Plan Review Details - Permit 06120094
Plan Review Stops For Permit 06120094
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-05-08 Cont ID  
Sent By jgomez Date 2008-05-08 Time 14:40 Rev Time 0.00
Received By jgomez Date 2008-05-08 Time 14:40 Sent To PC
Notes
2008-05-08 15:00:08BUILDING SUBMITTAL CHECKLIST.
  
 1- PROVIDE PRODUCT APPROVAL FOR ENTRY DOOR UNDER A
 SEPARATE PERMIT AS AGREED WITH OWNER (ELIZABETH
 DEWOODY)ON PROVISO DATED 4-20-07.PROVISO ALLOWED
 TO ISSUE THE HOUSE PERMIT WITHOUT HAVING TO PAY
 RE-SUBMITTAL FEES.PRODUCT APPROVAL SUBMITTED AT THAT
 TIME WAS NOT GOOD FOR 3'-6" X 8'-0" ENTRY DOOR AS SHOWN
 ON PLANS.
  
 ***NOTE: WHEN APPLYING FOR ENTRY DOOR SEPARATE
 PERMIT, PLEASE MAKE SURE THE FOLLOWING IS PROVIDED:
 2- PRODUCT APPROVAL SUBMITTED NOW STILLIS NOT GOOD
 FOR SIZE OF DOOR SHOWN ON PLANS. NEED TOPROVIDE
 PRODUCT APPROVAL FOR SIZE AND TYPE OF DOOR AS SHOWN ON
 PLANS.
  
 3- PRODUCT APPROVAL NEEDS TO BE REVIEWED AND APPROVED
 IN WRITING (NOT SIGNING AND SEALING)BY THE DESIGNER
 OF RECORD AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-04-01 Cont ID  
Sent By jgomez Date 2008-04-01 Time 10:08 Rev Time 0.00
Received By jgomez Date 2008-04-01 Time 10:08 Sent To  
Notes
2008-04-01 10:10:28PLANS RE-STAMPING.
  
 REMAINDER: PROVIDE INFORMATION REQUESTED ON PROVISO
 DATED 4-20-07 TO AVOID UNNECESSARY DELAYS. SEE ATTACHED
 COPY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-03-20 Cont ID  
Sent By jgomez Date 2008-03-20 Time 16:54 Rev Time 0.00
Received By jgomez Date 2008-03-20 Time 16:54 Sent To E
Notes
2008-03-20 17:00:12PLANS RE-STAMPING BUILDING REVIEW CHECKLIST.
  
 1- PLANS NEED TOHAVE ARCHITECT'S ORIGINAL SIGNATURE,
 NOT RUBBER STAMP.CHAPTER 481 FLORIDA STATUTE AND SEC.
 61G1-16.003 FLORIDA ADMINISTRATIVE CODE.
  
 2- REMAINDER: PROVIDE ALLITEMS REQUESTED ON PROVISO
 TO AVOID UNNECESSARY DELAYS. SEE ATTACHED PROVISO
 COPY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-06-05 Cont ID  
Sent By jgomez Date 2007-06-05 Time 10:51 Rev Time 0.00
Received By jgomez Date 2007-06-05 Time 10:04 Sent To Z
Notes
2007-06-05 10:52:25BUILDING REVISION OK.NEED TO PROVIDE INFORMATION
 REQUIRED ON PROVISO DATED 4/20/07.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-04-20 Cont ID  
Sent By jgomez Date 2007-04-20 Time 13:21 Rev Time 0.00
Received By jgomez Date 2007-04-20 Time 07:37 Sent To PC
Notes
2007-04-20 13:40:37BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE COMPLETE INFORMATION FOR ENTRY DOOR PRODUCT
 APPROVAL UNDER A SEPARATE PERMIT AS AGREED WITH THE
 OWNER (MRS. ELIZABETH DEWOODY) ON PHONE CONVERSATION.
  
 2- SURVEY WAS REVISED TO READ FLOOD ZONE B. CORRECT
 FLOOD ZONE IS A5. REVISE AS REQUIRED.
  
 3- SOIL TEST REPORT NEEDS TO HAVE FIRM'S CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BYSEC. 61G15-23.002
 OF FLORIDA ADMINISTRATIVE CODE.
  
 4- ALL ARCHITECT'S LETTERS TO HAVE ARCHITECT'S ORIGINAL
 SEAL, SIGNATURE AND DATE AS REQUIRED BY CHAPTER 481
 FLORIDA STATUTES. COPIES ARE NOT ALLOWED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-10 Cont ID  
Sent By jgomez Date 2007-04-10 Time 18:58 Rev Time 0.00
Received By jgomez Date 2007-04-10 Time 07:47 Sent To PC
Notes
2007-04-10 18:59:00BUILDING REVIEW SECOND CHECKLIST:
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 2- PROVIDE COPY OF IMPACT FEES PAID RECEIPT AS
 REQUESTED ON PREVIOUS CHECKLIST.
  
 3- FLAT ROOF NOA #04-0506.03:
 A) SPECIFY ON SHEET 16WHICH FASTENING OPTION IS
 GOING TO BE USED AS REQUIRED BY CITY POLICY FOR ROOFING
 PERMITS. SEE ATTACHED COPY.
  
 B) PROVIDE RAS 117 CALCULATIONS OR NAIL ENHANCING
 FOR PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. SEE PAGE 19 OF NOA SUBMITTED.
  
 4-DESIGNER OF RECORD NEED TO SPECIFY CONCRETE TILE
 SPECIFIC FASTENING AS REQUIRED BY SEC. 106.1.1.2 OF
 CITY AMENDMENTS TO FBC 2004. PRODUCT APPROVAL IS ONLY
 TO VERIFY THAT PRODUCT MEETS DESIGNER OF RECORDDESIGN
 CRITERIA.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) POCKET FRENCH SLIDING GLASS DOORS AS SHOWN ON
 PLANS.NOA #02-0306.01 SUBMITTED IS NOT FOR POCKET
 DOORS AND DOOR IS SMALLER THAN SIZE SPECIFIED ON PLANS.
 THEREFORE, IT DOESN'T WORK FOR THIS HOUSE.
  
 B) 3'-6" X 8'-0" INSWING ENTRY DOOR AS SHOWN ON
 PLANS.NOA #02-0129.10 SUBMITTED DOOR IS SMALLER THAN
 SIZE SPECIFIED ON PLANS AND NOA IS EXPIRED ALSO.
  
 C) FIXED WINDOWS. NOA #03-0428.03 SUBMITTED IS
 SUPERSEDED ACCORDING TO DADE COUNTY PRODUCT APPROVAL
 WEBSITE. SEE ATTACHED COPY. NEED CURRENT NOA.
  
 6- DESIGNEROF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALSAS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
 ***NOTE: DESIGNEROF RECORD TO MAKE SURE PRODUCT
 APPROVALS COVERTYPE AND SIZE OF PRODUCT SPECIFIED ON
 PLANS AND IS NOT EXPIRED TO AVOID FURTHER DENIALS AND
 EXPEDITE THE REVIEW PROCESS.
  
 7- PROVIDE COMPLETE SPECIFICATIONS AND UL LISTING FOR
 BBQ DESIGNED TO BE INSTALLED IN THE LOGGIA. OTHERWISE,
 DELETE FROM DRAWINGS AND APPLY FOR SUCH PERMIT AT TIME
 OF INSTALLATION.
  
 8- REVISE ALL SECTIONS/DETAILS THAT SHOW CORRECT RAIN
 DOWNSPOUTS TO COMPLY WITH SEC. R320.7 2004 FLORIDA
 RESIDENTIAL CODE.ILLUSTRATED RAIN LEADERS ARE NOT
 SHOWN CORRECTLY.
  
 9- CONNECTORS P AND O SHOWN ON SHEETS-2DON'T MEET
 THE UPLIFT LOADS SPECIFIED ON PLANS. REVISE/CLARIFY AS
 REQUIRED.
  
 10- SHEET S-4:
 A) CLARIFY GRAVITY LOADS. WHY ATTIC LIVE LOAD FOR
 ATTIC WITHOUT STORAGE IS NONCONCURRENT, WHILE ATTIC
 LIVE LOAD WITH STORAGE IS CONCURRENT. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 11- SOIL TEST REPORTTO HAVE ORIGINALENGINEER'S
 SIGNATURE,DATE AND THE ENGINEERING FIRM'S CERTIFICATE
 OF AUTHORIZATION NUMBER AS REQUIRED BY CHAPTER 471 AND
 FLORIDA ADMINISTRATIVE CODE SEC. 61G15-23.002.
  
 12-A) SURVEY TO HAVE ORIGINAL SIGNATURE, NOT COPY AS
 REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
 B) PROVIDE COMPLETE INFORMATION FOR FLOOD MAP,
 INCLUDING DATE OF MAP (MARCH 1ST. 1979).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-23 Cont ID  
Sent By jgomez Date 2007-01-23 Time 17:53 Rev Time 4.00
Received By jgomez Date 2007-01-23 Time 17:53 Sent To  
Notes
2007-01-23 17:55:52BUILDING REVIEW CHECKLIST:
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTES.
  
 2- PAY IMPACT FEES TO PALM BEACH COUNTY. NEED TO BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT.
  
 3- TRUSSES WILL BE REQUIRED FOR REVIEW PRIOR TO
 INSTALLATION. SEE SEC. R802.10 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR REQUIRED INFORMATION TO BE ON
 TRUSS DRAWINGS. DESIGNER OF RECORD TO REVIEW AND
 APPROVE THEM PRIOR TO SUBMITTAL.
  
 4- PROVIDE DRAINAGE PLANS AS REQUIRED BY SEC. R401.3
 2004 FLORIDA RESIDENTIAL CODE.
  
 ***NOTE: SEE SURVEY FOR FINISH FLOOR ELEVATIONS ON
 ADJACENT PROPERTIES AND PROPOSED FINISH FLOOR ELEVATION
 FOR THIS HOUSE TO AVOID DIVERTING WATER TO ADJACENT
 PROPERTIES.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FLAT ROOF SYSTEM. SEE ATTACHED COPY OF CITY
 POLICY FOR ROOFING PERMITS FOR REQUIRED INFORMATION.
 FOR FLAT ROOF SYSTEMS NEED TO SELECT SPECIFIC APPROVED
 ASSEMBLY AND FASTENING OPTION. IN ADDITION CHECK IF
 SYSTEM IS LIMITED BY GENERAL LIMITATION #7 OR #9
 (LIMITATION #9 CAN'T BE INSTALLED IN THIS AREA) AND
 PROVIDE REQUIRED INFORMATION ALSO. SEE GENERAL
 LIMITATIONS ON PRODUCT APPROVAL SUBMITTED.
  
 B) POCKET FRENCH SLIDING GLASS DOORS AS SHOWN ON
 PLANS.
  
 C) PARALAM BEAMS AS SHOWN ON PLANS.
  
 D) PRECAST LINTELS AS SHOWN ON PLANS.
  
 E) CONCRETE FLAT ROOF TILE.NOA 01-0417.09 EXPIRED
 ON 06/07/2006.NEED CURRENT PRODUCT APPROVAL. ALSO,
 SPECIFY TILE FASTENING. IF USING POLYFOAM FOR
 ATTACHMENT, THEN PROVIDE PRODUCT APPROVAL FOR
 POLYFOAM.
  
 F) GARAGE DOOR. ES LEGACY REPORT #2318 SUBMITTED
 STATES THAT THIS REPORT BELONGS TO FLORIDA PRODUCT
 APPROVAL FL674. THERE ARE NOT RECORDS FOR FL674.GO TO
 WWW.FLORIDABUILDING.ORG TO VERIFY INFORMATION. PROVIDE
 CURRENT GARAGE DOOR PRODUCT APPROVAL.
  
 G) 3'-6" X 8'-0"***INSWING*** MAHOGANY ENTRY DOOR
 AS SHOWN ON PLANS.
  
 H) 3'-0" X 6'-8"***INSWING*** ENTRY DOOR AT GUEST
 SUITE AS SHOWN ON PLANS.
  
 I) ENTRY DOOR SIDELITES.
  
 J) DOOR AND WINDOW STRUCTURAL MULLIONS AND SPECIFY
 FASTENING.
  
 K) FIXED WINDOWS AS SHOWN ON PLANS.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 7- PROVIDE MANUFACTURER'S SPECS THAT ALLOWS DECORATIVE
 CHIMNEY CAPS. THEN, PROVIDE COMPLETE SPECS SUCH AS
 CLEARANCES, MATERIALS ETC. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 8- PROVIDE COMPLETE STRUCTURAL SECTION THRU FIREPLACE
 AND CHIMNEY. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 9- PROVIDE COMPLETE SPECIFICATIONS AND UL LISTING FOR
 BBQDESIGNED TO BE INSTALLED IN THE LOGGIA. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 10- SHEET A-0:A) NAME OF SOIL TEST ENGINEER DOESN'T
 MATCH NAME OF COMPANY WHO SUBMITTED THE SOIL TEST
 REPORT. REVISE AS REQUIRED.
  
 B) NAME OF SURVEYOR DOESN'T MATCH NAME OF SURVEYOR
 WHO SUBMITTED SURVEY. REVISE AS REQUIRED.
  
 C) PROPOSED FINISH FLOOR ELEVATIONS DON'T MATCH
 PROPOSED FINISH FLOOR ELEVATIONS SHOWN ON SURVEY.
 REVISE EITHER ONE TO MATCH.
  
 11- SHEET A-1:NOTE BY LOGGIA AREA CALLS FOR CENTER
 LINE OF FIREPLACE AND CABANA DOORS. WHERE IS THE
 FIREPLACE?. REVISE AS REQUIRED.
  
 12-PROVIDE HANDRAIL AND GUARDRAILS DETAILS SHOWING
 DESIGN LOADS COMPLIANCE AS REQUIRED BYSEC. 1607.7.1
 FBC 2004 AND SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 13- CONTRACTOR'S WORKER'S COMPENSATION INSURANCE IS
 EXPIRED. UPDATE INFORMATION WITH PERMIT CLERK.
  
 14- EXTERIOR ELEVATIONS, WALL SECTIONS AND DETAIL CALL
 FOR DIFFERENT ROOF SHEATHING SIZE. SOME CALL FOR 3/4"
 PLYWOOD AND SOME CALL FOR 5/8" PLYWOOD. REVISE THEM ALL
 AS REQUIRED TO MATCH.
  
 15- SPECIFY FIREBLOCKING INALL WALL SECTIONS AS
 REQUIRED BY SEC. R602.8 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 16- PROVIDE COMPLETE SPECS AND INSTALLATION FOR
 COLONIAL SHUTTERS SHOWN ON ELEVATIONS.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004 ANDSEC. R301 FOR WIND
 LOADS. AND, CLARIFY IF DECORATIVE SHUTTERS OR
 STRUCTURAL SHUTTERS. STRUCTURAL SHUTTERS REQUIRE
 PRODUCTAPPROVAL AND COMPLETE INSTALLATION SCHEDULE.
  
 17- PROVIDE ATTIC VENTILATION CALCULATIONS AND VENT
 SIZES AND LOCATION TO COMPLY WITH SEC. R806 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 18- PROVIDE SPECIFICATIONS FOR GARAGE INTERIOR DOOR TO
 COMPLY WITH SEC. R309.1 2004 FLORIDA RESIDENTIAL CODE.
  
 19- PROVIDE SPECIFICATIONS FOR RAIN DOWNSPOUTS TO
 COMPLY WITH SEC. R320.7 2004 FLORIDA RESIDENTIAL CODE.
  
 20-MASTER WALK-IN-CLOSET; SPECIFY SIZE OF ATTIC
 ACCESS TO COMPLY WITH SEC. R807 2004 FLORIDA
 RESIDENTIAL CODE.
  
 21- WALL SECTIONS: SPECIFY MINIMUM FOOTING DEPTH BELOW
 GRADE AND MINIMUM. HEIGHT ABOVE GRADE AS REQUIRED BY
 SEC. R403.1.4ANDSEC. R404.1.6OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 22- WINDOW AND DOOR DETAILS ON SHEET A-12 DON'T APPLY
 TO THIS JOB. DELETE AS REQUIRED.PROVIDE ONLY THE
 DETAILS THAT APPLY TO THIS JOB.
  
 23- SHEET S-2:A) THERE ARE SOME DETAILSTHAT ARE
 KEYED FOR SHEET S-6. THERE IS NOT SHEET S-6. REVISE AS
 REQUIRED.EG: 3/S-6 AND 4/S-6.
  
 B) CONNECTORS M AND N ARE FOR WOOD TO WOOD
 CONNECTIONS. NEED TO SPECIFY WOOD TO MASONRY CONNECTORS
 AS REQUIRED.SEE SIMPSON CATALOGUE FOR PROPER MASONRY
 CONNECTOR AND TYPE AND NUMBER OF FASTENERS.OTHERWISE,
 PROVIDE COMPLETE ENGINEERING ANALYSIS FOR CONNECTORS
 AND FASTENERS THAT ARE DIFFERENT THAN THOSE TESTED AND
 PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 C) SPECIFY SPECIFIC SIMPSON HANGER FOR STAIRS 2X12
 CARRIAGES.
  
 D) SPECIFY CONNECTORS FOR GIRDER TRUSSES ENDS BY
 STAIRWAY AND GIRDER TRUSS END BYFAMILY ROOM AREA. SEE
 PLANS FOR COMMENTS.
  
 24- SHEET S-3:A) COORDINATE LOCATION OF ATTIC ACCESS
 BY MASTER BEDROOM WITH ARCHITECTURAL DRAWINGS.
  
 B) WHERE ARE DETAILS 2/S-6. THEREIS NOT SHEET
 S-6.
  
 C) SPECIFY UPLIFT LOAD AND CONNECTOR FOR GIRDER
 TRUSS RESTING ON CHIMNEY SIDE. SEE PLANS FOR COMMENTS.
  
 D) CLARIFY DETAIL 4/S-5 KEYED ON LEFT BOTTOM CORNER
 OF GUEST SUITE ROOF.DETAIL 4/S-5 IS FOR A BUCKET
 DETAIL. CLARIFY/REVISE AS REQUIRED.
  
 E) SPECIFY LEDGER SIZE AND FASTENERS AROUND CHIMNEY
 TO RECEIVE ROOF TRUSSES. SEE PLANS.
  
 25- SHEET S-4:A) REVISE STRUCTURAL NOTES. CLEARLY
 INDICATE DESIGN CRITERIA AS REQUIRED BY SEC. R301 OF
 2004 FLORIDA RESIDENTIAL CODE. INCLUDE ALL LOADS
 INCLUDING LIVE AND DEAD LOADS. AND, ATTIC LIVE LOADS
 FOR ATTIC WITH STORAGE AND ATTICS WITHOUT STORAGE AS
 REQUIRED BY TABLE R301.5 2004 FLORIDA RESIDENTIAL CODE.
 SPECIFY ALL LOADS. EG:ALL DEAD LOADS PLUS 30PSF LIVE
 LOAD FOR ROOF IS NOT PROVIDING ALL NECESSARY
 INFORMATION. REVISE ALL INFORMATION AS REQUIRED.
  
 B) INCLUDE 2004 FLORIDA RESIDENTIAL CODE WHICH IS
 THE CODE THAT APPLIES TO ONE AND TWO FAMILY DWELLINGS.
  
 C) NOTE I REFERS TO SOIL TEST REPORT BY ARDAMAN AND
 ASSOCIATES. THIS IS NOT THE SOIL TEST REPORT SUBMITTED
 WITH PLANS. REVISE/COORDINATE AS REQUIRED. SEE PROVIDED
 SOIL TEST REPORT.
  
 26- ENERGY CALCULATIONS:A) REVISE CONDITIONED AREA TO
 MATCH ARCHITECTURAL DRAWINGS.
  
 B) REVISE UNDER ATTIC AREA. SEE ARCHITECTURAL
 PLANS.
  
 C) CLARIFY WHERE ARE THE SINGLE ASSEMBLY AREAS.
  
 D) REVISE INFORMATION ON TOP OF FORM.THE
 PERMITTING OFFICE IS WEST PALM BEACH NOT PALM BEACH
 COUNTY AND THE CORRECT JURISDICTION # IS 604700 NOT
 601000.
  
 27- SURVEY SUBMITTED;A) SURVEY TO HAVE ORIGINAL
 SIGNATURE (NOT COPY) AS REQUIRED BY CHAPTER 472 FLORIDA
 STATUTES.
  
 B) PROPERTY IS LOCATED ON FLOOD ZONE "B" NOT "A5".
 SEE MAP DATED MARCH 1, 1979.REVISE AS REQUIRED.
  
 C) PROVIDE COMPLETE INFORMATION FOR FLOOD MAP.
 INCLUDE SUFFIX AND DATE OF MAP .
  
 D) SURVEY IS MISSING THE DIMENSIONS FOR THE COVERED
 REAR PORCH.
  
 28- SOIL TEST REPORT SUBMITTED: A) ENGINEER TO PROVIDE
 ORIGINAL SIGNATURE, NOT COPY AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES AND FLORIDAADMINISTRATIVE CODE.
  
 B) NEED THE FIRM'S CERTIFICATE OF AUTHORIZATION
 NUMBER IN THE LETTERHEAD AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2008-11-12 Cont ID  
Sent By btrobaug Date 2008-11-12 Time 15:14 Rev Time 0.00
Received By btrobaug Date 2008-11-12 Time 15:02 Sent To PC
Notes
2008-11-12 15:06:36 
  
 REVISION DENIED
  
 THE PLANS SUBMITTED FOR RESTAMP ARE IN FACT A REVISION.
 A CHANGE WAS HAND DRAWN IN THE BATHROOM (106) AND NOT
 NOTED IN THE REVISION BOX.
 ALSO ATTACHED ARE COMMENTS FROM THE LAST REVISION FROM
 DEWEY PALMER, THE ELECTRICAL REVIEWER OF RECORD. DIRECT
 FURTHER COMMUNICATIONS TO HIM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-04-10 Cont ID  
Sent By dpalmer Date 2008-04-10 Time 10:34 Rev Time 0.00
Received By dpalmer Date 2008-04-10 Time 10:34 Sent To PC
Notes
2008-04-10 10:36:07REDLINED DISCONNECT PER 110.26.
  
 STILL NEED REVISED PLANS FOR FINAL INCLUDING REVISED
 PANEL SCHEDULES FOR CIRCUITS ETC. 408.4, 240.4, 310.16

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-04-10 Cont ID  
Sent By dpalmer Date 2008-04-01 Time 08:34 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2008-04-10 08:34:54ELEC FOR RE-STAMP ONLY.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-03-21 Cont ID  
Sent By dpalmer Date 2008-03-21 Time 09:07 Rev Time 0.00
Received By dpalmer Date 2008-03-21 Time 09:07 Sent To M
Notes
2008-03-21 09:07:48** DENIEDREVIEW **
  
