Plan Review Details - Permit 06120209
Plan Review Stops For Permit 06120209
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-10-22 Cont ID  
Sent By mjacobs Date 2008-10-22 Time 07:48 Rev Time 0.00
Received By mjacobs Date 2008-10-22 Time 06:51 Sent To PC
Notes
2008-10-22 07:48:37BUILDING PLAN REVIEW
 PERMIT: 06120209
 ADD: 1325 9TH ST.
 CONT: OWNER
 TEL: (561)805-7240
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: ENERGY CALCS SUBMITTAL.
 ACTION: DENIED
  
 1) THE ENERGY CALCULATION SHEETS SUBMITTED REFERENCE
 THE 2001 FBC. ALLL PLANS, SPECIFICATIONS, REPORTS AND
 OTHER INFORMATION SUBMITTED AFTER OCTOBER, 1, 2004
 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 2) FBC 13-103.1.2 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-05 Cont ID  
Sent By mjacobs Date 2008-08-05 Time 11:45 Rev Time 0.00
Received By mjacobs Date 2008-08-05 Time 10:53 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-28 Cont ID  
Sent By mjacobs Date 2007-11-28 Time 15:35 Rev Time 0.00
Received By mjacobs Date 2007-11-14 Time 17:15 Sent To M
Notes
2007-11-15 15:48:47BUILDING PLAN REVIEW
 PERMIT:06120209
 ADD:1325 9TH STREET
 CONT:JUSTINA A. MCCRAY
 TEL: (561)805-7255
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)OK
 2)OK
 3)OK
 4)OK
 5)OK
  
 6)NOTED: INDICATE WHICH ITEMS OR SYSTEMS WILL BE USED
 FROM EACH PRODUCT APPROVAL, INCLUDING THE FASTENER
 SPACING OR THE STORM PANELS.
  
 7)OK
 8)OK
 9)OK
 10)OK
 11) OK
  
 NEW***************
  
 12)R802.1.6TRUSS DESIGN DRAWINGS PREPARED IN
 CONFORMANCE WITH SEC. R802.1.6.1 SHALL BE PROVIDED TO
 THE BUILDING OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION.
  
 A) INDICATE THE TYPE OF INSULATION AT THE EXTERIOR
 WALLS. THE DRAWINGS SHOW R-19 INSULATION FOR THE ATTIC
 AND THE ENERGY CALCULATIONS SHOW R-30 WHIC IS IT?
 CLARIFY.
 B)THE DRAWINGS CALL FOR 2500PSI CONCRETE FOOTINGS AND
 THE SOIL REPORT CALLS FOR 200PSI. CLARIFY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-14 Cont ID  
Sent By mjacobs Date 2007-07-14 Time 09:00 Rev Time 0.00
Received By mjacobs Date 2007-07-14 Time 05:06 Sent To PC
Notes
2007-07-14 08:59:57BUILDING PLAN REVIEW
 PERMIT:06120209
 ADD:1325 9TH STREET
 CONT:JUSTINA A. MCCRAY
 TEL: (561)805-7255
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)OK
  
 3)OK
  
 4)OK
  
 5)OK
  
 6)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE THE PRODUCT APPROVALS
 FOR THE HURRICANE PROTECTION OF THE GLASS BLOCKS.
  
 7)OK
  
 8)OK
  
 9)OK
  
 10)OK
  
 11) OK
  
 NEW***************
  
 12)R802.1.6TRUSS DESIGN DRAWINGS PREPARED IN
 CONFORMANCE WITH SEC. R802.1.6.1 SHALL BE PROVIDED TO
 THE BUILDING OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-08 Cont ID  
Sent By mjacobs Date 2007-02-08 Time 14:56 Rev Time 0.00
Received By mjacobs Date 2007-02-08 Time 08:42 Sent To PC
Notes
2007-02-08 09:44:29BUILDING PLAN REVIEW
 PERMIT:06120209
 ADD:1325 9TH STREET
 CONT:JUSTINA A. MCCRAY
 TEL: (561)805-7255
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3)THE EMERGENCY EGRESS WINDOWS SHALL REFER TO
 SECTION R310 OF THE 2004 RESIDENTIAL BUILDING CODE OR
 THE 2004 FBC. NOT THE 2001 FBC.
  
 4)WPB AMENDMENTS 108.3*THE VALUE IS TO LOW. IF IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHNICAL,
 INTERIOR FINISH, NORMAL SITE WORK, ARCHITECTURAL AND
 DESIGN FEES EXCLUDING LAND.OUR VALUATION REFERENCE IS
 ICC (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES.
  
