Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-14 Cont ID  
Sent By btrobaug Date 2006-12-14 Time 16:13 Rev Time 0.50
Received By btrobaug Date 2006-12-14 Time 16:01 Sent To M
Notes
2006-12-14 16:13:34 
  
 INCOMPLETE INFORMATION
  
 PLEASE SUBMIT THE MANUFACTURE'S INFORMATION ON
 RECOMMENDED SETBACKS FROM STRUCTURES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-12-18 Cont ID  
Sent By mperson Date 2006-12-18 Time 10:14 Rev Time 0.45
Received By mperson Date 2006-12-18 Time 10:14 Sent To B
Notes
2006-12-18 11:14:36DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE NOTE THAT THERE IS AN OPEN GAS PERMIT FOR
 THE SAID RESIDENCE. THE OPEN GAS PERMIT IS#06020480
 AND IT IS ATTACHED TO MASTER PERMIT #04101257 WHICH ARE
 SIGNED AND SEALED DRAWINGS. THE SUBMITTED GAS DRAWING
 FOR THE GENERATOR SHOULD BE SUBMITTED AS A REVISION TO
 THE GAS PERMIT AND IT SHALL BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD FOR THE MASTER PERMIT #04101257.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: PLEASE INDICATE THE PIPING MATERIALS.
  
 3. TYPE OF GAS, (LP OR NATURAL) MUST BE INDICATED ON
 DRAWINGS.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: PLEASE REFERENCE THE ATTACHED PERMIT INFORMATION
 INDICATING GAS AT SAID RESIDENCE. THE BTU LOAD OF THE
 EXISTING AS WELL AS THE PROPOSED GENERATOR NEEDS TO BE
 INDICATED ON THE RESUBMITTED GAS REVISION.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS INCLUDES THE EXISTING AS WELL AS PROPOSD.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: PLEASE SUBMIT MANUFACTURER SHEETS AND
 INSTALLATION INSTRUCTIONS OF THE PROPOSED GENERATOR
 WITH SETBACKS FROM STRUCTURES. MORE INFORMATION IS
 REQUIRED FROM THE SUBMITTED MANUFACTURER SHEETS SUCH AS
 THE NAME OF THE MANUFACTURER, THE SIZE OF THE
 GENERATOR, AND THE BTU LOAD. IF GAS DELIVERY PRESSURE
 INCREASES TO 2PSI PLEASE INCLUDE MANUFACTURER SHEETS OF
 THE MP REGULATORS. END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-12 Cont ID  
Sent By adarroug Date 2006-12-12 Time 18:09 Rev Time 0.00
Received By adarroug Date 2006-12-12 Time 18:09 Sent To E
Notes
2006-12-12 18:10:15TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 11:18 Sent To  
Notes
2006-12-04 11:19:06TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-15 Cont ID  
Sent By tgordon Date 2006-12-15 Time 08:58 Rev Time 0.20
Received By tgordon Date 2006-12-15 Time 08:58 Sent To P
Notes
2006-12-15 09:00:34*** DENIED ***
 1) SEE ZONING REVIEW, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-09 Cont ID  
Sent By mmclean Date 2006-12-09 Time 17:12 Rev Time 0.00
Received By mmclean Date 2006-12-09 Time 17:12 Sent To I
Notes
2006-12-09 17:15:10DENIED.
 1. PLEASE SUBMIT TWO COPIES OF FULL SURVEYS OF THE
 PROPOSED. THIS MUST SHOW THE EXISTING STRUCTURE WITH
 SETBACKS AND LOCATION OF THE PROPOSED GENERATOR WITH
 DISTANCE FROM PROPERTY LINE.
 2. THE HALF BLOWN UP ELECTRICAL PLANS WILL NOT BE
 ACCEPTABLE FOR A REVIEW.
 3. PLEASE PROVIDE THE DIMENSION OF THE PROPOSED
 GENERATOR.
  
 NOTE: SEC 94-303 MECHANICAL/POOL EQUIPMENT/GENERATOR
 MAY NOT PROJECT MORE THAN FOUR FEET INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved