Plan Review Details - Permit 06120212
Plan Review Stops For Permit 06120212
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-26 Cont ID  
Sent By btrobaug Date 2007-01-30 Time 13:32 Rev Time 0.00
Received By shill Date 2007-01-26 Time 12:12 Sent To E
Notes
2007-01-26 12:16:42SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FAC61G1-16.003,004.
  
 2.)HOW HAVE YOU ARRIVED AT THE CORNER ZONE PRESSURES
 FOR THE ROOF?FBC16.PROVIDE CALCULATIONS.
  
 3.)PRODUCT APPROVALS REQUIRED FOR THE ROOF.CHOOSE
 THE APPROVED ASSEMBLY YOU ARE USING AND SPECIFY
 ENHANCED FASTENING FOR ZONES 2 AND 3.IF PRODUCT
 APPROVALS ARE NOT PROPERLY SUBMITTED AND REVIEWED PRIOR
 TO PERMIT ISSUANCE, A SEPARATE PERMIT WILL BE REQUIRED.
  
  
 4.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-30 Cont ID  
Sent By btrobaug Date 2007-01-30 Time 13:41 Rev Time 0.50
Received By btrobaug Date 2007-01-30 Time 13:19 Sent To PC
Notes
2007-01-30 13:31:10 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON THE
 PLANS, MUST SIGN AND SEAL THE PLAN PER
 481.221(1)(B)FS.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 13:34 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 13:34 Sent To B
Notes
2006-12-18 13:35:10TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-30 Cont ID  
Sent By shill Date 2007-01-30 Time 13:41 Rev Time 0.00
Received By btrobaug Date 2006-12-07 Time 15:03 Sent To PC
Notes
2006-12-07 15:03:56TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-16 Cont ID  
Sent By mmclean Date 2006-12-16 Time 10:18 Rev Time 0.00
Received By mmclean Date 2006-12-16 Time 10:18 Sent To I
Notes
2006-12-16 10:31:53DENIED,
 1. SHALL PROVIDE A COPY OF SURVEY SHOWING THE SETBACKS
 OF THE EXISTING STRUCTURE.
 2. SITEPLAN SUBMITTED DOES NOT PROVIDE ALL SETBACKS OF
 THE EXISTING STRUCTURE (SIDE) AND IDENTIFY THE PROPERTY
 AS A CORNER LOT.
 3. PLEASE SUBMIT SURVEYS (TWO COPIES) SHOWING THE
 PROPOSED WORK WITH SETBACKS OF EXISTING AND PROPOSED.
 4. THE SETBACKS FOR SF7 IS 5FT MINIMUM ON SIDE, BOTH
 SIDE TOTALLING 15FT, CORNER 12.5 FT FROM THE SIDE.
 5. THE PROPOSED COVERED PATIO IS NOT MEETING THE SIDE
 SETBACK.
 6. PLEASE SHOW ACCESS TO THE COVERED PATIO FROM
 EXISTING ASPHALT DRIVEWAY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720