 5)R807.1 ATTIC ACCESS. IN BUILDINGS WITH COMBUSTIBLE
 CEILING OR ROOF CONSTRUCTION, AN ATTIC ACCESS OPENING
 SHALL BE PROVIDED TO ATTIC AREAS THAT EXCEED 30 SQUARE
 FEET AND HAVE A VERTICAL HEIGHT OF 30 INCHES OR
 GREATER.
 THE ROUGH-FRAME OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES AND SHALL BE LOCATED IN A HALLWAY
 OR OTHER REDAILY ACCESSIBLE LOCATION. A 30-INCH MINIMUM
 UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT SOME POINT ABOVE THE ACCESS OPENING. SEE
 SECTION M 1305.1.3 FOR ACCESS REQUIREMENTS WHERE
 MECHANICAL EQUIPMENT IS LOCATED IN ATTICS.
  
 6)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE THE PRODUCT APPROVALS
 FOR THE GLASS BLOCKS.
  
 7)M1506.2EXHAUST AIR FROM BATHROOMS AND TIOLET
 ROOMS SHALL NOT BE RECIRCULATED WITHIN A RESIDENCE OR
 TO ANOTHER DWELLING UNIT. MECHANICAL EXHAUST CAPACITY
 FOR BATHROOMS AND TOILET ROOMS SHALL BE NO LESS THAN 50
 CFM INTERMITTENT OR 20 CFM CONTINOUS.
  
 8)R308.4 (5)GLAZING IN DOORS AND ENCLOSURES FOR HOT
 TUBS, WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND
 SHOWERS. GLAZING IN ANY PART OF A BUILDING WALL
 ENCLOSING THESE XOMPARTMENTS WHERE THE BOTTOM EXPOSED
 EDGE OF THE GLAZING IS LESS THAN 60 INCHES MEASURED
 VERTICALLY ABOVE THE STANDING OR WALKING SURFACE.
  
 9)WPB AMENDMENTS 106.1.3*THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 COMFORMITY TO ITS RECORD RETENTION PROGRAM,THIS
 POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. THE SEAL ON THE DRAWINGS ARE ILLEGIBLE.
 61G15-23.002A PROFESSIONAL ENGINER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS, SEPCIFICATIONS,
 REPORTS, FINAL BID COCUMENTS OR OTHER DOCUMENTS
 PREPARED OR ISSUED BY SAID REGISTRANT AND BEING FILED
 FOR PUBLIC RECORD.
  
 10)PROVIDE AN INTERIOR ELEVATION SHOWING ALL
 DIMENTIONS OF THE LIVING SPACE CEILING INCLUDED. HOW
 WILL THE EXISTING STRUCTURE BE SUPPORTED WHEN THE
 EXTERIOR WALL AT THE KITCHEN AREA IS REMOVED. SHOW IN
 DETAIL HOW THIS AREA WILL BE SUPPORTED.
  
 11)
 ) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-08-05 Cont ID  
Sent By btrobaug Date 2008-08-05 Time 12:19 Rev Time 0.00
Received By btrobaug Date 2008-08-05 Time 12:19 Sent To B
Notes
2008-08-05 12:19:46 
  
 MOVED INTERIOR PANEL./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-11-08 Cont ID  
Sent By btrobaug Date 2007-11-08 Time 12:22 Rev Time 0.00
Received By btrobaug Date 2007-11-08 Time 12:00 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-03 Cont ID  
Sent By btrobaug Date 2007-07-03 Time 08:33 Rev Time 0.00
Received By btrobaug Date 2007-07-03 Time 07:28 Sent To P
Notes
2007-07-03 08:20:08 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE DISCONNECT LOCATION ON THE RISER IS INCORRECT AN
 DISCONNECTS NOTHING. PLEASE REDRAW AND INDICATE THE
 CONDUIT AND WIRE SIZES. SEE 250.122 AND INSTALL THE
 EQUIPMENT GROUND PER SAME (AFTER THE DISCONNECT AND RUN
 TO PANEL).
  
 2} THERE IS ONLY ONE A/C SYSTEM ON THE PANEL SCHEDULE,
 TWO IN THE CALCULATIONS. PLEASE CORRELATE.
  
