMITE PROTECTION. |
| | TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED |
| | TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES, |
| | BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR |
| | OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED |
| | FOR USE AS A PREVENTATIVE TREATMENT TO NEW |
| | CONSTRUCTION. SEE SECTION 202 , REGISTERED TERMITICIDE. |
| | UPON COMPLETION OF THE APPLICATION OF THE TERMITE |
| | PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL |
| | BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED |
| | PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING |
| | STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE |
| | TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. |
| | TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS |
| | ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE |
| | AND CONSUMER SERVICES.? |
| | |
| | 11) SHEET F-1 STRUCTURAL NOTE# 4, PLANS INDICATE |
| | ANCHORING HARDWARE TO MEET THE MINIMUM STANDARDS FOR |
| | ACI 318-05. PLEASE PROVIDE HOW THE |
| | PREFAB WILL BE ATTACHED TO THE FOUNDATION. 106.1.2*. |
| | |
| | 12)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 12A) WINDOWS- SINGLE HUNG |
| | 12B) WINDOWS- GLASS BLOCK |
| | 12C) EXTERIOR DOORS SOLID OR GLAZED |
| | 12D) ROLL UP DOORS |
| | 12E) ROOFING ASSEMBLIES |
| | |
| | 13)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 14) SPEAKING WITH ARCHITECT STEVEN BRUH THE |
| | MANUFACTURING COMPANY HAS APPLIED FOR DCA APPROVAL BUT |
| | HAS NOT RECEIVED SUCH APPROVAL AT THIS TIME. THE CITY |
| | HAS REVIEWED WHAT THEY WILL REQUIRE FOR A SITE SPECIFIC |
| | REQUIREMENTS FOR ROYAL CONCRETE CONCEPTS, INC. REQUIRED |
| | SUBMITTALS: |
| | |
| | 1) ALL REQUIRED SUBMITTALS FOR THE STRUCTURE ALONG WITH |
| | ENGINEERED PLANS, SHOP DRAWINGS INCLUDING ENGINEERING |
| | CALCULATIONS. |
| | 2) LETTER FROM A LICENSED THRESHOLD INSPECTOR STATING |
| | THAT AN INSPECTION WILL BE MADE AT THE MANUFACTURES |
| | SITE OF THE JOB SPECIFIC COMPONENTS TO VERIFY |
| | CONSTRUCTION COMPLIANCE OF THE COMPONENTS WITH THE |
| | ENGINEERED DESIGN. |
| | |
| | DURING CONSTRUCTION SUBMITTALS: |
| | THREE SETS OF PLANS, DOCUMENTS, REPORTS , PRODUCT |
| | APPROVALS AND SUBMITTALS. |
| | 1) CERTIFICATE OF COMPLIANCE AFFADAVIT FROM THE |
| | THRESHOLD INSPECTOR THAT, TO THE BEST OF HIS/ HER |
| | KNOWLEDGE AND BELIEF, THE OFF-SITE CONSTRUCTION |
| | COMPONENTS OUTLINED HEREIN AND INSPECTED UNDER HIS/ HER |
| | AUTHORITY HAVE BEEN COMPLETED IN CONFORMANCE WITH THE |
| | APPROVED PLANS, SHOP DRAWINGS AND ENGINEERING.ALSO, |
| | PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION SERVICES |
| | MANAGER - TEL: |
| | 561 805 6711), A MEETING INVOLVING THE |
| | THRESHOLD INSPECTOR, JOB INSPECTOR, CONTRACTOR AND |
| | ENGINEER. |
| | |
| | 15A) TABLE 602 REQUIREMENTS FOR EXTERIOR WALLS BASED ON |
| | FIRE SEPERATION DISTANCE, PLEASE PROVIDE THE DISTANCES |
| | FROM THE EXISTING STRUCTURES ALSO ON THIS SAME LOT. IT |
| | APPEARS THE STRUCTURES MAY BE CLOSER THAN 20'-0", THIS |
| | WILL AFFECT AN ASSUMED PROPERTY LINE BETWEEN BUILDINGS |
| | ON THE SAME LOT.503.1.3, TABLE 601,602,704.8. 715.3 AND |
| | 715.4. IF ASSUMING NO FIRE SEPERATION IS REQUIRED |
| | BETWEEN BUILDINGS, (ASSUMED ONE LARGE BUILDING) PROVIDE |
| | THE TOTAL SQUARE FOOTAGE OF ADJACENT BUILDINGS |
| | FOOTPRINT. |
| | |
| | 15B) PLANS INDICATE THE CONCRETE THICKNESSOF THE |
| | WALLS LTO BE 2" THICK, IF FIRE RESISTANCE WILL BE |
| | REQUIRED BETWEEN BUILDINGS PLEASE PROVIDE THE |
| | EQUIVALENT THICKNESS OF PRECAST CONCRETE WALL, SEE |
| | TABLE 721.2.1.1 OR 721.2.1.1.4.(RIBBED OR UNDULATING |
| | SURFACES). |
| | |
| | 16) SHEET S-3 INDICATES A STEEL BEAM IN SECTIONS A-A NO |
| | MENTION AS TO SIZE OR WEIGHT OF BEAM? 106.1.2.* |
| | ADMINISTRATIVE CODE. |
| | |
| | 17) THERE IS NO DBA OR CERTIFICATE OF AUTHORIZATION FOR |
| | BRUH-HOSEIN-RUPP AT DPBR.) 481.219 F.S.CERTIFICATE |
| | OF |
| | AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ARCHITECT |
| | PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL |
| | SERVICES, SHALL INCLUDE |
| | THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER.ADD THE NUMBER TO EACH SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | |
| | 18) SHEET S-3 VARIOUS SECTIONS SHOW A 3/4" =1'-0", |
| | WRONG SCALE DETAIL# 3 AND SECTION A-A.BEFORE A |
| | PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | .NOTE : ADDITIONAL COMMENTS MAY APPEAR ON THE NEXT |
| | REVIEW DUE TO COMMENT RESPONSE OR ADDITIONAL NEW |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |