Plan Review Details - Permit 06120040
Plan Review Stops For Permit 06120040
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-03 Cont ID  
Sent By shill Date 2007-01-03 Time 16:48 Rev Time 0.00
Received By shill Date 2007-01-03 Time 16:48 Sent To PC
Notes
2007-01-03 17:03:17****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)DECLARE GOVERNING CODE, INCLUDING FBC 2004
 EXISTING BUILDING CODE.
  
 3.)DECLARE LEVEL OF ALTERATION, FBC EXISTING BUILDING
 CODE CH 3.
  
 4.)PROVIDE WIND DESIGN CRITERIA FBC1603.1.4.
  
 5.)PROVIDE A CODE SUMMARY; BUILDING TYPE FBC CHAPTER
 5 INCLUDING A OR B, OCCUPANCY FBC 3, SPRINKLED OR
 UNSPRINKLED, BUILDING HEIGHT.
  
 6.)D1, A COLUMN IS SHOWN WITH THE NOTE "REMOVE
 EXISTING DRYWALL TO FRAMING SYSTEM."HOW IS FIRE
 RATING AFFECTED?WAS THE BUILDING BUILT AS PROTECTED
 OR UNPROTECTED, AND IS THIS STRUCTURAL?
  
 7.)D1, ON TENANT SEPARATION WALLS THERE IS A NOTE
 "REMOVE EXISTING DRYWALL TO FRAMING."HOW WILL THE 1
 HOUR TENANT SEPARATION BE MAINTAINED?PROVIDE A TESTED
 ASSEMBLY OR CALCULATED FIRE RESISTANCE.
  
 8.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 9.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-19 Cont ID  
Sent By dpalmer Date 2006-12-19 Time 07:34 Rev Time 0.00
Received By dpalmer Date 2006-12-18 Time 20:11 Sent To  
Notes
2006-12-19 07:35:03 
 **** UNSAT ****
  
 1) NOTE: PLEASE INDICATE THE CIRCUITING FOR THE
 LIGHTING, FANS AND HOW THEY ARE BEING CONTROLLED.
 PLEASE ALSO INDICATE IF THERE IS AN EXISTING OR NEW
 SIGN CIRCUIT. 600.5, 220.3(B)(6).
 FBC 106.1.2 ADMIN SECTION.
  
  
 2) NOTE: PLEASE COMPLETE INFORMATION AS REQUIRED ON
 TITLE BLOCK FOR THE MISSING PRINTED NAME OF THE
 ARCHITECT OF RECORD PER FLORIDA ADMINISTRATIVE CODE
 61G1-16.004.
 PLEASE ALSO SEE PRINT OUT ATTACHED FROM THE FLORIDA
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
 WHICH INDICATES THE CERTIFICATE OF AUTHORIZATION NUMBER
 AS LISTED ON THE TITLE BLOCKS IS THAT OF A COMPANY
 DIFFERENT FROM WHICH IS LISTED AND SHOWN ON SAID TITLE
 BLOCKS.
 PLEASE SEE NUMBER AS LISTED IS FOR A FIRM LOCATED OUT
 OF NEW YORK WHICH HAS BEEN ACTIVE SINCE 1977.
  
 ** PLEASE KNOW ONE COPY OF PLANS ARE BEING RETAINED BY
 THIS OFFICE UNTIL FURTHER INFORMATION IS PROVIDED FROM
 THE FLORIDA BOARD OF ARCHITECTS AND THE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2006-12-18 20:11:59IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-22 Cont ID  
Sent By mawillia Date 2006-12-22 Time 15:46 Rev Time 0.00
Received By mawillia Date 2006-12-22 Time 15:46 Sent To  
Notes
2006-12-22 16:21:40*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND / OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY RESPONDER ACCESS TO
 THE SAID PROPERTY OR PROPERTIES IN THE VICINITY THEREOF
 (INCLUDING FIRE LANES).
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.SHOW/DISPLAY THE SUITE NUMBER ON THE BUILDING TO BE
 VISIBLE FROM SOUTH ROSEMARY AVENUE.AS PER WEST PALM
 BEACH CODE, SUITE/TENANT SPACE NUMBERS SHALL BE NO LESS
 THAN 3" IN HEIGHT AND 1" IN WIDTH.COORDINATION WITH
 CITYPLACE MANAGEMENT MAY BE NEEDED TO MAITAIN
 CONSISTENCY AS TO THE SIZE AND STYLE OF CHARACTERS.
  
 6.SUBMITTED PLANS AND APPLICATION REFLECT THAT THE
 SCOPE OF WORK IS FOR STOREFRONT ALTERATION ONLY,
 HOWEVER, DOORS WITH PANIC HARDWARE WILL BE REQUIRED IN
 OCCUPANCY OF 100 OR MORE PERSONS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-03 Cont ID  
Sent By shill Date 2007-01-03 Time 17:03 Rev Time 0.00
Received By shill Date 2006-12-04 Time 11:52 Sent To  
Notes
2006-12-18 14:27:22TO "COMM" BD#5
2006-12-06 17:01:14ROUTED TO JROACH
2006-12-04 11:54:22WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 1 Status P Date 2006-12-07 Cont ID  
Sent By eschneid Date 2006-12-07 Time 09:19 Rev Time 0.00
Received By eschneid Date 2006-12-07 Time 09:19 Sent To I
Notes
***NONE***