  
 1) NOTE:PLANS ARE BEING SUBMITTED FOR RE-STAMP ONLY.
 PLEASE SEE FLORIDA STATUTES 481.221 AS A *RUBBER-STAMP*
 MAY NOT BE USED IN LIEU OF ORIGINAL SIGNATURE.
 PLEASE BE SURE TO SUBMIT PLANS ACCORDINGLY.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-05-18 Cont ID  
Sent By dpalmer Date 2007-05-18 Time 16:46 Rev Time 0.00
Received By dpalmer Date 2007-05-18 Time 16:38 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-04-17 Cont ID  
Sent By dpalmer Date 2007-04-17 Time 12:01 Rev Time 0.00
Received By dpalmer Date 2007-04-17 Time 12:01 Sent To M
Notes
2007-04-17 12:02:05REDLINED A/C DISC TO BE PER 110.26
 PLANS OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-21 Cont ID  
Sent By dpalmer Date 2007-03-21 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2007-03-21 Time 07:55 Sent To M
Notes
2007-03-21 12:59:37 
 ** UNSAT **
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE
 AIC RATINGS FOR THE SERVICE EQUIPMENT AND PLANS NOW
 INDICATE THE RATINGS FOR THE PANELS ONLY. PLEASE
 INDICATE THE RATINGS FOR MAINS ALSO.
 110.9
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE RISER WHICH SHOWS PANEL A-1 AS 100A
 AND PANEL A-1 WHICH IS SHOWN AS 150AMP.
 PLEASE CORRELATE.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE THAT THE IDENTIFICATION OF THE
 RECESSED LIGHTS WAS ADDED HOWEVER ONLY FOR THE IC
 RATING. PLEASE SEE THE SECTION AS STATED ALSO REQUIRES
 FIXTURES TO BE AIR TIGHT.
 FBC 13-606.1.ABC.1.2.4
  
 4) NOTE: PLEASE CLARIFY WHERE THE RECESSED LIGHTING IS
 FIGURED INTO THE LOAD CALCULATIONS AT THE MAXIMUM
 NUMBER OF FIXTURES TIME THE NUMBER OF FIXTURES?
 220.3B4
  
 5) NOTE: PLEASE SEE THE PANEL SCHEDULE WHICH STILL LIST
 MANY CIRCUITS AS *GENERAL*.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM
 THE NEC COMMENTARY FOR 408.4.
  
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 PLEASE KNOW IF THIS WAS THE ONLY COMMENT THIS COULD
 HAVE BEEN REVISED, HOWEVER PLEASE INDICATE THE
 ESTIMATED LOCATIONS AT THIS TIME PER DESIGNER. IT IS
 KNOWN THAT THESE WILL MOST LIKELY BE INSTALLED
 DIFFERENTLY AND MAY BE REVISED AT A LATER DATE.
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
  
 ** PLEASE KNOW THAT SOME OF THESE COMMENTSWERE MADE
 FROM THE PREVIOUS REVIEW AND SOME MAY HAVE BEEN
 REDLINED OR SET UP AS A PROVISO, HOWEVER SOME CAN NOT.
 PLEASE ADDRESS ALL AT THIS TIME AND IF THERE ARE ANY
 COMMENTS, QUESTIONS, PLEASE CALL TO GO OVER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-06 Cont ID  
Sent By dpalmer Date 2006-12-06 Time 09:16 Rev Time 0.00
Received By dpalmer Date 2006-12-05 Time 19:12 Sent To Z
Notes
2006-12-06 09:16:04**** UNSAT ****
  
 1) NOTE: PLEASE SEE THAT PLANS SHALL STATE THE
 FOLLOWING MINIMUM CODES.
 2002 NFPA-70 (NEC), 2002 NFPA-72.
  
 2) NOTE: PLEASE INDICATE THE MINIMUM AIC RATINGS FOR
 ALL SERVICE EQUIPMENT. IT IS NOTED THAT THE SUB PANELS
 INDICATE 10K , HOWEVER MAINS SHOULD CONTAIN THE MINIMUM
 RATINGS ALSO.
 PLEASE SEE 110.9 FBC 106.1.2 ADMIN SECTION.
  
 3) NOTE: PLEASE SEE PLANS INDICATE A/F PROTECTION AS
 EACH RECEPTACLE, HOWEVER BASED ON THE CODE AS STATED ON
 E-3 AND IN 210.12B, THE PROTECTION IS FOR THE BRANCH
 CIRCUIT. PLEASE KNOW IT IS NOT KNOWN TO THIS OFFICE AT
 THIS TIME THAT A AF TYPE RECEPT IS MANUFACTURED.
  
 4) NOTE: PLEASE INDICATE THE GFI PROTECTION FOR THE
 JACUZZI/WHIRLPOOL TUB. 680.71
  
 5) NOTE: PLEASE SEE MISSING RECEPTS PER 210.52. (2FT OF
 WALL IN BEDROOM #2 REDLINED).
 PLEASE CHECK OTHER LOCATIONS, HOWEVER PLANS SEEM TO
 INDICATE ALL REQUIRED.
  
 6) NOTE: PLEASE SEE 210.52C3 FOR MISSING PENINSULAR GFI
 RECEPTACLE REQUIRED. (REDLINED)
  
 7) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE
 DEVICES IN A DWELLING. PLEASE KNOW IN A RECENT SECTION
 MEETING WITH NFPA, THE DESIGNATION OF THESE DEVICES
 SHOULD BE AS FOLLOWS. PLEASE KNOW IF THE DEVICE IS 120V
 WHICH DETECTS AND SOUNDS AND ALARM, THEN THIS DEVICE
 WOULD ACTUALLY NOW BE SHOWN A "SA" FOR SMOKE ALARM. IF
 THE DEVICE IS LOW VOLTAGE AND PART OF ALV SECURITY OR
 LV FIRE ALARM SYSTEM , THEN DEVICE WOULD BE ONLY A "SD"
 FOR SMOKE DETECTOR AS IT ONLY DETECTS AND WILL CAUSE
 AND ALARM THROUGH OTHER SOUNDING DEVICES. PLEASE KNOW
 THAT SD HAS BEEN THE ACCEPTED PRACTICE FOR MANY YEARS
 THROUGH THIS AHJ, HOWEVER AS OF RECENT INFORMATION IF
 INDEED THESE DEVICES ARE 120V SMOKE ALARMS, PLEASE
 CHANGE THE DESIGNATIONS ON PLANS, NOTES AND SYMBOL
 LEGEND.
  
 8) NOTE: PLEASE ADJUST NOTES PERTAINING TO THE RELEVANT
 CODES. PLEASE SEE NFPA-72 11.5.1.1 AND 11.8.3 DICTATES
 THE PLACEMENT.
 PLEASE SEE THAT THE SA DEVICE SHALL BE LOCATED WITHIN
 12INCHES OF THE HIGHEST POINT ON A FLAT/TRAY CEILING
 AND WITHIN 3FT ON SLOPED ONLY CEILING. PLEASE KNOW, IF
 THE TRAY IS 12INCHES OR MORE IN DEPTH, THE SA DEVICE
 SHALL BE RELOCATED.
  
 9) NOTE: PLEASE SEE AREA AT THE TOP OF THE STAIRS WHICH
 SHOWS ONLY ONE SMOKE DEVICE. PLEASE KNOW DUE TO THE
 DISTANCE AND LOCATION SHOWN, PLEASE EITHER ADD ONE UNIT
 OR MOVE THE EXISTING TO BE CLOSER AND IN MORE OF THE
 IMMEDIATE VICINITY OUTSIDE BEDROOMS #3 AND MASTER
 BEDROOM.
 NFPA-72 11.5.1.1
  
 10) NOTE: PLEASE SEE ANY POSSIBLE ZONING COMMENTS FOR
 ANY CHANGES OR ACCESS REQUIREMENTS FOR THE GUEST SUITE
 LOCATED IN THE REAR. PLEASE KNOW THESE COMMENTS MAY OR
 MAY NOT AFFECT THE ELECTRICAL PLANS GREATLY.
  
 11) NOTE: PLEASE INDICATE THE ACTUAL RATING OF THE
 METER MAIN COMBO. PLEASE ALSO SHOW THIS E-1 PLAN
 LAYOUT.
 PLEASE SEE MISSING PANEL A-1 ON PLANS. THIS SUB PANEL
 COULD NOT LOCATED ON LOWER OR UPPER FLOORS. PLEASE SEE
 110.26,240.24 ETC
 FBC 106.1.2 ADMIN SECTION.
  
 12) NOTE: PLEASE SEE PANEL SCHEDULES FOR BRANCH
 CIRCUITING SHOULD BE MORE SPECIFIC TO AREAS IN WHICH
 THEY FEED. IE: B-23 MASTER BRM LTS, A-1 KITCHEN LTS.
 ETC
 PLEASE KNOW IT IS KNOW THAT DURING THE CONSTRUCTION
 THESE WILL MOST LIKELY CHANGE HOWEVER MINIMUMS SHALL BE
 SHOWN AT THIS TIME.
 PLEASE SEE 210.52B1 FOR DINING ROOMS AND AREAS OF THE
 LIKE.
 PLEASE SEE 240.4,310.16, 408.4.
 FBC ADMIN SECTION, 106.1.2, 106.3.5.4 PAR(8).
  
 13) NOTE: PLEASE INDICATE RECESSED LIGHTING IN LOAD
 CALCULATIONS PER 220.3B4, PLEASE KNOW THIS MANY
 FIXTURES CAN NOT BE CONSIDERED AS PART OF THE GENERAL
 LIGHTING LOADS.
  
 14) NOTE: PLEASE INDICATE THE REQUIREMENTS FOR AIR
 TIGHT RATED FIXTURES AS REQUIRED PER FBC
 13-606.1.ABC1.2.4
  
 15) NOTE: PLEASE CORRELATE THE A/C'S. PLEASE SEE PANEL
 SCHEDULES SHOW 3-10KW AHU'S AND LOAD CALCULATIONS
 INDICATE 4-10KW SYSTEMS?
 PLEASE SEE MECHANICAL PLANS WHICH INDICATE 2-15KW
 SYSTEMS AND ONE 5KW.PLEASE KNOW BASED ON THE MAXIMUM
 PERMITTED OVER CURRENT PROTECTION REQUIRED AND THE
 AMOUNT OF LOADS ETC AS SHOWN ON THE M-SHEETS, IF THESE
 UNITS ARE INSTALLED, THIS WILL GREATLY AFFECT THE
 ELECTRICAL BRANCH CIRCUIT RATINGS. PLEASE CORRELATE AND
 ADJUST AS THE EXACT SIZES CAN NOT BE VERIFIED AT THIS
 TIME.
 310.16, 240.4, 424.3B, 424.22(A) AND (B).
  
 16) NOTE:PLEASE INDICATE POOL PUMP AS FUTURE AS IT IS
 NOT BEING INSTALLED AT THIS TIME. THIS CAN BE REVISED
 AT A LATER DATE, OR IF POOL IS NOT BUILT DURING HOUSE
 CONSTRUCTION THIS WILL NOT HAVE TO BE REVISED LATER.
  
 17) NOTE: PLEASE SEE PANEL "A" WHICH SHOWS TWO
 DEDICATED CIRCUITS FOR GARAGE DOOR OPENERS, YET PLANS
 ONLY INDICATE ONE GDO RECEPT ON PLANS?
 PLEASE CORRELATE.
 FBC 106.1.2 ADMIN SECTION
 408.4. NEC.
  
