Plan Review Details - Permit 06120064
Plan Review Stops For Permit 06120064
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-22 Cont ID  
Sent By adarroug Date 2007-01-22 Time 16:16 Rev Time 0.00
Received By adarroug Date 2007-01-22 Time 16:16 Sent To M
Notes
2007-01-22 16:16:26TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 11:08 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 11:08 Sent To M
Notes
2007-01-09 11:08:28TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-08 Cont ID  
Sent By tgordon Date 2006-12-08 Time 09:06 Rev Time 0.00
Received By tgordon Date 2006-12-05 Time 10:03 Sent To  
Notes
2006-12-05 10:03:48TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-01-23 Cont ID  
Sent By tgordon Date 2007-01-23 Time 14:03 Rev Time 0.30
Received By tgordon Date 2007-01-23 Time 14:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-01-09 Cont ID  
Sent By tgordon Date 2007-01-09 Time 14:49 Rev Time 0.30
Received By tgordon Date 2007-01-09 Time 14:49 Sent To  
Notes
2007-01-09 14:57:11*** DENIED ***
 1) AS NOTED IN LAST REVIEW 12-8-06. NEE TO SHOW AN
 EQUIPMENT LISTING ON PLANS ( A/H AND COND. UNIT, MAKE,
 MODEL NUMBER, SEER, TOTAL AND SENSIBLE BTU'S, HEATER
 KW).
  
 2) BEFORE PICKING UP PERMIT YOU WILL NEED TO FILE A
 NOTICE OF COMMENCEMENT, PER F. S. 713.13 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-08 Cont ID  
Sent By tgordon Date 2006-12-08 Time 09:07 Rev Time 0.30
Received By tgordon Date 2006-12-08 Time 09:07 Sent To  
Notes
2006-12-08 09:17:09*** DENIED ***
 1) SHOW A EQUIPMENT LISTING WITH ALL PERTINENT
 INFORMATION ON THE MECHANICAL PLANS.
  
 2) NEED TO SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS.
  
 3) NEED TO SHOW THE SIZE OF THE GRILLS FOR THE RETURN
 AIR TRANSFER DUSTS.
  
 4) NEED TO SHOW THE SIZE OF ALL THE RETURN AIR TRANSFER
 DUCTS BALANCED RETURN AIR.
 MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.