Plan Review Details - Permit 06120325
Plan Review Stops For Permit 06120325
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-25 Cont ID  
Sent By rmcdouga Date 2007-10-19 Time 10:53 Rev Time 0.00
Received By rmcdouga Date 2007-10-18 Time 18:23 Sent To  
Notes
2007-10-23 10:11:23BUILDING PROVISO
  
 THE NOC THAT WAS SUBMITTED IS EXPIRED. OWNER TO PROVIDE
 RE-RECORDED NOC AT FIRST INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-25 Cont ID  
Sent By rmcdouga Date 2007-08-02 Time 16:15 Rev Time 0.00
Received By rmcdouga Date 2007-08-02 Time 16:15 Sent To  
Notes
2007-08-02 17:31:50DENIED BY BUILDING
  
 1) THE NOA HAS EXPIRED. THE WORK IS REQUIRED TO
 COMMENCE WITHIN 90 DAYS OF THE RECORDING DATE. THE WILL
 NEED TO BE RE-RECORDED.
  
 2) THE FINISH FLOOR ELEVATION OF THE ENCLOSED GARAGE IS
 REQUIRED TO BE 7'-6" ABOVE BASE FLOOD ELEVATION PER
 CITY OF WEST PALM BEACH MUNICIPAL CODE. THE PLANS
 SPECIFY THE FINISH FLOOR ELEVATION AS 7.0'. PLEASE
 CORRECT.
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FOR. THE FORM IS INCORRECT. THE EXTERIOR
 WALLS ARE LISTED ON THE ENERGY CALC. FORM AS WOOD
 FRAME. ACCORDING TO THE PLANS ALL OF THE EXTERIOR WALL
 ARE MASONRY EXCEPT FOR THE IN-FILL FRAMING AT THE
 GARAGE DOOR OPENING. PLEASE CORRECT.
  
 4) ITEM #11 FROM THE FIRST REVIEW REQUIRING CLEARANCE
 BETWEEN FINAL EARTH GRADE OR SLABS AND EXTERIOR WALL
 COVERINGS FOR TERMITE INSPECTIONS HAS NOT BEEN
 ADEQUATELYADDRESSED. EXCEPTION #4 WHICH ALLOWS PATIOS
 THAT HAVE BEEN SOIL TREATED FOR TERMITES TO MATCH THE
 BUILDING INTERIOR FINISH FLOOR ELEVATION, ONLY APPLIES
 TO MASONRY CONSTRUCTION. THE AREA AT THE GARAGE OPENING
 IS WOOD FRAME.
  
 5) IN ORDER TO ADDRESS ITEM #13 FROM THE FIRST REVIEW,
 PROVIDE A SECTION THROUGH THE FOUNDATION AT THE WOOD
 FRAME IN-FILL WALL AND THE CONCRETE BLOCK WALL SHOWING
 COMPLIANCE WITH R404.1.6 . SHOW A MINIMUM OF 4" ABOVE
 FINISH GRADE FOR MASONRY AND 6" AT WOOD FRAME.
  
 6) THE FLOOR PLAN DOES NOT INDICATE THE WALL TYPES FOR
 EXTERIOR OR INTERIOR WALLS.
  
 7) PROVIDE WALL SECTIONS WHICH SPECIFY THE EXTERIOR AND
 INTERIOR WALL COVERINGS, INSULATION, WATER BARRIER,
 LATH AND STUCCO, 1/2" DRYWALL, ETC.
  
 8) THE DESCRIPTION OF WORK ON THE APPLICATION INDICATES
 ADDING A HOT TUB AND A DECK FOR THE HOT TUB. THE PLANS
 THAT WERE SUBMITTED INDICATE THAT THIS IS EXISTING
 PLEASE CLARIFY. IF THIS IS NEW WORK TO BE PART OF THIS
 PERMIT, SUBMIT THE MANUFACTURER'S SPECS. AND LISTING
 INFORMATION FOR THE HOT TUB AND PLANS AND STRUCTURAL
 DETAILS FOR THE DECK. SHOW THAT THE DECK IS CAPABLE OF
 SUPPORTING THE HOT TUB WITH ASSOCIATED LIVE AND DEAD
 LOADS. SPECIFY THE HEIGHT OF THE DECK ABOVE GRADE AND
 PROVIDE GUARDRAIL AND STAIR DETAILS IF REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-25 Cont ID  
Sent By rmcdouga Date 2007-01-25 Time 08:19 Rev Time 0.00
Received By rmcdouga Date 2007-01-24 Time 18:28 Sent To Z
Notes
2007-01-25 08:19:46DENIED BY BUILDING
  
 1)THE EXISTING "CABANA" APPEARS TO BE A GARAGE THAT
 WAS CONVERTED TO LIVING SPACE WITHOUT PERMITS.
  