 18) NOTE: PLEASE CLARIFY THE LOCATION OF THE
 DISCONNECTSSHOWN ON THE CU'S ETC. PLEASE SEE IN ORDER
 TO CHANGE OUT THE EQUIPMENT, THE DISCONNECTBEING
 MOUNTED DIRECTLY ON THE EQUIPMENT WOULD CREATE SOME
 INTERFERENCE WIHT THIS.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-06 07:02:23REVIEW COMMENCED
2006-12-05 19:12:18IN ELEC FOR REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-10-30 Cont ID  
Sent By adarroug Date 2008-10-30 Time 15:13 Rev Time 0.00
Received By adarroug Date 2008-10-30 Time 15:13 Sent To M
Notes
2008-10-30 15:14:09TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-05-05 Cont ID  
Sent By adarroug Date 2008-05-05 Time 16:46 Rev Time 0.00
Received By adarroug Date 2008-05-05 Time 16:46 Sent To B
Notes
2008-05-05 16:47:15TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 11:21 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 11:21 Sent To E
Notes
2008-04-08 11:22:44TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-03-25 Cont ID  
Sent By mmiller Date 2008-03-25 Time 09:38 Rev Time 0.00
Received By mmiller Date 2008-03-25 Time 09:38 Sent To M
Notes
2008-03-25 09:38:34ROUTED TO HAROLD MOSER'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-03-20 Cont ID  
Sent By adarroug Date 2008-03-20 Time 09:58 Rev Time 0.00
Received By adarroug Date 2008-03-20 Time 09:58 Sent To B
Notes
2008-03-20 09:59:11TO "JGOMEZ" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-16 Cont ID  
Sent By adarroug Date 2007-05-16 Time 11:01 Rev Time 0.00
Received By adarroug Date 2007-05-16 Time 11:01 Sent To  
Notes
2007-05-16 11:01:49TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 16:44 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 16:44 Sent To E
Notes
2007-04-16 16:44:39TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-20 Cont ID  
Sent By adarroug Date 2007-03-20 Time 11:10 Rev Time 0.00
Received By adarroug Date 2007-03-20 Time 11:10 Sent To E
Notes
2007-03-20 11:10:59TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 10:20 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 10:20 Sent To Z
Notes
2007-03-16 10:20:54TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-23 Cont ID  
Sent By jgomez Date 2007-01-23 Time 17:56 Rev Time 0.00
Received By jgomez Date 2006-12-05 Time 14:35 Sent To  
Notes
2006-12-05 14:35:31TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-11-13 Cont ID  
Sent By rkussner Date 2008-11-13 Time 14:57 Rev Time 0.00
Received By rkussner Date 2008-11-13 Time 14:57 Sent To  
Notes
2008-11-13 14:58:42***LANDSCAPE REVIEW PASSED WITH PROVISO***
  
 FOUR (4) TREES SHALL BE INSTALLED WITHIN 45 DAYS FROM
 THE DATE OF C/O.---RAK

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-11-05 Cont ID  
Sent By tgordon Date 2008-11-05 Time 13:54 Rev Time 1.00
Received By tgordon Date 2008-11-05 Time 13:54 Sent To  
Notes
2008-11-05 13:55:31REVISION TO MECHANICAL PLANS, ENERGY CAL'S. AND COOLING
 LOAD CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2008-10-31 Cont ID  
Sent By tgordon Date 2008-10-31 Time 15:49 Rev Time 0.30
Received By tgordon Date 2008-10-31 Time 15:49 Sent To  
Notes
2008-10-31 16:03:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS
 *** DENIED ***
  
 1) THE ZONES FOR SYSTEM 1 AND 2 HAVE CHANGED, ALSO THE
 SIZE OF SYSTEM 2 IS LARGER. THE COOLING LOAD
 CALCULATIONS FOR ZONES 1 AND 2 NEED TO BE REVISED, PER
 2004 FBC 13-607.1.ABC.1.
  
 2) THE SUPPLY AIR DUCT FROM AHU #3 TO THE MIXING BOX
 AND FROM THAT MIXING BOX TO THE NEXT MIXING BOX, NEEDS
 TO BE SIZED (SEE YELLOW HIGH LIGHT ON PLAN) PER 2004
 FBC/M 603.1 AND 603.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2008-10-23 Cont ID  
Sent By tgordon Date 2008-10-23 Time 14:15 Rev Time 0.30
Received By tgordon Date 2008-10-23 Time 14:15 Sent To  
Notes
2008-10-23 14:19:54RE-STAMP
 *DENIED*
  
 1) PLANS ARE A REVISION.
  
 2) MECHANICAL PLANS ON FILE ARE SIGNED AND SEALED BY
 ARCHITECT (ROGER P JANSSEN) ONLY HE CAN MAKE REVISIONS
 TO THEM, SEE FAC 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-04-01 Cont ID  
Sent By tgordon Date 2008-04-01 Time 11:28 Rev Time 0.40
Received By tgordon Date 2008-04-01 Time 11:28 Sent To  
Notes
2008-04-01 11:30:19RE-STAMP PLANS. SENT TO LUIS M.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-03-25 Cont ID  
Sent By hmoser Date 2008-03-25 Time 17:00 Rev Time 0.00
Received By hmoser Date 2008-03-25 Time 17:00 Sent To  
Notes
2008-03-25 17:20:59PLAN DENIED
 PLANS MUST BE STAMPED BY THE ARCHITECTS, OR A LETTER
 FROM DAILEY JANSSEN ARCHITECTS RELIEVEING HINSELF FROM
 THE MECHANICAL PART OF THE JOB.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-03-21 Cont ID  
Sent By tgordon Date 2008-03-21 Time 11:04 Rev Time 0.25
Received By tgordon Date 2008-03-21 Time 11:04 Sent To P
Notes
2008-03-21 11:09:23PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** RE-STAMP OF PLANS **
 *** DENIED ***
 1) THE ARCHITECT MUST SIGN WHEN SEALING PLANS (WET
 SIGNATURE NOT RUBBER STAMP) PER FAC 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-04-17 Cont ID  
Sent By tgordon Date 2007-04-17 Time 14:15 Rev Time 0.30
Received By tgordon Date 2007-04-17 Time 14:15 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-26 Cont ID  
Sent By tgordon Date 2007-03-26 Time 12:14 Rev Time 0.25
Received By tgordon Date 2007-03-26 Time 12:14 Sent To P
Notes
2007-03-26 12:21:18*** DENIED ***
 1) AS NOTED IN LAST REVIEW 12-16-07 NOTE #6. SEE
 MECHANICAL PLANS PAGE M-1. THE 12" RETURN AIR TRANSFER
 DUCT FROM THE PLAYROOM TO THE BREAKFAST AREA NEEDS TO
 BE 14".
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING TO ACHIEVE
 PROPER RETURN AIR BALANCE. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-11 Cont ID  
Sent By tgordon Date 2006-12-11 Time 15:20 Rev Time 0.45
Received By tgordon Date 2006-12-11 Time 15:20 Sent To B
Notes
2006-12-11 15:33:28*** DENIED ***
 1) THE MECHANICAL PLANS NEEDS THE ARCHITECT'S SEAL ON
 THEM AS HIS INFORMATION IS IN THE TITLE BLOCK, PER FAC
 61G1-16.003.
  
