Plan Review Details - Permit 06120139
Plan Review Stops For Permit 06120139
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-05-15 Cont ID  
Sent By lmartine Date 2007-05-15 Time 15:41 Rev Time 0.00
Received By lmartine Date 2007-05-15 Time 15:41 Sent To  
Notes
2007-05-15 16:12:37REVISION FOR LOAD BEARING WALL AND SERVICE PLATFORM
 OKLM

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-04-02 Cont ID  
Sent By shill Date 2007-04-02 Time 12:28 Rev Time 0.00
Received By shill Date 2007-04-02 Time 12:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-03-26 Cont ID  
Sent By shill Date 2007-03-26 Time 14:47 Rev Time 0.00
Received By shill Date 2007-03-26 Time 14:47 Sent To  
Notes
2007-03-26 14:49:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)SEE FBC303; YOU HAVE DECLARED AN INCORRECT
 OCCUPANCY SUBCLASSIFICATION.PLANS APPEAR CODE
 COMPLIANT OTHERWISE, BUT PLEASE REVISE TO REFLECT
 CORRECT OCCUPANCY SUBCLASSIFICATION.
  
 2.)SEE ELECTRIC COMMENTS IN REGARDS TO ENERGY CALCS.
 FINAL ENERGY CALCS MUST BE REVIEWED BY BUILDING PRIOR
 TO PERMIT ISSUANCE.
  
 3.)ENERGY CALCS STATE 2032 SF, PLANS STATE 2160.THE
 TOTAL SF AREA SHOULD BE THE SAME.
  
 4.)SEE ATTACHED FS553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-21 Cont ID  
Sent By shill Date 2007-02-21 Time 09:39 Rev Time 0.00
Received By shill Date 2007-02-21 Time 09:39 Sent To  
Notes
2007-02-21 09:42:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE FBC303; YOU HAVE DECLARED AN INCORRECT
 OCCUPANCY SUBCLASSIFICATION.PLANS APPEAR CODE
 COMPLIANT OTHERWISE, BUT PLEASE REVISE TO REFLECT
 CORRECT OCCUPANCY SUBCLASSIFICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-08 Cont ID  
Sent By shill Date 2007-01-08 Time 07:59 Rev Time 0.00
Received By shill Date 2007-01-08 Time 07:36 Sent To  
Notes
2007-01-08 08:25:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 1.)INCLUDE FBC 2004 EXISTING BUILDING CODE IN THE
 GOVERNING CODE.
  
 2.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 3.)PROJECT IS TO COMPLY WITH FBC EB CHAPTER 8, CHANGE
 OF OCCUPANCY.
  
 4.)DECLARE THE OCCUPANCY OF THE ADJACENT TENANT.
 CORRECT OCCUPANCY SEPARATION FBC TABLE 302.3.2 CANNOT
 BE DETERMINED WITHOUT THIS INFORMATION.
  
 5.)BUILDING TYPE IIIB WAS DECLARED.SEE FBC TABLE
 601, 2 HOUR MINIMUM FOR EXTERIOR WALLS REQUIRED.
 PROVIDE A SITE PLAN, SHOWING DISTANCE FROM THE PROPERTY
 LINE.SEE FBC TABLE 602 AND INDICATE MINIMUM EXTERIOR
 WALL FIRE RATING REQUIRED, FBC 704.8 REGARDING
 OPENINGS.PROVIDE DETAILS FOR FIRE RATED WALLS.
  
 6.)AS THIS IS A CHANGE OF OCCUPANCY, COMPLIANCE WITH
 FBC TABLE 503.PROVIDE TOTAL AREA OF THE BUILDING.
  
 7.)DECLARE OCCUPANT LOAD, FBC 3.PLANS STATE "NUMBER
 OF SEATS".SEE FBC 1004, KITCHEN AREA IS TO ALSO BE
 INCLUDED IN OCCUPANT LOAD.
  
 8.)SHEET 1.0 SHOWS REFERENCE TO DETAILS ON SHEETS
 1.2, THIS SHEET IS NOT IN THE PLAN.
  
 9.)SHEET 1.0 SHOWS REFERENCE TO A DETAIL ON SHEET
 1.1, THE DETAIL IS NOT ON THE PLAN.
  
 10.)INTERIOR PARTITION DETAIL, 1.0, SHOWS FIRESTOP
 TYP IN THE TEXT, NOTHING SHOWN GRAPHICALLY.
  
 11.)SHEET 1.0 STATES EXISTING BRICK 2 HR DEMISING
 WALL, STATES ONLY "13" BRICK 2 HR".PROVIDE MORE
 INFORMATION IN REGARDS TO THE WALL FBC TABLE 720.1(2).
  
 12.)THERE APPEARS TO BE A WALL FROM THE ADJACENT
 TENANT WHICH PENETRATES THE EXISTING DEMISING WALL.
 PROVIDE INFORMATION IN REGARDS TO THIS WALL; SEPARATION
 TO BE MAINTAINED.IS THE SAME DETAIL TO BE USED?WALL
 GRAPHICALLY DOES NOT APPEAR TO BE THE SAME WALL AS THE
 EXISTING DEMISING WALL, CAN UL U408 STILL BE USED?IF
 NOT, PROVIDE A DETAIL FOR THIS WALL.
  
 13.)PROVIDE ALL INFORMATION REQUIRED FOR UL U408 ON
 SHEET 1.THE DETAIL PROVIDED IS INCOMPLETE.
  
 14.)SHOW ACCESSIBLE ROUTE FBC11-4.1.2(1), ACCESSIBLE
 PARKING.
  
 15.)SHOW ACCESSIBLE ROUTE AT GLASS PIZZA DISPLAY.
 WHEN SCALED, THE SPACE BETWEEN THE BACK OF THE CHAIRS
 WHEN PUSHED UNDER THE TABLE TO THE DISPLAY CASE IS 12".
 SEE ALSO FBC1013.
  
 16.)SHEET 3.1 REFERS TO THE WRONG BUILDING CODE
 (FBC2001).
  
 17.)PROVIDE ROOF LOADING INFORMATION; DESIGN LOAD,
 NEW LOAD FOR MECHANICAL EQUIPMENT.THREE DIFFERENT
 CONDITIONS ARE SHOWN (STEEL, WOOD, CONCRETE), WHICH
 APPLIES TO THIS JOB?
  
 18.)SHOW WORST CASE EXIT ACCESS TRAVEL DISTANCE, FBC
 TABLE 1015.1.NOTE THAT THERE ARE NO OVERALL
 DIMENSIONS ON THE FLOOR PLAN AND INCOMPLETE INTERIOR
 DIMENSIONS.INCLUDE OVERALL DIMENSIONS.
  
 19.)SHOW DISTANCE BETWEEN THE TWO EXITS FBC
 1014.2.1.
  
 20.)SEE FBC 11-4.1(3), WORK AREAS SHALL BE DESIGNED
 SO THAT INDIVIDUALS CAN APPROACH, ENTER, AND EXIT THE
 AREAS.THE DOORS TO THE KITCHEN DO NOT COMPLY WITH
 FBC11-4.13.
  
 21.)COUNTER LENGTH TO BE A MINIMUM OF 36",
 FBC11-7.2(1), 2'6" SHOWN 1.2A.
  
 22.)SHOW ACCESSIBLE SEATING, FBC11-4.32.
  
 23.)THE NOTE REGARDING THE SPECIFICATIONS BEING A
 GUIDE ONLY IS TOO VAGUE.SOME OF THE SPECIFICATIONS
 ARE REQUIRED BY CODE (COUNTER LENGTH/HEIGHT, WALL
 FINISH IN THE RESTROOMS, DETAILS REGARDING ACCESSIBLE
 SEATING, ETC.).THE NOTE STATES "MAY CHANGE WHERE CODE
 PERMITS"; HOW WILL THE CONTRACTOR IN THE FIELD KNOW
 WHERE CODE PERMITS?EITHER NOTE WHICH DETAILS MAY NOT
 BE CHANGED (OR REQUIRE A REVISION TO DETERMINE CODE
 COMPLIANCE) OR REMOVE THE NOTE FROM THE PLAN.
  
 24.)MINIMUM INTERIOR FINISH CLASSIFICATION NOTE ON
 THE COVER SHEET IS CONFUSING.IN ONE PLACE ASSEMBLY IS
 HIGHLIGHTED WITH REQUIREMENTS FOR BOTH SPRINKLED AND
 UNSPRINKLED, INCLUDING INTERIOR FINISH A THROUGH C, BUT
 FLAME SPREAD GROUP A IS CHECKED.NOTE REQUIREMENTS FOR
 THIS PARTICULAR JOB, NOT GENERAL NOTES OUT OF THE CODE
 BOOK.
  
 25.)IF THIS IS A SPRINKLED BUILDING, FIRE SPRINKLER
 PLANS REQUIRED PRIOR TO PERMITTING.
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-05-29 Cont ID  
Sent By btrobaug Date 2007-05-29 Time 16:52 Rev Time 1.00
Received By btrobaug Date 2007-05-29 Time 14:53 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-05-18 Cont ID  
Sent By dpalmer Date 2007-05-18 Time 09:39 Rev Time 0.00
Received By dpalmer Date 2007-05-17 Time 16:50 Sent To PC
Notes
2007-05-18 09:39:45** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE IDENTIFY ALL REVISIONS BY CLOUDS AND
 TRIANGLES AND COORDINATE WITH TITLE BLOCKS.
 FBC 106.1.2,
  
 2) NOTE: PLEASE SEE THE PANEL SCHEDULES HAVE REVISED
 PANEL DESIGNATIONS AND DO NOT CORRELATE.
 PLEASE SEE THERE ARE SEVERAL CIRCUITS ON PLANS WHICH DO
 NOT MATCH WITH PANEL SCHEDULE(S).
 PLEASE SEE THERE ARE MORE CIRCUITS ON PANELS THAN ON
 PLANS, LIGHTING SHOWN AS EQUIPMENT, EQUIPMENT AS
 SOMETHING ELSE AND SOME MISSING CIRCUIT DESIGNATIONS
 ALL TOGETHER.
 PLEASE REVISE AND COORDINATE ALL CIRCUITS FOR REVIEW.
 408.4.
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE THE PANEL *B* IS SHOWN AS 200A AND
 225A.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE THE SINGLE PHASE PANEL IS NOW FED
 FROM THE THREE PHASE SERVICE AND VICE VERSA.
  
 ** PLEASE COORDINATE ALL OF THE ABOVE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-03-31 Cont ID  
Sent By dpalmer Date 2007-03-31 Time 08:54 Rev Time 0.00
Received By dpalmer Date 2007-03-31 Time 08:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-10 Cont ID  
Sent By dpalmer Date 2007-03-10 Time 14:06 Rev Time 0.00
Received By dpalmer Date 2007-03-10 Time 13:18 Sent To  
Notes
2007-03-10 14:07:19** UNSAT 3RD REVIEW **
  
 1) NOTE: PLEASE SEE PLANS DO NOT INDICATE THE YEARS FOR
 THE NFPA-101 AND NFPA-72. SHOULD BE 2003 FOR 101 AND
 2002 FOR 72.
 THIS WOULD HAVE BEEN REDLINED HOWEVER PLANS ARE COMING
 BACK FOR OTHER COMMENTS.
  
 2) NOTE: PLEASE SEE THE SERVICE RISER AS THIS IS NOW
 NOTING THIS EXISTING 3-PHASE SERVICE FOR ONE OF THE
 METERS/MAINS WHICH ON PREVIOUS PLANS WAS BEING SHOWN AS
 AN EXISTING SINGLE PHASE METER AND MAIN? PLEASE CLARIFY
 THIS AS IT WAS THE UNDERSTANDING THAT A NEW 3-PHASE
 METER CAN, MAIN AND PANEL WAS BEING INSTALLED. PLEASE
 SEE THE PANEL *B* AS IT IS NOW BEING SHOWN AS 3-PHASE.
 PLEASE SEE BASED ON THE FEEDERS SHOWN FROM THE GUTTER,
 ONLY A SINGLE PHASE SERVICE IS BEING BROUGHT IN TO THE
 METER??
 PLEASE CORRELATE.
  
 3) NOTE: PLEASE CORRELATE ALL FIXTURES ON THE FIXTURE
 LEGEND WITH THE FIXTURES ON PLANS AND WATTAGES ON PLANS
 WITH THE NUMBER OF FIXTURES ON ENERGY CALCULATIONS AND
 THE WATTAGES INDICATED ON THE ENERGY CALCULATIONS.
 PLEASE SEE THE TRACK LIGHTING DOES NOT CORRELATE.
 PLEASE SEE THE WALL LIGHTING FIXTURES DO NOT
 CORRELATE.
 PLEASE SEE THE LIGHTING IN KITCHEN AREA (FRONT) DOES
 NOT CORRELATE.
 PLEASE SEE THE LIGHTING IN KITCHEN AREA (REAR) DOES NOT
 CORRELATE.
 PLEASE SEE THE LIGHTING IN OTHER AREAS, LIKE THE
 BATHROOMS, CLOSET, ETC WHICH DO NOT MATCH.
 PLEASE SEE THE TYPE OF FIXTURES NEED TO BE
 COORDINATED.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2
  
 4) NOTE: PLEASE SEE THE PLANS DO NOT INDICATE THE OVER
 RIDES AT THE POINT OF ENTRANCE INTO THE SPACES (EACH
 DOOR) TO TURN ON THE LIGHTING. PLEASE KNOW AS THIS IS
 REQUIRED IN 13-415.1.ABC.1.1, .1.2.
 PLEASE ALSO SEE THIS IS A LIFE SAFETY CODE ISSUE FOR
 EGRESS AND INGRESS IN AND OUT OF AREAS/SPACE.
 PLEASE SEE ONLY ONE LCP PAD WAS ADDED TO PLANS AND DID
 NOT LOCATE THIS AT THE POINT OF ENTRANCE NOR IS ONE
 LOCATED AT THE OTHER LOCATION/POINT OF ENTRANCE.
  
 5) NOTE: PLEASE SEE THE LIGHTING CONTROL PANEL AND PANE
 SCHEDULE AS BOTH THE SIGN AND SHOW WINDOW ARE BEING
 SHOWN TO THE SAME LOCATION/CIRCUIT EVEN THOUGH THESE
 ARE TWO SEPARATE CIRCUITS.
 PLEASE CORRELATE AND ADJUST THE CIRCUITING FOR THE LCP
 AS NEEDED.
 FBC 106.1.2
  
 6) NOTE: PLEASE KNOW THAT ONE SET OF THE ELECTRICAL
 PLANS AND ENERGY CALCULATIONS HAVE NOW BEEN RETAINED BY
 THIS OFFICE FOR POSSIBLE REVIEW FROM THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS. THIS IS THE RESPONSIBILITY
 OF THE ENGINEER OF RECORD.
 FS 471.025(2).
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) AS SOME OF THESE
 ITEMS ARE REPEAT COMMENTS FROM THE SECOND REVIEW, IF
 PLANS COME BACK WITHOUT ANY OF THE CODE COMMENTS
 ADDRESSED, A FEE WILL BE ASSESSED FOR THE PLAN REVIEW
 POTION OF THE PERMIT FEE. THIS IS ONLY BEING GIVEN AS A
 NOTICE AT THIS TIME.
  
 ** AS STATED IN PREVIOUS REVIEWS, IF THERE ARE
 QUESTIONS OR COMMENT PLEASE CONTACT THIS
 OFFICE/REVIEWER TO GO OVER THESE NOTES.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-12 Cont ID  
Sent By dpalmer Date 2007-02-12 Time 11:01 Rev Time 0.00
Received By dpalmer Date 2007-02-11 Time 18:44 Sent To  
Notes
2007-02-12 11:02:02** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE BE SURE ALL PLANS STATE THE FOLLOWING
 MINIMUM CODES IN WHICH PLANS ARE DESIGNED AND PERMITTED
 UNDER.
 PLEASE KNOW THE FOLLOWING WILL BE REQUIRED FOR
 ELECTRICAL SHEETS.
 2002 NFPA-70
 THE PREVIOUS NOTE ONLY MENTIONED PERMIT APPLICATIONS
 SUBMITTED AFTER THE DECEMBER 8TH 2006 DATE WOULD BE
 UNDER THE NEW CODES.
 PLEASE SEE THE PLANS STATE THE 2006 REVISIONS TO THE
 2004 FBC AND STATE THE 2005 NEC.
 PLEASE CORRECT.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3
 PLEASE INDICATE SCHEDULING, OVER RIDE DEVICES AT
 INGRESS/EGRESS, SEPARATE SPACES, TIMES ON ALL OVER RIDE
 DEVICES.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, AND 13-415.2.ABC.1
 ENERGY CALCULATIONS ARE MISSING AND PERFORMANCE
 CALCULATIONS.
 PLEASE SEE THE LOCATION OF OVER RIDES SHALL ALSO BE
 LOCATED AS REQUIRED AT THE POINT OF INGRESS/EGRESS TO
 THE SPACE. THIS CAN BE DONE BY WAY OF OCCUPANCY SENSORS
 OR OVER RIDES SWITCH DEVICES.
 PLEASE SEE NOT TIMES ARE STATED ON PLANS FOR ANY
 DEVICES, OR SCHEDULING.
 PLEASE SEE THE SYMBOL LEGEND FOR DEVICES DOES NOT
 CORRELATE WITH THE SYMBOLS ON PLANS AND DOES NOT
 INDICATE OVER RIDE CONTROL.
 PLEASE SEE THE FIXTURE LEGEND DOES NOT CORRELATE WITH
 THE ENERGY CALCULATIONS AND THE ENERGY CALCULATIONS DO
 NOT CORRELATE WITH FIXTURES ON PLANS. THE AMOUNT OF
 FIXTURES ON PLANS IS SUBSTANTIALLY MORE THAN THE AMOUNT
 OF FIXTURES IN THE ENERGY CALCULATIONS.
 PLEASE SEE SOME LIGHTING CIRCUITS ON PLANS ALONG WITH
 FIXTURES DO NOT SHOW CONTROL OR HOW THEY ARE BEING
 CONNECTED OR CONTROLLED WHICH WILL AFFECT THE LIGHTING
 CONTROL PANEL AS STATED.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO CONTROL AND
 CIRCUITS ON PLANS.
 PLEASE PROVIDE A PANEL SCHEDULE FOR THE LIGHTING
 CONTROL PANEL FOR ALL LIGHTING BEING CONTROLLED BY THE
 LCP.
 * THIS WAS ON PREVIOUS REVIEW
  
 3) NOTE: PLEASE CLARIFY LOAD FOR AHU, SHOWS 10KW AND
 12KW.
 PLEASE SEE THE PANEL SCHEDULE SHOWS BOTH? PLEASE
 CLARIFY THIS.
  
 4) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULE(S). PLEASE
 SEE SOME MISSING FOR LIGHTING, RECEPTS.
 PLEASE SEE THERE ARE SEVERAL FIXTURES WHICH DO NOT
 INDICATE ANY CIRCUITING, CONTROL ETC AS STATED IN NOTE
 #2 ABOVE.
 PLEASE CORRELATE WITH THE SUBMITTED PANEL SCHEDULES.
 FBC 106.1.2, 106.3.5.1.2,NEC 408.4, 310.16 ETC
  
 5) NOTE: PLEASE SEE KITCHEN AREA WHICH WILL REQUIRE AN
 ADDITIONAL EMERGENCY LIGHTING FIXTURE FOR EGRESS.
 PLEASE SEE AREA REDLINED ON PLANS.
 LS 101 7.8, 7.9.
 PLEASE SEE 700.12 FOR CIRCUITING OF EMERGENCY LIGHT
 FOR NEW FIXTURE..
  
  
 6) NOTE: PLEASE SEE RISER WHICH HAS NOW BEEN REVISED
 SHOWS THE TWO METERS AND TWO MAINS FOR THE SAME
 TENANT?? THIS IS ONE TENANT AND THIS IS SHOWING MORE
 THAN ONE METER FOR THIS SINGLE SPACE. PLEASE SEE THAT
 ONLY ONE METER FOR TENANT SPACE IS PERMITTED. PLEASE
 SEE THIS METER CAN BE LARGER AND THEN EACH OF THE TWO
 MAINS AS SHOWN CAN BE TAPPED FROM THE LARGER SINGLE
 METER CAN. PLEASE CORRELATE RISER AND PANEL AS TWO
 DIFFERENT SIZES ARE SHOWN FOR PANEL *A*.
 PLEASE SEE BUILDING, ZONING FOR A SINGLE TENANT SERVED
 BY A SINGLE METER.
 PLEASE SEE 230.2.
 PLEASE PROVIDE MORE INFORMATION. FBC 106.1.2,
 106.3.5.1.2
  
 7) NOTE: PLEASE SEE 210.8B3 FOR GFP PROTECTION FOR ALL
 15/20A 120V RECEPTS IN KITCHEN/ KITCHEN AREAS.
 PLEASE SEE THESE WERE NOT CORRECTED.
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTE GIVEN AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-11 19:21:152007-02-11 19:21:15
 REVIEW TO CONTINUE ON 2/12

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-04 Cont ID  
Sent By dpalmer Date 2007-01-04 Time 19:14 Rev Time 0.00
Received By dpalmer Date 2006-12-28 Time 08:50 Sent To  
Notes
2007-01-04 19:14:02** UNSAT **
  
 1) NOTE: PLEASE BE SURE ALL PLANS STATE THE FOLLOWING
 MINIMUM CODES IN WHICH PLANS ARE DESIGNED AND PERMITTED
 UNDER.
 PLEASE KNOW THE FOLLOWING WILL BE REQUIRED FOR
 ELECTRICAL SHEETS.
 2002 NFPA-70 *JUST AS AN FYI AS OF 12/8/06 THE STATE OF
 FLORIDA ADOPTED THE NEW 2005 NEC AND ANY PERMIT
 APPLICATIONS MADE FROM THAT DATE FORWARD WILL BE UNDER
 THE NEW CODE AND THE 2006 REVISIONS TO THE 2004 FBC.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THIS IS A CHANGE IN OCCUPANCY WHICH
 REQUIRES ALL ELECTRICAL TO BE BROUGHT UP TO THE CURRENT
 TECHNICAL CODES.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3
 PLEASE INDICATE SCHEDULING, OVER RIDE DEVICES AT
 INGRESS/EGRESS, SEPARATE SPACES, TIMES ON ALL OVER RIDE
 DEVICES.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, AND 13-415.2.ABC.1
 ENERGY CALCULATIONS ARE MISSING AND PERFORMANCE
 CALCULATIONS.
  
 3) NOTE: PLEASE SEE INFORMATION ON TITLE BLOCKS
 REFLECTS METRO DESIGN GROUP WHICH MUST BE LICENSED
 THROUGH THE STATE OF FLORIDA FOR PROVIDING ENGINEERING
 SERVICES.
 PLEASE SEE THAT THIS HAS BEEN NOTED ON PREVIOUS REVIEWS
 ON OTHER PROJECTS AND WILL BE DETERMINED FROM THE
 FLORIDA BOARD OF ENGINEERS. NO DETERMINATION HAS BEEN
 MADE AT THIS POINT IN TIME.
 FS 471.023, 481.229, FAC 61G15-23.002 ETC
 ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE AT
 THIS TIME.
  
 4) NOTE: PLEASE SEE NFPA-96 AND CLARIFY ANY LIGHTING
 AND ELECTRICAL WHICH MAY BE PART OF THE HOOD SYSTEM
 WHICH IS REQUIRED TO BE SHUNT TRIP.
  
 5) NOTE: PLEASE CLARIFY LOAD FOR AHU, SHOWS 10KW AND
 12KW. PLEASE SEE 424.3B FOR MINIMUM OCP AT 125% IF
 12KW?
  
 6) NOTE: PLEASE SEE 220.12A FOR DETERMINING LOAD
 CALCULATIONS FOR SERVICE FEEDERS ON WINDOWS. PLEASE SEE
 QUOTED COMMENTARY.
 ?THE 200-VOLT-AMPERE CALCULATION FOR EACH LINEAR FOOT
 OF A SHOW WINDOW IS REQUIRED TO DETERMINE THE FEEDER
 LOAD. SEE THE COMMENTARY FOLLOWING 220.3(B)(7) FOR LOAD
 CALCULATIONS FOR BRANCH CIRCUITS IN SHOW WINDOWS.?
  
 7) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULE(S). PLEASE
 SEE SOME MISSING FOR LIGHTING, RECEPTS AND ROOF TOP
 EQUIPMENT.
 FBC 106.1.2, 106.3.5.1.2,NEC 408.4, 310.16 ETC
  
 8) NOTE: PLEASE SEE 700.12 FOR CIRCUITING OF EMERGENCY
 AND EXIT LIGHTS.
  
 9) NOTE: PLEASE SEE THE TWO BATHROOMS AS SHOWN DO NOT
 SEEM TO INDICATE ANY ELECTRICAL. PLEASE KNOW THESE
 ROOMS WILL BE REQUIRED TO COMPLY WITH GFI PROTECTION
 FOR RECEPTS IF THEY ARE LOCATED IN THE BATHROOM AND
 ALSO WILL BE REQUIRED TO MEET FBC CHAPTER 13,
 13-415.1.ABC.1.2
  
 10) NOTE: PLEASE PROVIDE MORE INFORMATION FOR THE
 EXISTING SERVICE.PLEASE INDICATE THE EXISTING SERVICE
 ENTRANCE CONDUCTORS. 310.16, 240.4
 MUST MEET LOAD CALCULATIONS WHICH WILL ALSO BE NOTED TO
 BE SUPPLIED.
  
 11) NOTE: PLEASE SEE RISER AS SHOWN WHICH SHOWS THE TWO
 NEW METERS AS MAINS ONE OF TWO AND TWO OF TWO? PLEASE
 SEE THE RISER ALREADY SHOWS A MAIN.
 PLEASE SEE RISER ALSO SHOWS WHAT SOME BROKEN LINES
 WHICH WOULD INDICATE EXISTING APPEAR, YET THE RISER
 SEEMS TO SHOW ALL AS NEW? PLEASE SEE EVEN SERVICE NOTED
 AS EXISTING SEEMS TO BE NEW?
 PLEASE CLARIFY THE ENTIRE RISER FOR NEW AND EXISTING.
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE: PLEASE SEE BASED ON THE EXISTING 600A SERVICE
 AS SHOWN, THE EXISTING GROUNDING ELECTRODE SHOULD BE
 VERIFIED FOR SIZE. PLEASE KNOW IN EITHER CASE IS THIS
 IS REALLY A #1 AS SHOWN THEN IT WILL BE REQUIRED TO BE
 BROUGHT UP TO CODE PER 250.66, IF LARGER THEN INDICATE
 THE EXITING SIZE MEETING CODE.
  
 13) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 THE EXISTING SERVICE AND THE NEW LOADS BEING ADDED.
 PLEASE SEE NEC 220,
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 14) NOTE: PLEASE SEE THE RISER SHOWS THE NEW SUB PANEL
 "B" BEING FED FROM THE NEW PANEL "A", YET THE PANEL "A"
 DOES NOT SHOW ANY BREAKER, OR IS LISTED ON THE PANEL
 SCHEDULE IN ANYWAY.
 408.4, 310.16, 240.4 ETC
 REVIEW CAN NOT BE DONE FOR THIS FOR CODE COMPLIANCE AT
 THIS TIME.
  
 15) NOTE: PLEASE INDICATE A "FLOATING NEUTRAL" FOR ALL
 METERS AFTER THE FIRST MEANS OF DISCONNECT. PLEASE SEE
 250.6, AND 250.24B.
  
 16) NOTE: PLEASE SEE SHOW ALL EQUIPMENT LOCATIONS ON
 PLANS. THE NOTE WHICH MENTIONS TO SEE COVER SHEET FOR
 LOCATIONS, DOES NOT PROVIDE ENOUGH INFORMATION. PLEASE
 SEE 240.24, 110.26, 408.7 ETC.
 NO REVIEW FOR CODE COMPLIANCE CAN BE DONE AT THIS
 TIME.
  
 17) NOTE: PLEASE SEE 210.8B3 FOR GFP PROTECTION FOR ALL
 15/20A 120V RECEPTS IN KITCHEN/ KITCHEN AREAS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-04 17:48:482007-01-04 17:48:48
 ELECTRICAL REVIEW IN PROGRESS.
2006-12-28 08:50:53CURRENTLY ON HOLD PER THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-05-15 Cont ID  
Sent By mwennerg Date 2007-05-15 Time 14:23 Rev Time 0.00
Received By mwennerg Date 2007-05-15 Time 14:23 Sent To  
Notes
2007-05-15 14:24:22REVISION DATED 5/1/07.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-04-03 Cont ID  
Sent By mawillia Date 2007-04-03 Time 15:39 Rev Time 0.00
Received By mawillia Date 2007-04-03 Time 15:32 Sent To  
Notes
2007-04-03 15:38:55*****APPROVED*****
  
  
 PLAN SHEET 1-2A STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-03-21 Cont ID  
Sent By mawillia Date 2007-03-21 Time 18:30 Rev Time 0.00
Received By mawillia Date 2007-03-21 Time 18:27 Sent To  
Notes
2007-03-21 18:30:07******PROVISO*****
  
  
 ALL PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED.APPROPIATE PLAN SHEET(S) WILL BE STAMPED
 WHEN ALL PLAN REVIEWS HAVE BEE SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-20 Cont ID  
Sent By mawillia Date 2007-02-20 Time 15:17 Rev Time 0.00
Received By mawillia Date 2007-02-20 Time 15:17 Sent To  
Notes
2007-02-20 15:25:50*****UNSAT*****
  
  
 THE BELOW COMMENT(TAKEN FROM PREVIOUS FIRE PLAN REVIEW)
 STILL NEED TO BE ADDRESSED
  
  
 11. SHOW/DISPLAY THE NUMERICAL ADDRESS ONTHE EXTERIOR
 ELEVATION THAT FRONTS NORTH DIXIE HIGHWAY.AS PER WEST
 PALM BEACH CODE, THE ADDRESS NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH.PLEASE SHOW ON
 PLAN
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-05 Cont ID  
Sent By mawillia Date 2007-01-05 Time 16:10 Rev Time 0.00
Received By mawillia Date 2007-01-05 Time 16:10 Sent To  
Notes
2007-01-05 17:05:11*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 4.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.THE SCOPE OF WORK IS FOR THE ALTERATION TO CONVERT
 A COMMERCIAL STORE (MERCANTILE OCCUPANCY) TO A FOOD
 ESTABLISHMENT (ASSEMBLY OCCUPANCY).PLEASE BE ADVISED
 THAT THIS STRUCTURE SHALL BE CONSIDERED AS A NEW
 ASSEMBLY OCCUPANCY.
  
 6.PANIC HARDWARE OR FIRE EXIT HARDWARE IS REQUIRED ON
 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS.
  
 7.PROVIDE LIFE SAFETY PLAN SHEET WHICH SHALL SHOW THE
 TRAVEL DISTANCE TO REACH AN EXIT.THE LOCATION OF EXIT
 LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHERS MAY ALSO
 BE INCLUDED.
  
 8.WILL THE BUILDING/STRUCTURE BE EQUIPPED WITH A FIRE
 ALARM AND/OR FIRE SPRINKLER SYSTEM?
  
 9.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE
 WITH NFPA 96.SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED.
  
 10. PROVIDE INTERIOR FINISH CLASSIFICATION FOR THE
 PROPOSED STRUCTURE.BE ADVISED THAT INTERIOR WALL AND
 CEILING FINISH MATERIALS SHALL BE CLASS A OR CLASS B IN
 EXITS AND EXIT ACCESS CORRIDORS.IN GERNERAL ASSEMBLY
 AREAS HAVING OCCUPANT LOADS OF 300 OR FEWER, INTERIOR
 WALL AND CEILING FINISH SHALL BE CLASS A, B, OR C.
  
 11. SHOW/DISPLAY THE NUMERICAL ADDRESS ONTHE EXTERIOR
 ELEVATION THAT FRONTS NORTH DIXIE HIGHWAY.AS PER WEST
 PALM BEACH CODE, THE ADDRESS NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH.
  
 12. SMOKING IN ASSEMBLY OCCUPANCIES SHALL BE REGULATED
 BY THE AUTHORITY HAVING JURISDICTION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2007-06-22 Cont ID  
Sent By mperson Date 2007-06-22 Time 16:17 Rev Time 0.45
Received By mperson Date 2007-06-22 Time 16:17 Sent To PC
Notes
2007-06-22 16:19:19REVISION: SHEET 3.0A, NAT/GAS AS-BUILT ONLY.

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2007-06-08 Cont ID  
Sent By mperson Date 2007-06-08 Time 10:42 Rev Time 0.45
Received By mperson Date 2007-06-08 Time 10:42 Sent To PC
Notes
2007-06-08 11:06:29GAS REVISION DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATIONREQUIRED FOR GAS
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1.NOTE: THE SUBMITTED GAS REVISION DRAWINGS ARE NOT
 LEGIBLE AND ARE HARD TO READ. PLEASE CORRECT THIS ON
 THE RESUBMITTED GAS REVISION.
 PER FBC-2004 CHAPTER 1, SECTION 106.1.1:INFORMATION
 ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED GAS REVISION DRAWINGS ARE NOT
 INDICATING CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF
 PIPE. PLEASE CORRECT THIS ON THE RESUBMITTED GAS
 REVISION.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THE TOTAL DEVELOPED LENGTHS INDICATED ON THE
 DRAWINGS OF 85' ON THE 2 PSI, AND 35' ON THE 0.5 PSI
 CAN NOT BE VERIFIED UNTIL COMMENTS #1 AND #2 HAVE BEEN
 ADDRESSED.
  
 4.PER FBC-2004 FUEL GAS SECTION 408.4 A SEDIMENT
 TRAP REQUIRED ON COOK LINE AND SHALL BE INSTALLED
 DOWNSTREAM OF THE EQUIPMENT SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE EQUIPMENT AS PRACTICAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2007-05-18 Cont ID  
Sent By mperson Date 2007-05-18 Time 16:00 Rev Time 0.45
Received By mperson Date 2007-05-18 Time 16:00 Sent To PC
Notes
2007-05-18 16:18:08DENIED REVISION
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 THE GAS REVISION PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: THIS IS NOT A GAS SUBMITTAL, THIS IS A GAS
 REVISION AND ADDITIONAL FEES ARE DUE. THE APPROVED
 PERMITTED GAS DRAWINGS ON SHEET 3.0A, ARE SIGNED AND
 SEALED BY DESIGNPROFESSIONAL THOMAS TWOMEY P.E.
 #25626, AND ANY REVISIONS TO SAID DRAWINGS MUST BE
 SIGNED AND SEALED BY SAID DESIGN PROFESSIONAL PER
 CHAPTER 471, FLORIDA STATUTES.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-04-03 Cont ID  
Sent By mperson Date 2007-04-03 Time 14:49 Rev Time 0.45
Received By mperson Date 2007-04-03 Time 14:49 Sent To P
Notes
2007-04-03 14:53:43NOTE: GAS PERMIT REQUIRED FOR PROJECT.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-03-21 Cont ID  
Sent By mperson Date 2007-03-21 Time 11:26 Rev Time 0.55
Received By mperson Date 2007-03-21 Time 11:26 Sent To  
Notes
2007-03-21 13:58:37DENIED 2ND TIME
 REFERENCE: FBC-2004 FUEL GAS; THE CITY OF WEST PALM
 BEACH GAS PERMIT APPLICATION REQUIREMENTS;
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1.**OK**
  
 2.**OK**
  
 3.**OK**
  
 4.**NO/OK**SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: PLEASE INDICATE ON THE RESUBMITTED MANUFACTURER
 SHEETS THE MODEL NUMBER THAT CORRELATES WITH THE GAS
 LOAD CALCULATIONS ON SHEET 3.0A. SUBMITTALS MUST
 INDICATE A LISTINGS FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY (NRTL). THE FOLLOWING IS A LIST OF
 MANUFACTURER SHEETS THAT NEED CLARIFICATION.AN **OK**
 BY THE APPLIANCE MEANS THE SUBMITTAL IS ACCEPTABLE.
  
 A} WATER HEATER- SUBMITTAL **OK**, AN INDICATION OF
 WHICH MODEL NUMBER BEING USED IS REQUIRED.
  
 B} PIZZA- SUBMITTAL REQUIRED.
  
 C} PIZZA- SUBMITTAL REQUIRED.
  
 D} RANGE- 269,000 BTU RANGE, A LISTING (NRTL)
 REQUIRED.
  
 E} RANGE- 147,000 BTU RANGE, A LISTING (NRTL)
 REQUIRED. AN INDICATION OF WHICH MODEL NUMBER BEING
 USED IS REQUIRED. A CLEAR INDICATION THAT THE SUBMITTAL
 BTU'S CORRELATE WITH THE GAS LOAD CALCULATIONS ON SHEET
 3.0A.
  
 F} CONVECTION OVEN- SUBMITTAL **OK**, HOWEVER PLEASE
 REFERENCE THE NEW COMMENT IN RELATION TO THE CONVECTION
 OVEN.
  
 G} FRYER- SUBMITTAL **OK**.
  
 H} FRYER- SUBMITTAL **OK**.
  
 I} GRIDDLE- SUBMITTAL REQUIRED.
  
 J} MP REGULATOR- SUBMITTAL **OK**.
  
 K} EMERGENCY HOOD SHUT DOWN VALVE- SUBMITTAL **OK**.
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 5. SHEET 3.0A GAS ISOMETRIC INDICATES 2 GAS
 CONNECTIONS WHICH WOULD MAKE IT A DOUBLE DECK
 CONVECTION OVEN WITH A TOTAL BTU LOAD OF 140,000. THE
 SUBMITTALS AND THE GAS LOAD CALCULATIONS ARE REFLECTING
 A SINGLE DECK COVECTION OVEN. IF THIS IS A SINGLE DECK
 COVECTION OVEN PLEASE DELETE ONE OF THE GAS CONNECTIONS
 ON THE GAS ISOMETRIC. IF THIS IS A DOUBLE DECK
 CONVECTION OVEN PLEASE CORRECT THE GAS LOAD
 CALCULATIONS ON SHEET 3.0A AND SUBMITTALS TO REFLECT
 THIS. PLEASE CLARIFY, CORRELATE, AND CORRECT ON THE
 RESUBMITTAL.
  