 2) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE, WHICH
 REQUIRES THE FINISH FLOOR TO HAVE A BASE FLOOD
 ELEVATION OF 7' 6". SPECIFY THE ELEVATION OF FINISH
 FLOOR OF THE CABANA. SUBMIT AN ELEVATION CERTIFICATE
 FOR THIS AREA.
  
 3) THE ENCLOSING OF THE GARAGE IS ADDING ADDITIONAL
 LIVING SPACE TO THE EXISTING RESIDENCE. THEREFORE, THE
 PLANS ARE REQUIRED TO BE REVIEWED PALM BEACH COUNTY TO
 DETERMINE IF IMPACT FEES ARE OWED. THE PLANS MUST BE
 STAMPED BY THEM AND A COPY OF THE RECIEPT SUBMITTED
 BEFORE THE PERMIT IS ISSUED.
  
 4)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 6) SUBMIT ENERGY CALCULATIONS FOR THE ENCLOSED GARAGE
 PER FBC CHAPTER 13.
  
 7) SPECIFY THE CEILING AND WALL INSULATION ON THE
 PLANS.
  
 8) WOOD SIDING, SHEATHING AND WALL FRAMING ON THE
 EXTERIOR OF A BUILDING HAVING A CLEARANCE OF LESS THAN
 6 INCHES SHALL COMPLY WITH SECTION R319 PROTECTION
 AGAINST DECAY.
  
 9)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 10)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES.
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
 EXCEPTIONS:
 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS
 THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE
 INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH
 RAMPS ONLY.
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO
 AND GARAGE SLABS AND ENTRY AREAS.
 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES,
 THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR
 FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5.MASONRY VENEERS.
  
 12) SHOW COMPLIANCE WITH R401.3 DRAINAGE .
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 13) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 14) SUBMIT FLORIDA PROUCT APPROVAL NUMBERS FOR THE USP
 CONNECTORS.
  
 15) FENCES AND WALLS REQUIRE SEPARATE PERMITS. NOTE:
 THE LETTER SUBMITTED FOR THE MASORY PRIVACY WALL MUST
 SPECIFY A 140 MPH WINDSPEED.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-12-21 Cont ID  
Sent By btrobaug Date 2006-12-21 Time 13:12 Rev Time 1.00
Received By btrobaug Date 2006-12-21 Time 11:55 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-27 Cont ID  
Sent By adarroug Date 2007-09-27 Time 09:10 Rev Time 0.00
Received By adarroug Date 2007-09-27 Time 09:10 Sent To B
Notes
2007-09-27 09:10:35TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 11:07 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 11:07 Sent To Z
Notes
2007-06-19 11:07:43TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-25 Cont ID  
Sent By rmcdouga Date 2007-01-25 Time 08:20 Rev Time 0.00
Received By rmcdouga Date 2006-12-15 Time 15:25 Sent To  
Notes
2006-12-15 15:25:58TO "E" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-01 Cont ID  
Sent By jroach Date 2007-08-01 Time 10:02 Rev Time 0.00
Received By jroach Date 2007-08-01 Time 10:02 Sent To B
Notes
2007-08-01 10:02:20***PROVISO***
  
 1) HOT TUB (SPA) SHALL BE LOCATED A MINIMUM OF FIVE (5)
 FEET FROM THE SIDE AND REAR PROPERTY LINES.
  
 2) NO COOKING FACILITIES (I.E. STOVE OR 220 OUTLETS)
 SHALL BE PROVIDED IN THE CABANA.THE CABANA SHALL NOT
 BE USED OR RENTED AS A SEPARATE DWELLING UNIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-01 Cont ID  
Sent By jroach Date 2007-03-01 Time 08:57 Rev Time 0.00
Received By jroach Date 2007-03-01 Time 08:57 Sent To  
Notes
2007-03-01 09:00:43***FAILED***
  
 1) THE AREA OF RENOVATION SHWON ON SP-1 DOES NOT
 CORRESPOND WITH THE OTHER SHEETS, NOR THE DESCRIPTION
 ON THE PERMIT APPLICATION.
  
 2) THE PERMIT APPLICATION INDICATES THAT THE SURVEY IS
 BEING SUBMITTED FOR THE FENCE AND HOT TUB.WAS THIS
 PREVIOUSLY PERMITTED?HOT TUBS ARE TO BE A MINIMUM OF
 FIVE (5) FEET FROM THE PROPERTY LINE.IF NEW, DETAILS
 OF THE FENCE HEIGHT/LOCATION SHALL BE PROVIDED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.