 3} THE ELECTRICAL PANEL LOCATION IN THE KITCHEN WOULD
 NOT COMPLY WITH THE 3' CLEARANCE REQUIREMENT OF 110.26,
 WITH RESPECT TO THE PENINSULAR.
  
 4}BATH CIRCUIT REQUIRED TO HAVE A 20 AMP CIRCUIT PER
 210.11(C) (3), INCLUDE IN THE PANEL SCHEDULE.
  
 5} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1)
 AND 210.52 (A) (2), SEE DINING ROOM AND NEW BEDROOM.
 NOTE THE DINING ROOM MUST BE ON A SMALL APPLIANCE
 CIRCUIT PER 210.52(B)(1).
  
 6} THE ISLAND AND PENINSULAR RECEPTACLES MUST BE GFCI
 PROTECTED PER 210.8(A)(6), INDICATE ON PLAN..
  
 7}A RECEPTACLE IS REQUIRED FOR THE SERVICING OF THE
 CONDENSING UNITS PER 210.63. NONE IS INDICATED ON THE
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-21 Cont ID  
Sent By btrobaug Date 2006-12-21 Time 11:11 Rev Time 0.50
Received By btrobaug Date 2006-12-21 Time 10:35 Sent To P
Notes
2006-12-21 11:10:59 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} SHOW THE PHYSICAL LOCATION OF ALL SERVICE EQUIPMENT
 ON THE PLAN. 215.5. PER THE RISER DIAGRAM IT WOULD
 APPEAR THAT A 200 AMP DISCONNECT WOULD BE REQUIRED AT
 THE METER PER 230.70 (A) (1).
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-10-23 Cont ID  
Sent By shill Date 2008-10-23 Time 16:03 Rev Time 0.00
Received By shill Date 2008-10-23 Time 16:03 Sent To B
Notes
2008-10-23 16:04:04TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-10-20 Cont ID  
Sent By adarroug Date 2008-10-20 Time 08:37 Rev Time 0.00
Received By adarroug Date 2008-10-20 Time 08:37 Sent To B
Notes
2008-10-20 08:37:47TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-08-14 Cont ID  
Sent By adarroug Date 2008-08-14 Time 11:21 Rev Time 0.00
Received By adarroug Date 2008-08-14 Time 11:21 Sent To M
Notes
2008-08-14 11:22:18TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-07-31 Cont ID  
Sent By adarroug Date 2008-07-31 Time 10:57 Rev Time 0.00
Received By adarroug Date 2008-07-31 Time 10:57 Sent To M
Notes
2008-07-31 10:57:44TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-04 Cont ID  
Sent By adarroug Date 2007-12-04 Time 11:50 Rev Time 0.00
Received By adarroug Date 2007-12-04 Time 11:50 Sent To M
Notes
2007-12-04 11:50:58TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 09:12 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 09:11 Sent To Z
Notes
2007-11-06 09:12:22TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-26 Cont ID  
Sent By adarroug Date 2007-06-26 Time 11:34 Rev Time 0.00
Received By adarroug Date 2007-06-26 Time 11:33 Sent To Z
Notes
2007-06-26 11:34:23TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 13:05 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 13:05 Sent To E
Notes
2006-12-18 13:06:01TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-02-08 Time   Rev Time 0.00
Received By adarroug Date 2006-12-07 Time 15:09 Sent To  
Notes
2006-12-07 15:11:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-10-29 Cont ID  
Sent By tgordon Date 2008-10-29 Time 13:47 Rev Time 0.40
Received By tgordon Date 2008-10-29 Time 13:47 Sent To  
Notes
2008-10-29 13:48:08REVISION TO ENERGY CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-09-08 Cont ID  
Sent By tgordon Date 2008-09-08 Time 11:58 Rev Time 0.15
Received By tgordon Date 2008-09-08 Time 11:58 Sent To  
Notes
2008-09-08 11:59:37RE-STAMP

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-08-14 Cont ID  
Sent By tgordon Date 2008-08-14 Time 14:22 Rev Time 0.30
Received By tgordon Date 2008-08-14 Time 14:22 Sent To  
Notes
2008-08-14 14:23:03REVISION TO MECH. PLAN AND COOLING LOAD CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-08-04 Cont ID  
Sent By tgordon Date 2008-08-04 Time 13:51 Rev Time 0.45
Received By tgordon Date 2008-08-04 Time 13:50 Sent To B
Notes
2008-08-04 13:58:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN.
 *** DENIED ***
  