 6. SHEET 3.0A GAS ISOMETRIC: PLEASE DELETE THE 4'@ ON
 THE 2 PSI GAS PIPE BY THE SOV. THIS IS CONFUSING BEING
 THAT A BOLD 5' IS ALSO INDICATED FOR THE SAME
 CORRESPONDING CUT SECTION.
  
 7. SHEET 3.0A GAS ISOMETRIC GAS LOAD CALCULATIONS:
 PLEASE CORRECT THE 2 PSI LENGTH TO 60' AND THE 0.5 PSI
 LENGTH TO 31' ON THE RESUBMITTAL.
  
 8. SHEET 3.0A GAS ISOMETRIC: PLEASE CLEARLY INDICATE
 THE PIPE SIZE BETWEEN THE WATER HEATER AND PIZZA AS 2"
 ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-02-16 Cont ID  
Sent By mperson Date 2007-02-20 Time 16:33 Rev Time 0.00
Received By mperson Date 2007-02-16 Time 16:33 Sent To  
Notes
2007-02-16 16:59:49DENIED
 REFERENCE: FBC-2004 FUEL GAS AND CITY OF WEST PALM
 BEACH GAS PERMIT APPLICATION REQUIREMENTS.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW ON THE RESUBMITTED GAS ISOMETRIC ON SHEET 3.OA:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE ALL THE
 CORRESPONDING LENGTHS IN RELATION TO THE INDICATED CUT
 SECTIONS. PLEASE CORRECT AND RESUBMIT.
  
 2. TYPE OF GAS, (LP OR NATURAL)
 NOTE: IT IS ASSUMED BY THE INFORMATION ON SHEET 3.0A
 GAS ISOMETRIC THAT THE GAS IS NATURAL BUT IT IS NOT
 INDICATED. PLEASE INDICATE THE GAS TYPE ON THE
 RESUBMITTAL.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THE INDICATED DISTANCES OF 59' FOR THE 2 PSI AND
 29' FOR THE 0.5 PSI CAN NOT BE VERIFIED UNTIL COMMENT
 NUMBER ONE IS COMPLETED.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: PLEASE INDICAE ON THE RESUBMITTED MANUFACTURER
 SHEETS THE MODEL NUMBER THAT CORRELATES WITH THE GAS
 LOAD CALCULATIONS ON SHEET 3.0A. THE FOLLOWING IS A
 LIST OF MANUFACTURER SHEETS THAT NEED CLARIFICATION. AN
 (OK) BY THE APPLIANCE MEANS THE SUBMITTAL IS
 ACCEPTABLE.
  
 A} WATER HEATER- NO MANUFACTURER SHEET SUBMITTED.
  
 B} PIZZA- SUBMITTED MAUFACTURER SHEET DOES NOT
 CORRELATE.
  
 C} PIZZA- SUBMITTED MANUFACTURER SHEET DOES NOT
 CORRELATE.
  
 D} RANGE- SUBMITTED MANUFACTURER SHEET DOES NOT
 CORRELATE.
  
 E} RANGE- SUBMITTED MANUFACTURER SHEET DOES NOT
 CORRELATE.
  
 F} CONVECTION OVEN- (OK)
  
 G} FRYER- (OK)
  
 H} FRYER- (OK)
  
 I} GRIDDLE- SUBMITTED MANUFACTURER SHEET DOES NOR
 CORRELATE.
  
 J} MP REGULATOR (PRV)- NO MANUFACTURER SHEET
 SUBMITTED.
  
 K} EMERGENCY HOOD SHUT DOWN VALVE- NO MANUFACTURER
 SHEET SUBMITTED.
  
  
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 13:17 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 13:17 Sent To M
Notes
2007-06-24 13:17:32TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-06-22 Cont ID  
Sent By adarroug Date 2007-06-22 Time 14:37 Rev Time 0.00
Received By adarroug Date 2007-06-22 Time 14:37 Sent To G
Notes
2007-06-22 14:37:34TO "MPERSON" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-06-04 Cont ID  
Sent By adarroug Date 2007-06-04 Time 11:35 Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 11:35 Sent To G
Notes
2007-06-04 11:36:02TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 15:53 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 15:53 Sent To M
Notes
2007-06-01 15:53:32TO"M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 16:09 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 16:09 Sent To E
Notes
2007-05-22 16:12:53TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 14:48 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 14:48 Sent To E
Notes
2007-05-15 14:48:34TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 14:13 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 14:13 Sent To G
Notes
2007-05-08 14:13:25TO "G" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 13:29 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 13:29 Sent To  
Notes
2007-05-08 13:30:07WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 17:43 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 17:43 Sent To  
Notes
2007-03-30 17:44:28TO COMM BOARD # 58

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-28 Cont ID  
Sent By spalmer Date 2007-03-28 Time 18:23 Rev Time 0.00
Received By spalmer Date 2007-03-28 Time 18:23 Sent To  
Notes
2007-03-28 18:23:42WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-09 Cont ID  
Sent By adarroug Date 2007-03-09 Time 11:10 Rev Time 0.00
Received By adarroug Date 2007-03-09 Time 11:10 Sent To  
Notes
2007-03-09 11:10:28TO "COMM' BD#41

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 10:28 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 10:28 Sent To  
Notes
2007-02-07 16:33:25TO "COMM" BD#7
2007-01-31 10:28:40WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-16 Cont ID  
Sent By swurafti Date 2007-01-16 Time 10:25 Rev Time 0.00
Received By swurafti Date 2006-12-06 Time 15:10 Sent To  
Notes
2006-12-21 11:40:48TO "COMM" BD#32
2006-12-06 15:11:13WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-06-25 Cont ID  
Sent By tgordon Date 2007-06-25 Time 11:56 Rev Time 0.20
Received By tgordon Date 2007-06-25 Time 11:56 Sent To  
Notes
2007-06-25 11:57:54REVISION TO MECH. PLANS PAGE A3.1.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2007-06-11 Cont ID  
Sent By tgordon Date 2007-06-11 Time 14:23 Rev Time 0.30
Received By tgordon Date 2007-06-11 Time 14:22 Sent To  
Notes
2007-06-11 14:26:00REVISION TO MECH. PLANS PAGE A3.1
 *** DENIED ***
 1) THE NEW SUPPLY AIR DUCT ADDED TO PLAN NEEDS TO BE
 SIZED AND SHOW CFM'S, SEE YELLOW HIGH LIGHT ON PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-05-15 Cont ID  
Sent By tgordon Date 2007-05-15 Time 10:42 Rev Time 0.25
Received By tgordon Date 2007-05-15 Time 10:42 Sent To B
Notes
2007-05-15 10:43:50REVISION TO MECH. PLANS PAGE A3.1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-14 Cont ID  
Sent By tgordon Date 2007-03-14 Time 11:22 Rev Time 0.30
Received By tgordon Date 2007-03-14 Time 11:22 Sent To  
Notes
2007-03-14 11:25:14*** PROVISO ***
 1) ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (A) WALK-IN-COOLER
 (B) KITCHEN HOOD
 (C) FIRE SUPPRESSION
 ** SUBMIT PLANS WITH PERMIT APPLICATION **
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-02-15 Cont ID  
Sent By tgordon Date 2007-02-15 Time 14:36 Rev Time 0.30
Received By tgordon Date 2007-02-15 Time 14:36 Sent To  
Notes
2007-02-15 15:04:21*** DENIED ***
 1) SEE PLANS PAGES A3.1 AND A3.2A, CHANGES TO PLANS MAY
 NOT BE DONE BY HAND.
  
 2) PLEASE SUBMIT TWO COPY'S OF THE ENERGY CALCULATIONS
 AND COOLING LOAD CAL'S.
  
