Plan Review Stops For Permit 06120206
Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2007-02-15 Cont ID  
Sent By rchokshi Date 2007-02-15 Time 10:56 Rev Time 0.00
Received By rchokshi Date 2007-02-15 Time 10:56 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-02-09 Cont ID  
Sent By rchokshi Date 2007-02-09 Time 16:51 Rev Time 0.00
Received By rchokshi Date 2007-02-09 Time 16:49 Sent To  
Notes
2007-02-09 16:51:17SOME OF THE DRAWING SHEETS ARE NOT SEALED & SIGNEDBY
 P E,

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2007-02-09 Cont ID  
Sent By rchokshi Date 2007-02-09 Time 09:31 Rev Time 0.00
Received By rchokshi Date 2007-02-09 Time 09:31 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-12-21 Cont ID  
Sent By rchokshi Date 2006-12-21 Time 14:08 Rev Time 0.00
Received By rchokshi Date 2006-12-21 Time 14:00 Sent To  
Notes
2006-12-21 14:08:36PLEASE PROVIDE FOLLOWING INFO:
  
 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,GEOTECHNICAL
 REPORT ETC.
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL.
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-09 Cont ID  
Sent By adarroug Date 2007-02-09 Time 15:49 Rev Time 0.00
Received By adarroug Date 2007-02-09 Time 15:49 Sent To Z
Notes
2007-02-09 15:50:09TO "KDFREEDMAN" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 12:50 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 12:50 Sent To ENG
Notes
2007-02-08 12:50:58TO "ENG" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-06 Cont ID  
Sent By adarroug Date 2007-02-06 Time 16:41 Rev Time 0.00
Received By adarroug Date 2007-02-06 Time 16:41 Sent To Z
Notes
2007-02-06 16:42:46TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-12 Cont ID  
Sent By adarroug Date 2007-01-12 Time 13:18 Rev Time 0.00
Received By adarroug Date 2006-12-07 Time 14:56 Sent To  
Notes
2006-12-07 14:56:36TO "ENG" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2007-02-09 Cont ID  
Sent By kdfreema Date 2007-02-09 Time 16:24 Rev Time 0.00
Received By kdfreema Date 2007-02-09 Time 16:24 Sent To I
Notes
2007-02-09 16:26:08PROVISO:
  
 THIS PERMIT IS FOR UNDERGROUND WORK ONLY; NO VERTICAL
 CONSTRUCTION SHALL TAKE PLACE UNTIL THE PLAT PERTAINING
 TO THIS PROPERTY IS RECORDED.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-02-07 Cont ID  
Sent By kdfreema Date 2007-02-07 Time 11:06 Rev Time 0.00
Received By kdfreema Date 2007-02-07 Time 11:06 Sent To  
Notes
2007-02-07 12:04:58NO VERTICAL IMPROVEMENTS MAY TAKE PLACE UPON THE
 PROPERTY UNTIL THE PLAT HAS BEEN RECORDED. WHEN
 RESUBMITTING, PLEASE REVISE THE SCOPE OF THE PERMIT TO
 EXCLUDE ALL VERTICAL IMPROVEMENTS.
 PLEASE CONTACT KELLY FREEMAN, PLANNER AT 561-822-1435
 WITH ANY QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-12 Cont ID  
Sent By kdfreema Date 2007-01-12 Time 11:59 Rev Time 0.00
Received By kdfreema Date 2007-01-12 Time 11:59 Sent To  
Notes
2007-01-12 13:04:55**FAILED**
  
 AS SUBMITTED, THE SITE PLAN IS NOT CONSISTENT WITH THE
 APPROVED SITE PLAN. SPECIFICALLY, THE WIDTH OF THE
 SIDEWALK ALONG THE SOUTH BOUNDARY HAS BEEN REDUCED FROM
 EIGHT FEET TO FIVE FEET. ADDITIONALLY, THE SIDEWALK
 CONFIGURATION SURROUNDING THE IHOP RESTAURANT HAS BEEN
 ALTERED. THESE CHANGES WILL REQUIRE A MINOR PLANNED
 DEVELOPMENT AMENDMENT.
  
 PER ORDINANCE NO. 3847-05, A PLAT OF THE PROPERTY MUST
 BE RECORDED. THAT PROCESS MUST BE COMPLETE BEFORE THE
 PERMIT CAN BE APPROVED BY ZONING.
  
 PARKING SPACE STRIPING DETAILS AS SHOWN ON SHEET PV-3
 DO NOT MEET THE REQUIREMENTS OF THE ZONING CODE AS
 FOUND IN SECTION 94-485. NO STRIPING OF ANY PARKING OR
 VEHICULAR CIRCULATION AREAS SHALL TAKE PLACE AS PART OF
 THIS PERMIT.
  
 PLEASE CALL KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH ANY QUESTIONS.