 1) THE COOLING LOAD CALCULATIONS ON FILE ARE CALLING
 FOR 20,232 TOTAL COOLING BTU'S, THE REVISED MECHANICAL
 PLAN EQUIPMENT SCHEDULE SHOWS 29,200 TOTAL COOLING
 BTU'S, THE PLANS CAN ONLY CALL FOR 15% MORE TOTAL
 COOLING BTU'S THAN THE COOLING LOAD CALCULATIONS, PER
 2004 FBC 13-607.1.ABC.1.1. A 2.5 TON A/C SYSTEM IS TO
 LARGE PER THE COOLING LOAD CAL'S. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-12-04 Cont ID  
Sent By tgordon Date 2007-12-04 Time 14:00 Rev Time 0.30
Received By tgordon Date 2007-12-04 Time 14:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-11-28 Cont ID  
Sent By tgordon Date 2007-11-28 Time 10:42 Rev Time 0.30
Received By tgordon Date 2007-11-28 Time 10:42 Sent To  
Notes
2007-11-28 11:21:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) INFORMATION ON MECHANICAL PLAN SHOW TOTAL COOLING AT
 22,600 BTU'S FOR THIS 2.5 TON SYSTEM IS INCORRECT. SEE
 ATTACHED ARI CERTIFICATE FOR THAT SYSTEM SHOWS THE
 TOTAL COOLING IS 27,200 BTU'S. AS NOTED IN LAST REVIEW
 11-13-07 NOTE #1. THE COOLING LOAD CALCULATIONS ARE
 CALLING FOR 20,232 TOTAL BTU'S AND THE CORRECT TOTAL
 BTU,S FOR THE SYSTEM LISTED ON THE MECHANICAL PLAN IS
 27,200 (SEE ATTACHED ARI LISTING). THE MECHANICAL PLANS
 CAN ONLY CALL FOR 15% MORE TOTAL BTU'S THAN THE COOLING
 LOAD CAL'S, SEE FBC 13-607.1.ABC.1.1. PLEASE CORRECT.
  
 2) TWO DIFFERENT SIZE MECHANICAL PLANS WERE SUBMITTED,
 PLEASE INDICATE WHICH PLAN IS FOR REFERENCE AND NOT TO
 BE USED.
  
 3) BE ADVISED ONE COPY OF THE COOLING LOAD
 CALCULATIONS, ENERGY CAL'S. AND MECHANICAL PLANS HAVE
 BEEN RETAINED FOR OUR RECORDS, PLEASE PROVIDE TWO
 COPIES WHEN RE-SUBMITTING.
  
 4) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-11-13 Cont ID  
Sent By tgordon Date 2007-11-13 Time 09:01 Rev Time 0.30
Received By tgordon Date 2007-11-13 Time 09:01 Sent To B
Notes
2007-11-13 09:09:36PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE COOLING LOAD CALCULATIONS ARE CALLING FOR 20,232
 TOTAL BTU'S AND THE TOTAL BTU,S LISTED ON THE
 MECHANICAL PLAN IS 27,200 (SEE ATTACHED ARI LISTING).
 THE MECHANICAL PLANS CAN ONLY CALL FOR 15% MORE TOTAL
 BTU'S THAN THE COOLING LOAD CAL'S, SEE FBC
 13-607.1.ABC.1.1. PLEASE CORRECT.
  
 2) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND
 CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE
 W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-13 Cont ID  
Sent By tgordon Date 2007-07-13 Time 10:54 Rev Time 0.25
Received By tgordon Date 2007-07-13 Time 10:54 Sent To B
Notes
2007-07-13 11:04:23*** DENIED ***
  
 1) AS NOTED IN LAST REVIEW 12-22-07 NOTE #1. PLEASE
 SHOW AN A/C EQUIPMENT LISTING ON THE MECHANICAL PLANS.
  
 2) TWO DIFFERENT SETS OF THE COOLING LOAD CALCULATIONS
 HAVE BEEN SUBMITTED, PLEASE REMOVE ONE SET.
  
 3)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING
 FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-22 Cont ID  
Sent By tgordon Date 2006-12-22 Time 16:39 Rev Time 0.30
Received By tgordon Date 2006-12-22 Time 16:39 Sent To B
Notes
2006-12-22 16:42:18*** DENIED ***
 1) PLEASE SHOW AN A/C EQUIPMENT LISTING ON THE
 MECHANICAL PLANS.
  
