| Plan Review Stops For Permit 06120322 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-07-23 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-07-23 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-07-23 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-07-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-07-12 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-07-12 |
Time |
07:45 |
Sent To |
|
|
| Notes |
| 2007-07-12 07:52:32 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)SHOW DIMENSIONS OF THE NEW DOORS, INCLUDING EACH | | | LEAF OF THE DOUBLE DOOR, FBC11-4.13.5, FBC.YOUR | | | RESPONSE THAT THIS BUILDING WAS BUILT PRIOR TO 1997 IS | | | ACKNOWLEDGED; HOWEVER, SEE FBC11-41.1.6.THIS | | | RENOVATION AFFECTS THE USABILITY OF THE SPACE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-03-26 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-03-26 |
Time |
10:44 |
Sent To |
M |
|
| Notes |
| 2007-03-26 10:52:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)THE PRINTED NAME OF THE PERSON SEALING THE | | | DOCUMENT IS TO BE ON EACH SHEET, FAC61G15-23.002. | | | | | | 2.)SEE FBC 11-11-4.1.6(2), ALTERATION TO AN AREA | | | CONTAINING PRIMARY FUNCTION.SEE | | | FBC11-11.4.1.6(2)(2)A.NO ACCESSIBLE FEATURES SHOWN, | | | NO ACCESSIBLE PARKING SHOWN ALTHOUGH PARKING AREA IS | | | SHOWN ON THE PLAN. | | | | | | 3.)THE PLAN REFERENCES FIRE RATED WALLS.NOTE ALL | | | FIRE RATED WALLS ON THE PLAN. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-01-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-25 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-25 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2007-01-25 10:40:36 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBEXISTING BUILDING CODE 2004 | | | FBC R RESIDENTIAL 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | | | | 1.)ENGINEERING REQUIRED.PROVIDE DETAILS, SIGNED, | | | SEALED, AND DATED. | | | | | | 2.)PROVIDE A FLOOR PLAN AND ELEVATION.SCOPE OF WORK | | | IS NOT CLEAR.ONE DETAIL STATES TWO WINDOWS, THE OTHER | | | DOES NOT STATE HOW MANY WINDOWS ARE TO BE CLOSED IN, | | | AND THE PHOTOGRAPH PROVIDED SHOWS FOUR BOARDED WINDOWS. | | | PLANS REQUIRED TO CLEARLY SHOW SCOPE OF WORK AND | | | DETAILS TO SHOW HOW THE MODIFICATION WILL COMPLY WITH | | | FBC CHAPTER 16 (STRUCTURAL LOADS; WIND, ETC.). | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2007-04-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-04-02 |
Time |
14:08 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2007-04-02 |
Time |
14:00 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-06-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-06-21 |
Time |
19:18 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-06-21 |
Time |
19:08 |
Sent To |
B |
|
| Notes |
| 2007-06-21 19:16:47 | ***APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED;PLAN SHEET STAMPED, INITIALED, AND | | | DATED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-04-09 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-04-09 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2007-04-09 12:41:44 | *****DENIED***** | | | | | | | | | 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 04. THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | | NEW BUILDING SUPPLIES & MATERIALS SHALL NOT INTERFERE | | | OR HINDER WITH ACCESS TO OR EGRESS FROM THE PROPERTY OR | | | VICINITY THEREOF (INCLUDING STREETS, ROADS, AND FIRE | | | LANES). | | | | | | 05.IT IS NOT INDICATED WHETHER THE BUILDING IS | | | EQUIPPED WITH A FIRE SPRINKLER SYSTEM.IF THE PROPOSED | | | WALL IMPACTS THE DISTRUBUTION PATTERN OF THE FIRE | | | SPRINKLER SYSTEM, SEPARATE PLANS AND PERMIT WILL BE | | | REQUIRED FOR THE FIRE SPRINKLER REMODEL. | | | | | | 06.SPECIFY THE INTERIOR FINISH CLASSIFICATION FOR THE | | | PROPOSED WALLAS CLASS A, CLASS B, OR CLASS C. | | | | | | 07.ALL REQUIRED EXIT COMPONENTS WITHIN THE STRUCTURE | | | SHALL BE MAINTAINED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM | | | WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-06-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-01 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-01 |
Time |
16:26 |
Sent To |
M |
|
| Notes |
| 2007-06-01 16:26:28 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-03-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-25 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-25 |
Time |
13:14 |
Sent To |
B |
|
| Notes |
| 2007-03-25 13:14:28 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-01-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-25 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-12-15 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2006-12-15 15:03:03 | TO "MISC" BOX#1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-06-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-06-11 |
Time |
14:53 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-06-11 |
Time |
14:53 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-03-28 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-03-28 |
Time |
12:09 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-03-28 |
Time |
12:09 |
Sent To |
E |
|
| Notes |
| 2007-03-28 12:13:18 | *** DENIED *** | | | 1) SEE PLANS PAGE R-2, PLEASE PROVIDE FOR RETURN AIR TO | | | THE SHOWROOM AND WAREHOUSE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|