 3)ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-26 Cont ID  
Sent By tgordon Date 2006-12-26 Time 15:33 Rev Time 0.45
Received By tgordon Date 2006-12-26 Time 15:33 Sent To  
Notes
2006-12-26 15:41:38*** DENIED ***
 1) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1.
  
 2) PLEASE SHOW ON MECHANICAL PLANS BATHROOM EXHAUST FAN
 (EF3) CFM'S.
  
 3) ROOF PLAN PAGE 3.2A DOES NOT SHOW AN OSA INLET FOR
 AHU #2, PLEASE CORRECT.
  
 4) PAGE 3.2A SHOWS SF1 AS SF1& EF1, ALSO SHOWS SF2 AS
 SF2 & EF2, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-04-03 Cont ID  
Sent By mperson Date 2007-04-03 Time 14:50 Rev Time 0.33
Received By mperson Date 2007-04-03 Time 14:50 Sent To PC
Notes
2007-04-03 14:54:31NOTE: PLUMBING PERMIT REQUIRED FOR PROJECT.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-03-21 Cont ID  
Sent By mperson Date 2007-03-21 Time 10:40 Rev Time 0.55
Received By mperson Date 2007-03-21 Time 10:40 Sent To G
Notes
2007-03-21 11:24:16DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1.**OK**
  
 2.**OK**
  
 3.**OK**
  
 4 A}**OK**, AND B}**OK**
  
 5.**OK**
  
 6.**OK**
  
 7.**OK**
  
 8.**OK**
  
 9.**OK**
  
 10.**OK**
  
 11.**OK**
  
 12.**NO/OK** SHEET 3.0A ISOMETRIC WATER RISER AND THE
 WATER HEATER DETAIL: PLEASE CORRELATE THE WATER HEATER
 P&T VALVE AND HEATER PAN DRAIN LOCATION.
 NOTE: THE RESUBMITTED WATER HEATER DETAIL INDICATES P&T
 TO SAFE PAN, SAFE PAN TO MOP SINK. THE ISOMTRIC WATER
 RISER INDICATES P&T VALVE TO MOP SINK. PLEASE CORRELATE
 THE ISOMETRIC WATER RISER WITH THE WATER HEATER DETAIL
 ON THE RESUBMITTAL.
  
 13.**OK**
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 14. SHEET 3.0A ISOMETRIC SANITARY RISER DIAGRAM
 INDICATING A TRAPZILLA AT325. I BELIEVE THAT MODLE
 NUMBER IS INCORRECT, I BELIEVE THE CORRECT MODEL NUMBER
 IS TZ-325 PLEASE CLARIFY ON THE RESUBMITTAL. PLEASE
 KNOW THAT THIS GREASE TRAP NEEDS APPROVAL FROM
 ENVIRONMENTAL COMPLIANCE.
 NOTE: PER ARTICLE LLL. SEWERS AND SEWEAGE DISPOSAL.
 PLEASE CONTACT THE FOLLOWING.
  
 ENVIRONMENTAL COMPLIANCE MANAGER:
 LYNN MASSON
 PHONE= (561) 822-2271
 FAX= (561) 822-2279
 E-MAIL= [email protected]
  
 15. SHEET 3.0A PLUMBING FLOOR PLAN: PLEASE DELETE THE
 FOLLOWING "2 WAY FCO SAMPLE POINT" AND "TIE TO EXISTING
 4" SANITARY" ON THE RESUBMITTAL.
  
 16. SHEET 3.0A SANITARY ISOMETRIC RISER DIAGRAM:
 TWO-WAY CLEANOUT REQUIRED ON BOTH THE INLET AND THE
 OUTLET OF THE GREASE TRAP PER THE CITY OF WEST PALM
 BEACH STANDARD GREASE TRAP DETAIL. PLEASE REFERENCE THE
 ATTACHED COPY OF THIS DETAIL TO THE PLUMBING COMMENTS.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-16 Cont ID  
Sent By mperson Date 2007-02-16 Time 14:06 Rev Time 0.00
Received By mperson Date 2007-02-16 Time 14:06 Sent To G
Notes
2007-02-16 15:32:52DENIED 2ND TIME
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FROM THE
 PREVIOUS PLUMBING PLAN REVIEW.
 NOTE: THIS REVIEW WILL FOLLOW THE SAME NUMERICAL ORDER
 AS THE PREVIOUS REVIEW WITH NEW ITEMS BEING NOTED AT
 THE END.
 AN (OK) BY THE NUMBER MEANS PREVIOUS COMMENT WAS
 ADDRESSED.
  
 1. (OK)
  
 2. (OK)
  
 3. (OK)
  
 4. A} (OK)
  
 B} (COMMENT NOT ADDRESSED) PER FBC-2004 PLUMBING,
 SECTION 708.3.5 TWO WAY CLEANOUT REQUIRED AT THE
 JUCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER.
 PLEASE ADD THESE FOR THE RESUBMITTAL.
 NOTE: A SAMPLE POINT IS NOT CONSIDERED A TWO-WAY
 CLEANOUT. PLEASE REFERENCE THE ATTACHED DETAIL OF A
 SAMPLE POINT THATS APPROVED BY THE CITY AND CLEARLY
 INDICATE BOTH THE TWO-WAY CLEANOUT AND THE SAMPLE POINT
 ON THE RESUBMITTED PRINTS.
  
 5. (OK)
  
 6. (OK)
  
 7. (OK)
  
 8. (COMMENT NOT ADDRESSED) SHEET 3.0A WATER HEATER
 DETAIL SAFETY PAN: PLEASE INDICATE THE FOLLOWING PER
 FBC-2004 PLUMBING, SECTION 504.7.1, THE SAFETY PAN
 DRAIN SIZE AND PER SECTION 504.7.2 THE SAFETY PAN DRAIN
 TERMINATION ON THE RESUBMITTAL.
  
 9. (OK)
  
 THE FOLLOWING ARE NEW ITEMS: NOTE, GAS PLAN REVIEW WILL
 NOW BE A SEPERATE PLAN REVIEW BECAUSE OF THE SUBMITTED
 DRAWINGS.
  
 10. SHEET 3.0A PLUMBING PLAN DOES NOT REFLECT THE
 RESUBMITTED SANITARY RISER. PLEASE REFERENCE THE
 CORRECTED RED LINED SHEET AND PLEASE CORRELATE AND
 RESUBMIT.
  
 11. SHEET 3.0A SAITARY RISER: PLEASE DELETE THE RED
 LINED PIPING FOR THE DD ON THE RESUBMITTAL.
  
 12. SHEET 3.0A WATER RISER AND THE WATER HEATER
 DETAIL: PLEASE CORRELATE THE WATER HEATER P&T DRAIN
 LOCATION. WATER HEATER DETAIL INDICATES DRAIN TO
 EXTERIOR, AND WATER RISER INDICATES DRAIN TO MOP SINK.
  
 13. SHEET 3.0A WATER RISER: PLEASE DELETE THE
 FOLLOWING "INSTALL APPROVED SHOCK ARRESTOR @ EA.
 FIXTURE GROUP" AND ADD IN ITS PLACE THE FOLLOWING "
 WATER HAMMER ARRESTORS TO BE INSTALLED PER FBC-2004
 PLUMBING, SECTION 604.9."
  
 ******IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-16 Cont ID  
Sent By mperson Date 2007-01-16 Time 13:44 Rev Time 0.00
Received By mperson Date 2007-01-12 Time 13:44 Sent To  
Notes
2007-01-12 15:09:50DENIED
 REFERENCE: FBC-2004 PLUMBING, FBC-2004 CHAPTER 1, AND
 FBC-2004 CHAPTER 11
  
 NOTE: SEPERATE PLUMBING AND GAS PERMITS REQUIRED FOR
 THIS JOB
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW:
  
 1. THE TWO COPIES OF PRINTS NEED TO BE STAMPED AND THE
 TWO PAGE WORK SHEETS NEED TO BE COMPLETED AND ATTACHED
 TO PRINTS BY DPBR HOTEL AND RESTAURANT DIVISION ON THE
 RESUBMITTAL AND PER FBC-2004 CHAPTER 1 SECTION
 102.2.1.
  