 2) SEE ELECTRICAL REVIEW NOTE #15, PLEASE CORRECT.
  
 3) SEE PAGE M-2 SECOND FLOOR, SHOWER ROOM BETWEEN THE
 TWO BEDROOMS NEEDS AN EXHAUST FAN, SEE 2004 FBC/R
 M1506.1.
  
 4) RETURN AIR DUCT TO AHU #3 NEEDS TO BE SIZED, SEE
 HIGH LIGHT ON PAGE M-2.
  
 5) TWO RETURN AIR DUCTS TO AHU #1 NEED TO BE SIZED
 (PLEASE DO NOT USE PENCIL).
  
 6) 12" RETURN AIR TRANSFER DUCT FROM PLAYROOM TO
 BREAKFAST AREA NEEDS TO BE 14". BALANCED RETURN AIR MAY
 BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-04-01 Cont ID  
Sent By jleech Date 2008-04-01 Time 14:17 Rev Time 0.00
Received By jleech Date 2008-04-01 Time 14:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-03-27 Cont ID  
Sent By jleech Date 2008-03-27 Time 08:16 Rev Time 0.00
Received By jleech Date 2008-03-27 Time 08:14 Sent To  
Notes
2008-03-27 08:19:04DENIED;
 SEE ELECTRICAL AND BUILDING PLAN REVIEW. PLANS MUST BE
 SIGNED NOT COPYS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-06-04 Cont ID  
Sent By jleech Date 2007-06-04 Time 10:36 Rev Time 0.00
Received By jleech Date 2007-06-04 Time 10:36 Sent To  
Notes
2007-06-04 10:38:25PROVISO;
  
 OUTSIDE SHOWER TO DRAIN TO PLANTED AREA OR FRENCH
 DRAIN, NOT TO SANITARY.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-02 Cont ID  
Sent By jleech Date 2007-04-02 Time 09:43 Rev Time 0.00
Received By jleech Date 2007-04-02 Time 09:43 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-09 Cont ID  
Sent By jleech Date 2006-12-09 Time 07:56 Rev Time 0.00
Received By jleech Date 2006-12-09 Time 07:55 Sent To M
Notes
2006-12-09 08:08:28DENIED;
 1. WATER HEATER DETAIL; SHUTOFF VALVE REQUIRED UP
 STREAM OF THE EXPANSION TANK. PAGE A-1 SHOWS A TANKLESS
 GAS WATER HEATER WHERE IS WATER HEATER IN DETAIL
 LOCATED? IF RECIRC. SYSTEM IS USED ADD NOT INDICATING
 INSULATION MATERIAL TO BE USED AROUND PIPES TO COMPLY
 WITH FLORIDA ENERGY CODE.
 2. RISER DIAGRAM; UP STAIRS LAUNDRY WASHER AND L/T
 CANNOT DISCHARGE THROUGHABATHROOM GROUP SECTION
 909.1.
 3. ADD NOTE TO PAGE A-1 " OUTSIDE SHOWER TO DRAIN TO
 GRASSY AREA OR DRYWELL"
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2007-06-05 Cont ID  
Sent By choops Date 2007-06-05 Time 13:45 Rev Time 0.00
Received By choops Date 2007-06-05 Time 13:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-03-19 Cont ID  
Sent By kdfreema Date 2007-03-19 Time 18:22 Rev Time 0.00
Received By kdfreema Date 2007-03-19 Time 18:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-07 Cont ID  
Sent By mmclean Date 2006-12-07 Time 10:46 Rev Time 0.00
Received By mmclean Date 2006-12-07 Time 10:46 Sent To M
Notes
2006-12-07 11:51:08DENIED,
 1. PLEASE PROVIDE THE DIMENSION OF THE PROPOSED
 DRIVEWAY AND WALKWAY (LENGTH & WIDTH).
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF LANDSCAPE,
 WHICHEVER IS LESS WITHIN THE FIRST 25FT FRONT SETBACK.
  
 NOTE: MUST PULL A SEPARATE PERMIT FOR THE POOL/SPA
  
 NOTE: POOL EQUIPMENT SHALL BE NO CLOSER THAT 6FT FROM
 THE SIDE SETBACK.SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE THAN FOUR FEET
 INTO A SETBACK.
  
 NOTE: MUST PULL A SEPARATE PERMIT FOR THE
 GATE/COLUMNS/FENCE/PIERS WITH EASEMENT APPROVAL FROM
 THE CITY OF WEST PALM BEACH UTILITIES DEPT.
  
 2. THE PROPOSED GUEST ROOM MUST HAVE INTERIOR ACCESS
 FROM THE FIRST FLOOR. STRUCTURE CANNOT BE RENTED OUT AS
 A SEPARATE LIVING SPACE WITHIN THE MAIN STRUCTURE, SF7.
 ELEVATON PLANS ALSO SHOWS THE STAIRS EXTERIOR FOR
 ACCESS TO THE GUEST ROOM.
  
 3. PLEASE SHOW ON THE ELEVATION PLAN THE FINISH GRADE.
 THE MAXIMUM HEIGHT ALLOWED IS 33FT WITH CHIMNEY.
  
 4. THE PROPOSED GUTTER WITH ROOF CAN ONLY PROJECT 3FT
 INTO SETBACK. SEC 94-305(2).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  
  
  
  
  