Plan Review Details - Permit 06120322
Plan Review Stops For Permit 06120322
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-07-23 Cont ID  
Sent By lmartine Date 2007-07-23 Time 11:33 Rev Time 0.00
Received By lmartine Date 2007-07-23 Time 11:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-07-12 Cont ID  
Sent By shill Date 2007-07-12 Time 07:45 Rev Time 0.00
Received By shill Date 2007-07-12 Time 07:45 Sent To  
Notes
2007-07-12 07:52:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)SHOW DIMENSIONS OF THE NEW DOORS, INCLUDING EACH
 LEAF OF THE DOUBLE DOOR, FBC11-4.13.5, FBC.YOUR
 RESPONSE THAT THIS BUILDING WAS BUILT PRIOR TO 1997 IS
 ACKNOWLEDGED; HOWEVER, SEE FBC11-41.1.6.THIS
 RENOVATION AFFECTS THE USABILITY OF THE SPACE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-26 Cont ID  
Sent By shill Date 2007-03-26 Time 10:44 Rev Time 0.00
Received By shill Date 2007-03-26 Time 10:44 Sent To M
Notes
2007-03-26 10:52:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT IS TO BE ON EACH SHEET, FAC61G15-23.002.
  
 2.)SEE FBC 11-11-4.1.6(2), ALTERATION TO AN AREA
 CONTAINING PRIMARY FUNCTION.SEE
 FBC11-11.4.1.6(2)(2)A.NO ACCESSIBLE FEATURES SHOWN,
 NO ACCESSIBLE PARKING SHOWN ALTHOUGH PARKING AREA IS
 SHOWN ON THE PLAN.
  
 3.)THE PLAN REFERENCES FIRE RATED WALLS.NOTE ALL
 FIRE RATED WALLS ON THE PLAN.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-25 Cont ID  
Sent By shill Date 2007-01-25 Time 10:30 Rev Time 0.00
Received By shill Date 2007-01-25 Time 10:30 Sent To  
Notes
2007-01-25 10:40:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)ENGINEERING REQUIRED.PROVIDE DETAILS, SIGNED,
 SEALED, AND DATED.
  
 2.)PROVIDE A FLOOR PLAN AND ELEVATION.SCOPE OF WORK
 IS NOT CLEAR.ONE DETAIL STATES TWO WINDOWS, THE OTHER
 DOES NOT STATE HOW MANY WINDOWS ARE TO BE CLOSED IN,
 AND THE PHOTOGRAPH PROVIDED SHOWS FOUR BOARDED WINDOWS.
 PLANS REQUIRED TO CLEARLY SHOW SCOPE OF WORK AND
 DETAILS TO SHOW HOW THE MODIFICATION WILL COMPLY WITH
 FBC CHAPTER 16 (STRUCTURAL LOADS; WIND, ETC.).
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2007-04-02 Cont ID  
Sent By btrobaug Date 2007-04-02 Time 14:08 Rev Time 0.33
Received By btrobaug Date 2007-04-02 Time 14:00 Sent To FIRE
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-06-21 Cont ID  
Sent By mawillia Date 2007-06-21 Time 19:18 Rev Time 0.00
Received By mawillia Date 2007-06-21 Time 19:08 Sent To B
Notes
2007-06-21 19:16:47***APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEET STAMPED, INITIALED, AND
 DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-09 Cont ID  
Sent By mawillia Date 2007-04-09 Time 12:41 Rev Time 0.00
Received By mawillia Date 2007-04-09 Time 12:15 Sent To  
Notes
2007-04-09 12:41:44*****DENIED*****
  
  
 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04. THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING SUPPLIES & MATERIALS SHALL NOT INTERFERE
 OR HINDER WITH ACCESS TO OR EGRESS FROM THE PROPERTY OR
 VICINITY THEREOF (INCLUDING STREETS, ROADS, AND FIRE
 LANES).
  
 05.IT IS NOT INDICATED WHETHER THE BUILDING IS
 EQUIPPED WITH A FIRE SPRINKLER SYSTEM.IF THE PROPOSED
 WALL IMPACTS THE DISTRUBUTION PATTERN OF THE FIRE
 SPRINKLER SYSTEM, SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED FOR THE FIRE SPRINKLER REMODEL.
  
 06.SPECIFY THE INTERIOR FINISH CLASSIFICATION FOR THE
 PROPOSED WALLAS CLASS A, CLASS B, OR CLASS C.
  
 07.ALL REQUIRED EXIT COMPONENTS WITHIN THE STRUCTURE
 SHALL BE MAINTAINED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 16:26 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 16:26 Sent To M
Notes
2007-06-01 16:26:28TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-25 Cont ID  
Sent By adarroug Date 2007-03-25 Time 13:14 Rev Time 0.00
Received By adarroug Date 2007-03-25 Time 13:14 Sent To B
Notes
2007-03-25 13:14:28TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-25 Cont ID  
Sent By shill Date 2007-01-25 Time 10:42 Rev Time 0.00
Received By shill Date 2006-12-15 Time 15:02 Sent To  
Notes
2006-12-15 15:03:03TO "MISC" BOX#1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-11 Cont ID  
Sent By tgordon Date 2007-06-11 Time 14:53 Rev Time 0.25
Received By tgordon Date 2007-06-11 Time 14:53 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-28 Cont ID  
Sent By tgordon Date 2007-03-28 Time 12:09 Rev Time 0.25
Received By tgordon Date 2007-03-28 Time 12:09 Sent To E
Notes
2007-03-28 12:13:18*** DENIED ***
 1) SEE PLANS PAGE R-2, PLEASE PROVIDE FOR RETURN AIR TO
 THE SHOWROOM AND WAREHOUSE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.