 2) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-11-13 Cont ID  
Sent By mperson Date 2007-11-13 Time 07:50 Rev Time 0.00
Received By mperson Date 2007-11-13 Time 07:50 Sent To M
Notes
2007-11-13 07:55:05****************PROVISO****************
 (A) 708.3.5 BUILDING DRAIN AND BUILDING SEWER
 JUNCTION. THERE SHALL BE A TWO-WAY CLEANOUT NEAR THE
 JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER.
  
 (B) 708.7 MINIMUM SIZE. CLEANOUTS SHALL BE THE SAME
 NOMINAL SIZE AS THE PIPE.
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3 INCH.
 THEY SERVE UP TO 4 INCHES (102MM)
  
 (C) 708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL
 CLEANOUTS.
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE 4' A.F.F.
  
 (D) DISHWASHER DRAIN PER FLOOR PLAN LAYOUT IS LOCATED
 AT THE OTHER END OF TRIPLE COMPARTMENT KITCHEN SINK.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-13 Cont ID  
Sent By mperson Date 2007-07-13 Time 09:48 Rev Time 0.45
Received By mperson Date 2007-07-13 Time 09:48 Sent To M
Notes
2007-07-13 09:51:16DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. SHEET A1: THE RESUBMITTED SANITARY RISER DIAGRAM
 STILL DOES NOT REFLECT THE FLOOR PLAN ON SHEET A2.
 PLEASE REFERENCE THE FOLLOWING RED LINE CORRECTIONS ON
 SHEET A1 SANITARY RISER DIAGRAM THAT REFLECTS THE FLOOR
 PLAN AND CORRECT THEM FOR THE NEXT RESUBMITTAL.
  
 A} LAV IN MASTER BATH IS BEING INDICATED IN THE
 WRONG PLACE.
 B} LAV IN TUB BATH IS BEING INDICATED IN THE
 WRONG PLACE.
 C} WASHING MACHINE IS BEING INDICATED IN THE
 WRONG PLACE.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-22 Cont ID  
Sent By mperson Date 2006-12-22 Time 14:04 Rev Time 1.25
Received By mperson Date 2006-12-22 Time 14:03 Sent To M
Notes
2006-12-22 14:31:58DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A2 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN, PLEASE REFERENCE THE ATTACHED CORRECTED
 SANITARY RISER DIAGRAM TO THE PLUMBING COMMENTS
 REFLECTING THE FLOOR PLAN THAT IS CODE COMPLIANT.
  
 2. PER FBC-2004 PLUMBING THE FOLLOWING CORRECTIONS ARE
 REQUIRED FOR THE WASHING MACHINE.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANPIPE ON THE
 RESUBMITTED DRAWINGS.
 (C) 708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL
 CLEANOUTS, ON RESUBMITTED DRAWINGS PLEASE INDICATE
 CLEANOUT FOR WASHING MACHINE AT 4 FEET ABOVE FINNISH
 FLOOR (4' AFF).
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-11-08 Cont ID  
Sent By choops Date 2007-11-08 Time 08:12 Rev Time 0.00
Received By choops Date 2007-11-08 Time 08:12 Sent To E
Notes
2007-11-08 08:13:23***APPROVED - RESUB #2***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-06-26 Cont ID  
Sent By choops Date 2007-06-26 Time 16:00 Rev Time 0.00
Received By choops Date 2007-06-26 Time 16:00 Sent To E
Notes
2007-06-26 16:03:09***FAILED***
  
  
 1)PREVIOUS COMMENT NOT ADDRESSED.STILL NEED TO SHOW
 THE SETBACK DIMENSION FROM PROPOSED A/C UNIT TO
 PROPERTY LINE. (NOTE: MAY NOT BE CLOSER THAN 1' TO THAT
 PARTICULAR SIDE PROPERTY LINE).
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-16 Cont ID  
Sent By mmclean Date 2006-12-16 Time 10:35 Rev Time 0.00
Received By mmclean Date 2006-12-16 Time 10:35 Sent To I
Notes
2006-12-16 10:39:30DENIED,
 1. SITEPLANS SUBMITTED DOES NOT SHOW THE LOCATION OF
 A/C UNIT, PLEASE SHOW THE A/C UNIT ON THE TWO COPIES OF
 SITEPLANS WITH SETBACKS.
 NOTE: THE PROPOSED A/C SHALL NOT BE CLOSER THAN 6FT
 FROM SIDE PROPERTY LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720