 2. SHEET 1.1 OF 9 INDICATES "NO GREASE TRAP- WAIVER
 FROM CITY OF WEST PALM BEACH"
 NOTE: PER WASTE ORDINANCE #3434 FOR THIS WAIVER PLEASE
 CONTACT
 ENVIRONMENTAL COMPLIANCE MANAGER
 LYNN MASSON (561) 822-2271
 FAX (561) 822-2279
 E-MAIL [email protected]
  
 3. SHEET 1.0 OF 9 THE MEN AND WOMENS BATHROOM: NOTE PER
 FBC-2004 PLUMBING SECTION 405.3.1 AND FBC-2004 CHAPTER
 11 SECTION 11-4.16 FIG. 28; BATHROOM IS TO SMALL THE
 MINIMUM FINNISH REQUIRED IS FIVE FEET THREE INCHES
 (5'-3") NOT THE INDICATED FIVE FEET TWO INCHES (5'-2")
 INDICATED. PLEASE CORRECT ON THE RESUBMITTAL.
  
 4. SHEET 3.0A OF 9 SANITARY RISER DIAGRAM: A} PER
 FBC-2004 PLUMBING, SECTION 901.2.1 A VENT IS REQUIRED
 FOR THE MOP SINK. PLEASE CORRECT ON THE RESUBMITTAL. B}
 PER FBC-2004 PLUMBING, SECTION 708.3.5 TWO WAY CLEANOUT
 REQUIRED. PLEASE ADD THESE FOR THE RESUBMITTAL.
  
 5. SHEET 3.0A OF 9 WATER RISER: A} ADD A WATER HAMMER
 ARRESTOR TO THE ICE MACHINE PER FBC-2004 PLUMBING,
 SECTION 604.9. B} DELETE 3/8" C INDICATED BETWEEN THE
 BATHROOM AND ICE MACHINE. C} PLEASE CORRELATE THE
 FIXTURES BEING SUPPLIED ON THE WATER RISER WITH SHEET
 1.1 OF 9, EQUIPMENT PLAN ITEM NUMBERS ON THE
 RESUBMITTAL.
  
 6. SHEET 3.0A OF 9 PLUMBING NOTES: A} NOTE #8 DELETE
 1/8" FT. MIN. AND ADD IN ITS PLACE TABLE 704.1. B} NOTE
 #12 DELETE AIR CHAMBER PER FBC-2004 PLUMBING SECTION
 604.9.
  
 7. SHEET 1.1 OF 9 ITEM #22 WAREWASHER DRAIN NEEDS TO BE
 INDICATED ON SHEET 3.0A SANITARY AND WATER RISER
 DIAGRAMS AND PLUMBING PLAN. PER WEST PALM BEACH CODE
 SECTION 90-124 (7) B. GREASE INTERCEPTERS (SEPERATORS,
 GREASE TRAPS) ARE TO BE INSTALLED OUTSIDE OF THE FOOD
 PREPERATION AREAWITH THE DISHWASHER DISCHARGING VIA A
 SEPERATE LINE.
 NOTE: THERE IS NO INDICATION ON THE PRINTS ON HOW THIS
 UNIT IS TO DRAIN, OR HOW ITIS SUPPLIED WITH WATER.
 THE UNIT MUST DRAIN INTO THE SANITARY SYSTEM SEPERATE
 FROM THE GREASE WASTE. PLEASE CLARIFY THIS ON THE
 RESUBMITTAL.
  
 8. SHEET 3.0A OF 9 WATER HEATER DETAIL SAFEY PAN:
 PLEASE INDICATE THE FOLLOWING PER FBC-2004 SECTION
 504.7.1 PAN DRAIN SIZE AND PER SECTION 504.7.2 DRAIN
 TERMINATION ON THE RESUBMITTAL.
  
 9. PLEASE NOTE ELECTRICAL COMMENT #3 ON TITLE BLOCK
 REFLECTING METRO DESIGN GROUP PER FS 471.023, 481.229,
 FAC 61G15-23.002 AND CORRECT ON THE RESUBMITTAL.
  
 10. PRINTS INDICATE GAS APPLIANCES, THE FOLLOWING
 INFORMATION IS REQUIRED FOR GAS PLAN REVIEW TO MEET
 CODE COMPLIANCE:
 A} SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 B} SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C} TYPE OF GAS, (LP OR NATURAL)
 D} BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 E} SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 F} SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 G} INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H} SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 I} SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 J} CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K} CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 L} EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 2 Status N Date 2007-02-13 Cont ID  
Sent By jbabcock Date 2007-02-13 Time 16:56 Rev Time 0.00
Received By jbabcock Date 2007-02-13 Time 16:56 Sent To I
Notes
2007-02-13 16:57:36 
 ASSESSED VALUE IS $476,656 AND PERMIT VALUE IS
 $70,000.
  
 THEREFORE, SECTION94-212 (D) (5)"STOREFRONTS ARE
 REQUIRED ON THE NORTHWOOD ROAD FRONTAGE. STOREFRONTS
 SHALL BE DIRECTLY ACCESSIBLE FROM THE SIDEWALK. EACH
 STOREFRONT MUST HAVE CLEAR GLAZED AREAS, EQUAL TO A
 MINIMUM OF 70 PERCENT OF ITS FACADE, BETWEEN TWO AND
 EIGHT FEET FROM THE GROUND. IF THE COST OF A RENOVATION
 MEETS OR EXCEEDS 50 PERCENT OF THE ASSESSED VALUE PER
 THE COUNTY PROPERTY APPRAISER'S OFFICE OF THAT AFFECTED
 PORTION OF THE STRUCTURE PRIOR TO THE COMMENCEMENT
 THEREOF, THE RENOVATION MUST COMPLY WITH THE STOREFRONT
 CODE REQUIREMENT" IS NOT APPLICABLE.

Review Stop Z ZONING
Rev No 1 Status N Date 2007-01-16 Cont ID  
Sent By lmartine Date 2007-01-16 Time 11:02 Rev Time 0.00
Received By lmartine Date 2007-01-16 Time 11:02 Sent To  
Notes
2007-02-13 16:53:14REVIEW NOT REQUIRED PER ERIC, ANGELLA, AND LINDA
  
  
 ASSESSED VALUE IS $476,656 AND PERMIT VALUE IS
 $70,000.
  
 THEREFORE, SECTION94-212 (D) (5)"STOREFRONTS ARE
 REQUIRED ON THE NORTHWOOD ROAD FRONTAGE. STOREFRONTS
 SHALL BE DIRECTLY ACCESSIBLE FROM THE SIDEWALK. EACH
 STOREFRONT MUST HAVE CLEAR GLAZED AREAS, EQUAL TO A
 MINIMUM OF 70 PERCENT OF ITS FACADE, BETWEEN TWO AND
 EIGHT FEET FROM THE GROUND. IF THE COST OF A RENOVATION
 MEETS OR EXCEEDS 50 PERCENT OF THE ASSESSED VALUE PER
 THE COUNTY PROPERTY APPRAISER'S OFFICE OF THAT AFFECTED
 PORTION OF THE STRUCTURE PRIOR TO THE COMMENCEMENT
 THEREOF, THE RENOVATION MUST COMPLY WITH THE STOREFRONT
 CODE REQUIREMENT" IS NOT APPLICABLE.
2007-01-16 11:04:21REVIEW NOT REQUIRED PER ANGELA , ERIC ANDLINDA